Download presentation
Presentation is loading. Please wait.
Published byMarsha Long Modified over 9 years ago
1
WESP FUNCTIONS REMOVAL OF FUMES AND MIST CREATED DURING FRYING PROCESS. FUMES-GAS MIST- SOLIDS REDUCE POLLUTANTS TO ATMOSPHERE REDUCE HEAT IN BUILDING REMOVES SMOKE FROM BUILDING.
2
GENERAL LAYOUT DUCTWORK/DAMPER SECTION QUENCH CHAMBER 5’x60’ WATER SPRAYS CYCLONE WITH WATER SPRAYS E-TUBES/GRID 189 10”x 13’ CENTER PROBES W/15 ELECTRODE DISKS FLOOR WASH DEMISTER PADS I D FAN 68,800 ACFM @ 155 F EXHAUST STACK 6’x60’
3
PUMPING SYSTEMS RECYCLE PUMP Constant flow through sprays. FLUSH PUMP Intermittent cleaning sprays. TRANSFER PUMP Floor sump to recycle tank. GORMAN RUPP SUMP PUMP from overflow sump to fume room sump. SKIMMER DIAPHRAGM PUMP from recycle tank to fume room sump. OUTSIDE SUMP DIAPHRAGM PUMP (Located by inside sump pump) Pumps from outside apron sump to inside sump.
4
RECYCLE and FLUSH SYSTEM PRIMARY RECYCLE SYSTEM RECIRCULATES THROUGH WHOLE SYSTEM FROM 6000 GALLON TANK. FLUSH SYSTEM WASHES INTERNAL AREAS FROM 800 GALLON TANK AT 3 HOUR INTERVALS. (Approx. 350 Gal. per flush) MAKE UP WATER IS ADDED TO RECYCLE AND FLUSH TANKS TO MAKE UP FOR EVAPORATION AND SKIMMER.
5
WESP LAYOUT DRAWING