Communication Aided Protection Schemes
Pilot Relay Schemes Tribhuwan Choubey – SCE/TDBU/ECQ SCE Property
2
Introduction Relays at the Transmission terminals talk with each other using telecommunication media. Pilot relays do not pick up for faults outside their defined zone of protection. Pilot relays pick up instantaneously for faults within their defined zone of protection. For increased reliability some type of backup protection is also provided SCE Property
3
2- Zone Distance Relay SCE Property
4
Pilot relay telecommunication
SCE Property
5
Relay communication Leased Telephone Line ( 56 or 64kbps over copper)
Power Line Carrier (PLC – 64kbps) – Twisted copper wire for 2/ 3 terminals Microwave or UHF radio (Multiplexed – mbits/ sec DS1 signal – 24 channels) Dedicated Optical Fiber (Single Mode – 10 miles or Multi mode – 60 miles) SONET (Multiplexed Symmetrical Optical Network - Synchronous) T1 Multiplexing – mbits/ sec (Asynchronous – voice and data communication) SCE Property
6
Microwave Tower SCE Property
7
Microwave Tower SCE Property
8
Microwave Telecom Equipment
Microwave Radio frequency spectrum: , , and MHz Operation: Two frequency duplex operation Telecom Equipment: Transmitters, Receivers, Order wires, Filters, Power Supplies, switching devices Microwave RF Apparatus specifications: T-8505 Carrier Frequency and Bandwidth : FCC Rules and 94.71 Frequency Stability: FCC rules 94.67 Baseband I/O level: < -35dBm/ -15dBm per channel Power Supply: 48V DC SCE Property
9
Microwave Telecom Equipment
Each terminal is equipped with hot standby transmitter. Switching circuitry is bilateral in between transmitters The input to the receivers from the antenna is connected through an RF Hybrid Switching time for manual operation < 20 msec. Switching time for automatic operation < 25 msec. Operation of either or both of these switches cause a “Guard” or “Off Normal” lamps Hot standby operation of Transmitters and Receivers allows uninterrupted operation on failure of one equipment SCE Property
10
SONETcommunication SONET - Synchronous Optical Network SCE Property
11
SONET Data Service SCE Property
12
Fiber optic communication
SCE Property
13
Fiber optic Data Losses
SCE Property
14
T1 Extended Super Frame SCE Property
15
Categories of Pilot Relaying
Following categories of protection schemes are typically applied in pilot relaying. Phase comparison Directional comparison blocking Remote tripping Transfer trip Line differential SCE Property
16
Pilot Relaying Philosophy
500 KV Pilot Relaying Schemes: Redundant Pilot relaying systems Redundant Transfer Trip relaying systems One set of electromechanical relays as backup protection system. Mix of communication system like Power Line Carrier (PLC) and Microwave are used for communication redundancy SCE Property
17
Pilot Relaying Philosophy
220 KV Pilot Relaying Schemes: One Pilot relaying systems One set of electromechanical relays or another Pilot relaying scheme with microwave as communication channel are used as backup protection system Mix of communication system like Power Line Carrier (PLC) or Microwave are used for communication redundancy SCE Property
18
Pilot Relaying Philosophy
Principle of Differential Relaying is applied for instantaneous tripping for in zone faults Four wires, normally termed as Pilot Wires, run in between substations to compare current between terminals (Typical F/C 15ms – 25ms) HCB Relays from Westinghouse (ABB) are predominantly used as Pilot relays for lines up to 20 miles. HCB relay contains Sequence filters, DC polar unit with Operating and Restraining coils, Insulating and Saturating Transformers SCE Property
19
Differential Relaying Philosophy
SCE Property
20
Pilot Relaying Philosophy
SCE Property
21
Pilot Relaying Philosophy
Westinghouse (ABB) LCB relays are used for Pilot Relaying for Transmission lines from 20 to 250 miles length. The communication medium is Fiber Optics The relay contains Sequence Filter, Transmitter Modulator ( 1 Ph -> FM), Receiver De Modulator (FM –> 1Ph), Phase comparison Unit (compare currents at Local/ Remote terminal) For out of zone fault, the signals would be out of phase and in phase for fault in the zone. SCE Property
22
Pilot Relaying Philosophy
SCE Property
23
Phase Comparison Relaying
Relay combination used with phase comparison systems are SLD or SKBU carrier relaying and CO( Residual Ground)/ ICC (Directional ground). Phase comparison relaying compares current phasors at local and remote terminals. Line and Neutral potential are not required. Faults in the protected zone would cause the currents to trip in less than 3 cycles Fault detector turns on carrier signal during Fault Transmitter generates blocking pulse during negative half cycle. During external fault both transmitters produce additive blocking pulse for the full cycle. During internal fault out of phase pulse cancel blocking pulse, allowing the relay to trip. SCE Property
24
Phase Comparison Relaying
SPCU relays are used for Phase comparison for Phase and Phase to Ground faults Microwave is used for communication of current phasors. Guard signals are transmitted for communication health. Relay trips in 9 cycles on loss of guard signal. Noise on communication channel will block tripping. SRU/ UIO as auxiliary relay for annunciation purpose Directional comparison blocking ( SLYP/ SLYN) compares current direction at both terminals to determine in zone or out of zone faults to block tripping SLYP provides Zone1 element ( 80% of line: instantaneous trip with TT), Zone2 (125% of Line) (Instantaneous for in zone fault and TT or blocking signal for out of zone faults) and Zone3 (180% of line sends blocking signal out of zone faults) SLYN provides Directional overcurrent, trip for in zone faults and block for out of zone faults SCE Property
25
DCB Philosophy Impedance relays trip instantaneously for z1 faults covering 80% of line Over reaching impedance relays with z2 faults operate with time delay covering 125% of the line Directional comparison Blocking (DCB) allows over reaching relays to trip instantaneously by blocking out of zone faults Thus Phase Distance Relays and ground over current relays can provide instantaneous protection for in zone faults Only one Communication channel is used for sending blocking signal only , used with PLC schemes SCE Property
26
DCB Relaying Philosophy
SCE Property
27
Typical Transfer Trip Relaying
Transfer Trip schemes are another flavor of Directional comparison schemes, where two relays communicate to trip rather than block. The two frequencies transmitted through two communication channels are: Guard frequency to keep guard relays closed to block tripping over channel noise Tripping Frequency to allow tripping relay to pickup and trip circuit breakers Basic Transfer trip Schemes: Direct Transfer Trip (DTP) Direct Overreaching Transfer Trip (DOTT) – 125% Direct Under reaching Transfer Trip (DUTT) – 80% Permissive Transfer Trip Permissive Overreaching Transfer Trip (POTT) – 125 % Permissive Under reaching Transfer Trip (PUTT) –80% SCE Property
28
Typical PUTT Relaying Scheme
Typical PUTT Relaying Scheme would have following components: 3 GCX (Directional Distance Relays ( Z1, Z2 and Z3 protection) Z2 and Z3 timer provides backup delayed tripping to POTT 1 JBCG directional Ground Relays 2 Transmitter and Receiver systems 2 Transfer Trip communication channels 1 Ground Fault detector relay (SC) 1 HD Balance relay to be used as backup for Transfer Tripping Trip signal at Remote terminal is enabled only when both transmitters are keyed to trip simultaneously, if Local and Remote permissive trip signal is available Loss of Guard signal for six cycles continuously will disable the channel equipment and if it continues for more than 2 seconds resulting into alarm and if alarm is continuous, then the relays are made inactive SCE Property
29
PUTT Relaying Philosophy
SCE Property
30
Typical POTT Relaying Scheme
Typical POTT Relaying Scheme would have following components: 3 CEY (Impedance relay with zone 2 timer- starts at fault detection) 1 SLYG directional Ground Relays 2 GE Type 40 Transmitter and Receiver systems 2 Transfer Trip communication channels (Primary/ Secondary) When a terminal receives the shift from Guard to trip frequency and a trip signal is present from Local relay, the local CB will trip Zone 2 timer is reset after the fault is cleared If zone 2 timer times out it will trip the local CBs irrespective of Tone signals from receiver to provide a backup protection If the fault is out of zone, then relay at the remote terminal will not pickup and removes the Guard frequency, preventing local relay to trip Loss of Guard signal for six cycles continuously will disable the channel equipment and continuous alarm will deactivate the relays SCE Property
31
POTT Relaying Philosophy
SCE Property
32
Digital POTT Relaying Scheme
Some of the new microprocessor based relays being used in the industry are as follows: D60 Hybrid POTT Relays from GE L90 Differential with DTT from GE PLC Transfer Trip via RFL-9780 MW Transfer Trip via RFL-9745 FO Transfer Trip via RFL-9745 SEL 421 – POTT/ DTT with PLC from Schweitzer Electric SEL-311L – Differential with DTT from Schweitzer Electric SEL-311C – POTT from Schweitzer Electric Communication Details: Serial RS485 communication Port Ethernet full duplex network Modbus communication Protocol IEC61850 communication data architecture Communication speed 9600MB/sec SCE Property
33
Issues in Relay Communication
Optical fiber cable damage or too high output from communications interface causes loss of channel signal alarm and may need attenuation or proper splice tray connection. T1 communication standard (DS1) requires transmittal of at least one pulse within any eight bit sequence. Loss of synchronization and unlocked frequency clocks could result in frame slips. Resulting in data loss. Leased Phone Lines need CSU channels as demarcation point between vendor and customer’s communication terminals. Interference on the cable/ CSU may cause loss of signal. SCE Property
34
Issues in Relay Communication
High induced voltages across pilot wire possibly caused by faults or lightning could cause induced fluxes and rise in ground voltage. This is remediated through provision of neutralizing reactors, voltage limiting circuits or surge suppressors. Open or shorted pilot wires are monitored and resulting erroneous trip signals are blocked. SCE Property