 R2 Four Basic Components of a Refrigeration System #4 Metering Devices.

Similar presentations


Presentation on theme: " R2 Four Basic Components of a Refrigeration System #4 Metering Devices."— Presentation transcript:

1  R2 Four Basic Components of a Refrigeration System #4 Metering Devices

2  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 2 Metering Devices Feed refrigerant to evaporator Provide pressure drop From high side to low side

3  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 3 Thermostatic Expansion Valves TEVs can vary the amount of refrigerant Responds to suction line temperature

4  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 4 Courtesy of Sporlan Valve Co. Sweat connections External equalizer Inlet Outlet Head Body Cap for Adjuster Thermostatic Expansion Valve (TEV)

5  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 5 SPORLAN Wire from electronic controller Motorized head Body Outlet Inlet Courtesy of Sporlan Valve Co. Electronic Expansion Valve

6  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 6 Fixed Metering Device Provides consistent pressure drop Condensing pressure to evaporator pressure

7  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 7 Fixed orifice capillary tube Courtesy of Supco Sealed Unit Parts Co. Fixed orifice capillary tube (cap tube)

8  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 8 Courtesy of Rob Dohse Carrier Training Center Valve body Metering Device End cap Carrier’s Accurator® Fixed orifice nozzle

9  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 9 TEV Cut-Away View Shows internal parts of a TEV

10  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 10 Valve Construction Valve Construction: Diaphragm, tube, and sensing bulb Valve body Needle and orifice Inlet Screen Spring, adjuster, and packing gland

11  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 11 TEV Operation Meters refrigerant Maintains superheat Opening force: Bulb pressure Closing forces: 1. Evaporator pressure 2. Adjustable spring

12  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 12 Expansion Valve Detail RETURN AIR 75 o EVAPORATOR 40º 50º Typical A/C Using R22 69 psig 278 psig SPORLAN

13  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 13 Expansion Valve Detail RETURN AIR 75 o EVAPORATOR 40º 50º Typical A/C Using R22 69 psig 278 psig R22 @ 50º = 84 psig Pressure on diaphragm Evaporator pressure @ 40º = 69 psig closing pressure Spring pressure to maintain equilibrium is: 84 psig – 69 psig = 15 psig

14  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 14 Adjusting Superheat To lower superheat: Decrease spring pressure Increases refrigerant in evaporator

15  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 15 Lower Superheat from 10° to 6° RETURN AIR 75 o EVAPORATOR 50º 40º 46º 69 psig 278 psig Superheat Adjustment Back out adjuster one full turn

16  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 16 Adjusting Superheat Increase superheat: Increase spring pressure Decreases refrigerant in evaporator

17  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 17 Raise Superheat from 6° to 14° RETURN AIR 75 o EVAPORATOR 40º 46º 54º 69 psig 278 psig 40º Superheat Adjustment Screw in adjuster two full turns

18  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 18 Identifying the Valve Connections: Flare, sweat, and flanged Evaporator Pressure Equalization: Internal equalizer External equalizer

19  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 19 Flare Sweat Flanged External equalizer Internal equalizer External equalizer Expansion Valve Connections

20  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 20 Sensing Bulb Placement Must sense true suction temperature –Not bottom of pipe –Not top of pipe Following are Sporlan’s recommendations

21  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 21 ≥ 7/8” Factory Recommended TEV Bulb Placement If pipe OD is greater than or equal to ( ) 7/8” then bulb should be placed at 4:00 or 8:00 (≥)

22  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 22 Factory Recommended TEV Bulb Placement If pipe OD is less than (<) 7/8” then bulb can be placed anywhere between 8:00 and 4:00 < 7/8”... but never on the bottom!

23  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 23 Simplifying bulb location Following is a simple rule for bulb placement

24  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 24 “Rule of Thumb” TEV Bulb Placement Warmer vapor on top Oil insulates bottom Bulb mounted on side works well on all pipes

25  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 25 More suggestions on bulbs Make sure it is on a flat surface of pipe Use stainless steel hose clamps: –Easier to install –Easy to service

26  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 26 Picture of bulbs and clamps TEV Bulb Straps Coupling Braze Joints No Bulb Contact Good Bulb Contact Radiato r Clamp

27  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 27 More on Mounting TEV Bulbs Best on horizontal line If you must put on vertical line: Oil in line may affect operation Cap tube must come out top of bulb

28  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 28 TEV Bulb on Vertical Line SPORLAN

29  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 29 TEV Bulb on Vertical Line System Off Start Up Oil pushed up sides of pipe Oil collects in P-trap SPORLAN

30  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 30 TEV Bulb Mounted Upside Down Liquid Flows to Head of Valve No Liquid In Bulb to Boil Off SPORLAN

31  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 31 “Reading” a Valve Understand the numbering system, and you will know the valve. Following are examples of Sporlan valves

32  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 32 Picture of SVE-2-GA valve “S” style valve “V” R22 “E” externally equalized “2” Two Tons (24,000 Btu) “G” Air Conditioning

33  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 33 Picture of GV-1/2-C Valve “G” type valve “V” R22 “1/2” ton (6,000) Btu “C” Commercial (medium temp.)

34  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 34 Capillary tubes (cap tubes) A fixed metering device Regulates refrigerant flow by pressure drop Pressure drop is based on: Cap tube length Internal diameter of tubing

35  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 35 Hose Pressure 25’ of hose 200’ of hose 75 psig 25 psig 100 psig 100 psig

36  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 36 Picture of Supco capillary tube.040” I.D. Courtesy of Supco Sealed Unit Parts Co.

37  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 37 Plugged cap tubes Beaded desiccant in most filter driers Desiccant can plug cap tube inlet Solution: Cut off some cap tube Replace filter drier

38  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 38 Correcting Plugged Cap Tube Beaded Desiccant Powder flakes off beads Clogs inlet of cap tube Replace Drier Cut off an inch or two of cap tube to remove clog

39  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 39 Cap tube guidelines Following is an information sheet from J/B Industries Interesting points are highlighted in yellow

40  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 40 Factors Affecting Refrigerant Flow capillary tubes depend on their length as well as their diameter to determine their total restriction. changing the diameter by.005" as between.026" I.D. and.031" I.D. can double the flow. The longer the tube, the slower the flow, the shorter the tube, the faster the flow.

41  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 41 Cap tube sizing J/B has charts for sizing cap tubes The following example is a 1/3 H.P. unit Operating at a 15° evaporator The cap tube size is.o36” I.D., 6’ long

42  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 42 Refrigeration Application Chart (R-12 & R- 22) R-22 H.P.REF +5 to +20 6 Ft TC-36 1/3

43  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 43 Cutting cap tubes  Do not use tubing cutters  Use a file to score it, then snap it  J/B also makes special cutters

44  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 44 Cap tube file and Cutter A10972 CAP TUBE FILE Specially designed to cut and open tube. File notch around tubing at desired cutting point. Snap tube by bending at notch. Clean burrs by reaming out with special file tip. In cleaning or deburring, always hold tube downward to keep small particles from entering tube. A10973 CAP CUTTING TOOL Specially designed to cut all sizes of soft and many sizes of hard drawn cap tubes. WORKING WITH CAPILLARY TUBING Every precaution possible should be taken to prevent chips, dirt, flux, moisture, filings, etc. from entering the system when changing the cap tube. Cap tube is sealed and dehydrated from the factory. Remember, most cap tubes have very small holes... it doesn't take much to plug them. The A10972 Cap Tube File and A10973 Cap Tube Cutter are specifically designed tools for working with cap tube.

45  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 45 What is existing cap tube size? J/B has a tool to check cap tube size

46  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 46 The A10971 Cap Tube Gauge accurately measures a full range of capillary tube sizes. Correct tube size is determined by using both the I.D. and O.D. dimensions. Check OD of tube in "V" slot. Compare OD with reference chart printed on back of gauge to determine probable ID. Use pin gauge to confirm actual size of ID. This same means of cross referencing can be used whenever two standard I.D.'s are very close or OD's are the same. DETERMINING CAP TUBE SIZE

47  © 2004 Refrigeration Training Services - R2 Subject 4 Metering Devices v1.2 47