Download presentation
Presentation is loading. Please wait.
1
Chilled-Water Systems
Fundamentals of H V A C R Third Edition Chapter 81 Chilled-Water Systems If this PowerPoint presentation contains mathematical equations, you may need to check that your computer has the following installed: 1) MathType Plugin 2) Math Player (free versions available) 3) NVDA Reader (free versions available) Copyright © 2017, 2013, 2010 Pearson Education, Inc. All Rights Reserved
2
Objectives (1 of 3) 81.1 Describe the difference between a flooded and a dry (direct expansion) type chiller Explain why low-pressure chillers need purge recovery Explain why some chillers are better suited for air- cooled condensers while others operate with water-cooled condensers.
3
Objectives (2 of 3) 81.4 List the different types of compressor arrangements found on chillers Describe the function of a chiller economizer Describe the operation for an oil-return system for a chiller Transfer refrigerant to and from a chiller.
4
Objectives (3 of 3) 81.8 Explain how an absorption chiller operates.
5
Introduction (a) Chilled-water cooling loop from central unit to multiple zones; (b) glycol and chilled- water piping connections to air handler The more common way to deliver refrigerant to individual air handlers is to use a secondary refrigerant such as chilled water. The chilled water is cooled in a central station chiller by a primary refrigerant. The chilled water is then delivered throughout the building to individual air handlers by circulating pumps.
6
Flooded and Dry-Type Water Chillers
Chilled-water cooling loop for cooling coil Centrifugal compressor chiller The water in a chiller is cooled to approximately 43–45°F. The chilled-water pump circulates the chilled-water supply (CHWS) to the cooling coil in the air handler. The chilled-water loop will have an expansion tank and fill connections for makeup water, and it will also have air vents, balancing valves, and cooling coil flow controls,
7
Purge Recovery Units and Air-Cooled Condensers
Centrifugal compressor suction-side rupture disk A low-pressure chiller will operate with a negative suction pressure that is below atmospheric. Any leaks in the system will draw in air. This air typically collects in the top section of the condenser. The air will increase the discharge pressure of the unit and lead to higher compressor power consumption. The air will also contain water that will oxidize the oil in the system and lead to the formation of sludge and acids. Chillers of this type generally have some type of purge recovery unit. Never allow a low-pressure chiller to reach or exceed the rupture disk setting when testing for leaks. The rupture disk setting for low-pressure chillers is normally set at 15 psig, but it is advisable not to exceed 10 psig. If this happens, then the chiller rupture disk will release and all of the refrigerant in the unit will be lost.
8
Air-Cooled Condensers (1 of 2)
Package chiller with reciprocating compressor Control sensor: pressure transducer Starting at the lower capacities, packaged water chillers use one or more reciprocating compressors. This type of unit would be mounted directly outside or on a rooftop with supply and return connections for the chilled water piped into the building. For head (discharge) pressure control, the condenser fan control receives input from a pressure transducer. The fans are maintained at the lowest condensing pressure and temperature possible to maintain the highest unit efficiency.
9
Air-Cooled Condensers (2 of 2)
(a) Air-cooled condenser installation with a package chiller; (b) remote air-cooled condenser The larger package chillers with reciprocating compressors can be air cooled or water cooled and range upward from 40 to 200 tons. The cooler and compressor can be located indoors and the air-cooled condenser located on the rooftop or outside the building.
10
Scroll Compressor Chillers
Cutaway view of a scroll compressor In addition to reciprocating compressors, the scroll-type compressor is being utilized increasingly in packaged chillers. These compressors use a pair of mating scroll-shaped surfaces to compress the refrigerant with pure rotary motion.
11
Centrifugal Compressor Chillers
Hermetic centrifugal compressor Centrifugal compressor impeller Compressor discharge through casing volute to condenser Hermetic centrifugal compressors vary in design and refrigerant type. This unit has a hermetically sealed motor that will drive the compressor through a set of transmission-speed-increasing gears. The compressor speed is typically much higher than the motor speed. The refrigerant vapor is drawn from the cooler into the suction eye of the rotating impeller. The pressure of the refrigerant is increased as it passes through the discharge of the spiral compressor casing (volute) and into the condenser.
12
Centrifugal Compressor Capacity Control and Screw Compressor Chillers
Inlet guide vanes in the closed position Inlet guide vanes in the open position Screw compressor, end view Variable-speed prime movers may also have limitations in speed reduction and only operate within a specific range. To accommodate this, most centrifugal compressors will have variable inlet guide vanes located at the compressor suction. These vanes will be closed at low load and at compressor start-up, and open at high load. An important type of packaged water chiller uses the helical rotary compressor, commonly known as a screw compressor because of the appearance of the rotors.
13
Screw Compressor Chillers
Diagram of the rotors of a screw compressor Cooling water tower for closed-loop water-cooled condenser The twin rotor screw compressor uses a mating pair of rotors with lobes that rotate much like a pair of gears. Screw compressors are used because of their high capacity for a small unit and their continuously variable (stepless) capacity control, typically modulating from 100 to 10 percent of full capacity. Being positive displacement, screw compressors have piping flexibility to accommodate remotely located condensers and can be used with high-pressure refrigerants. They can operate with both water- and air-cooled condensers. Cooling water towers may be used for closed-loop water-cooled condensers.
14
Screw Compressor Chiller Operation (1 of 2)
Screw compressor refrigerant flow without economizer An hermetic screw compressor drawing suction from a flooded cooler. The refrigerant vapor is compressed and discharged into the condenser. A float valve will control refrigerant flow and allow for the pressure drop required for the refrigerant to expand in the cooler. A hot-gas bypass solenoid-operated valve is used to recirculate refrigerant at low loads.
15
Screw Compressor Chiller Operation (2 of 2)
Screw compressor refrigerant flow with economizer Many large commercial centrifugal and screw-type chillers utilize economizer sections. Their purpose is to subcool the liquid refrigerant before it enters the cooler.
16
Chiller Oil Return Screw compressor oil flow A typical oil return
system for a hermetic screw-type compressor chiller. A metered amount of oil collecting in the bottom of the cooler is allowed to pass to the vaporizer section. Hot gas from the condenser passes through a coil located in the vaporizer. This will vaporize any liquid refrigerant that has been carried over with the oil. The oil then passes from the vaporizer to the oil sump, where an electric heater is utilized to further vaporize any refrigerant liquid entrained in the oil. Mist eliminators are used to remove any entrained oil in the refrigerant vapor before returning to the compressor suction. This reduces the possibility of any oil carryover that would slug the compressor.
17
Chiller Refrigerant Recovery and Transfer
Liquid recovery first Vapor recovery follows liquid recovery This system is permanently installed and can be used to transfer refrigerant from multiple chiller circuits. Chillers that do not have permanently installed transfer systems will require a portable unit. This is different from conventional portable recovery units because of the valve arrangement.
18
Absorption Chiller Operation
Absorption-cycle operation Absorption-cycle components and operational cycle The refrigerant used is simply water, and the absorbent is lithium bromide (LiBr). The evaporator shell pressure is reduced to 0.12 psia (29.7 in Hg vacuum). At this low pressure, water will evaporate at 41°F.
19
Summary (1 of 3) Air-conditioning chillers are typically designed for indirect expansion. Chilled water is circulated to individual air handlers or fan rooms rather than the primary ingredient. Chillers come in various sizes, with smaller tonnage units utilizing reciprocating or scroll compressors with electric motor drives. 19
20
Summary (2 of 3) It is important to understand the refrigerant cycle and operation of a chiller before transferring refrigerant. Always remove liquid refrigerant from a chiller first before recovering the vapor or charging a unit. Failure to do so could result in chiller freeze-up and damage. 20
21
Summary (3 of 3) Never charge liquid refrigerant to a chiller that is under a deep vacuum. Never raise the pressure in a chiller above the rupture disk burst pressure. Follow all manufacturer’s recommendations and procedures when servicing a chiller.
22
Copyright This work is protected by United States copyright laws and is provided solely for the use of instructors in teaching their courses and assessing student learning. Dissemination or sale of any part of this work (including on the World Wide Web) will destroy the integrity of the work and is not permitted. The work and materials from it should never be made available to students except by instructors using the accompanying text in their classes. All recipients of this work are expected to abide by these restrictions and to honor the intended pedagogical purposes and the needs of other instructors who rely on these materials.
Similar presentations
© 2025 SlidePlayer.com Inc.
All rights reserved.