Desig n Compute moment per meter

Similar presentations


Presentation on theme: "Desig n Compute moment per meter"— Presentation transcript:

1 Desig n Compute moment per meter
Choose rft (same regulations as solid slabs) 5-10 bars/meter Minimum diameter=10 mm Preferable to have constant number of bars per meter We can use consecutive different diameters.

2 Note s Table ratios are based on column strip width equals field strip width In case field strip width is larger, increase field strip moment by the following ratio, R R=real width of field strip/(half C.L. to C.L.) Reduce column strip moments accordingly Rule: [M(F.S.)+ M(C.S)]before=[M(F.S.)+M(C.S.)]after

3 Example F.S.=4.25 m C.S.=2.75 m

4

5 Details of RFT [without drop panels]
If ts>160 mm ∴ shrinkage bars must be placed (clear span)

6 Details of RFT [with drop panel]
Ex:Let x of drop panel =3m There`s 15 ϕ /3m ∴ 2ϕ must be extended to supports 13 ϕ Details of RFT [with drop panel]

7

8

9 Span perpendicular on marginal beam

10 Column s Resist normal force and bending moments
Internal columns resist 50% of column strip negative moment Moment is distributed between lower and upper columns Exterior columns resist 90% of column strip negative moment Moment is distributed between lower and upper columns Mcolumn= 0.9x0.25 Mo x stiffness ratio