Presentation is loading. Please wait.

Presentation is loading. Please wait.

Reduce Arcing Time – Bus Differential

Similar presentations


Presentation on theme: "Reduce Arcing Time – Bus Differential"β€” Presentation transcript:

1 Reduce Arcing Time – Bus Differential
Bus Differential (87B) MV or HV IM1 = IF1 + IF2 + IF3 IM1 = IF1 + IF2 + IF3 + IF4 87B IM1 IF2 IF3 IF1 IM1 ο‚Ή IF1 + IF2 + IF3 X IF4 Instantaneous trip! CT issues CT balancing CT accuracy / linearity CT β€œburden” capacity Load impedance - saturation Zone Selective Interlocking is a way of communicating between circuit breakers to let upstream breakers know when they should delay tripping and when they should trip instantaneously. Normally, the upstream breaker must delay since you want only the downstream breaker to clear the fault and the upstream breaker to remain closed on the fault. But if the fault occurs upstream from the downstream breaker, the downstream breaker can’t clear the fault. The Zone Selective Interlocking works is that a restraining signal is transmitted from any downstream breaker that sees a fault up to the upstream breaker feeding that downstream breaker. The upstream breaker sees the fault current, but also sees the restraining signal and delays tripping, allowing the downstream breaker to clear the fault. On the other hand, if the downstream breaker doesn’t see the fault, it won’t send the restraining signal and that is a green flag for the upstream breaker to trip instantaneously, as it is closest breaker that clear the fault. The result is that the fault is cleared in 80 milliseconds instead of 1/2 second and the incident energy released at the point of the fault drops from 43.7 calories (which exceeds the 40 calorie limit of PPE 4), down to only 7 calories, safely below the 8 calorie PPE 2 limit which is only a fire resistant shirt and pants.

2 CT Error 𝐼 𝑒 = 𝐸′ 𝑋 𝑒 𝐸′=πΌβ€²βˆ™ 𝑍 β€² + 𝑍 𝐡 𝐢𝑇 π‘’π‘Ÿπ‘Ÿ = 𝐼 𝑒 𝐼′+ 𝐼 𝑒
Primary Current Secondary Current CT excitation current 𝐼 𝑒 = 𝐸′ 𝑋 𝑒 𝐸′=πΌβ€²βˆ™ 𝑍 β€² + 𝑍 𝐡 𝐢𝑇 π‘’π‘Ÿπ‘Ÿ = 𝐼 𝑒 𝐼′+ 𝐼 𝑒

3 CT Saturation #14 AWG (0.002525 /ft) 100’ total wiring (50’ x 2)
22.5V ISEC or I’ I PRI 600:5 Z’/2 (conductor impedance) Z’/2 + - E’ ZB (relay burden) Emax ~5V 𝐸′=πΌβ€²βˆ™ 2 𝑍 β€² /2 + 𝑍 𝐡 E’ < EMax 𝐸′=πΌβ€²βˆ™ 𝑍 π‘‡π‘œπ‘‘π‘Žπ‘™ #14 AWG ( /ft) 100’ total wiring (50’ x 2) ZB = 0.2  load Z’ = 100 * = 0.25  ISEC = I’ = 5A * 10 = 50A (10x fault) E’ = I’*ZTotal = 50*( ) = 22.5V 22.5V 0.04A 0.5% (or better) accuracy?

4 οƒΌ CT Error 𝐢𝑇 π‘’π‘Ÿπ‘Ÿ = 𝐼 𝑒 𝐼′+ 𝐼 𝑒 𝐢𝑇 π‘’π‘Ÿπ‘Ÿ = 0.04 50+0.04 =0.08% I’ = 50 A
I’ Secondary Current I Primary Current 𝐢𝑇 π‘’π‘Ÿπ‘Ÿ = 𝐼 𝑒 𝐼′+ 𝐼 𝑒 I’ = 50 A Ie = 0.04 𝐢𝑇 π‘’π‘Ÿπ‘Ÿ = =0.08% οƒΌ Better than 0.5%


Download ppt "Reduce Arcing Time – Bus Differential"

Similar presentations


Ads by Google