1 Psychrometric analysis Revision of principles - Central plant
for UBCLQT-40-3: Building & Engineering Systems Performance and UBLLSM-20-3: Mechanical Services

2 Psychrometric quantities
temperature dry bulb, t [oC d.b.] wet bulb, t’ [oC w.b.] relative humidity,  [%rh] = avp / svp percentage saturation, μ [% sat.] = ms/mss moisture content, x [kg.kg-1dry air] specific volume, v [m3.kg-1 dry air] = 1/ specific enthalpy, h [kJ.kg-1 dry air] dew point temperature, td [oC]

3 Psychrometric chart Lines of constant d.b. temp.
Dry bulb temperature, t

4 Psychrometric chart Lines of constant moisture content
Moisture content, x

5 Psychrometric chart percentage saturation , 
Lines of constant relative humidity,  (percentage saturation)

6 Psychrometric chart Wet bulb temperature, t’
Lines of constant w.b. temp. Wet bulb temperature, t’ 5oC wb 5oC db

7 Psychrometric chart Lines of constant specific volume
specific volume, v

8 Psychrometric chart Specific enthalpy, h ‘Lines’ of constant

9 Psychrometric chart Dew point temperature, td oC

10 State point Any two psychrometric quantities can be used to define a state point. All other properties can be read from the chart 50 %rh 26.5 kJ.kg-1 0.82 m3.kg-1 8.9oC db kg.kg-1 14oC db

11 Exercise - complete Table 1

12 Exercise – Solutions

13 Ideal processes Isothermal humidification Adiabatic humidification
Sensible heating Sensible cooling Adiabatic dehumidification Isothermal dehumidification

14 Real processes - Sensible Heating
Heating load, QH = ma (h2 - h1) h2 - h1 1 2 Heater Battery

15 Heating load, QH = ma (h2 - h1)
Real processes - Sensible Heating Plant Loads Example 1: Air flows at a rate of 3.42 kg.s-1 into a heater battery. If the initial condition of the air is state 5 (see Table 1) and the air leaves the heater battery at a temperature of 31 oC d.b., determine the load on the heater battery in kW. Heating load, QH = ma (h2 - h1)

16 Real processes - Sensible cooling
Cooling load, QC = ma (h1 - h2) (Nominal) h1 - h2 2 1 Cooler Battery

17 Real processes - Cooling & Dehum.
1 2 Cooler Battery

18 Real processes - Cooling & Dehum.
Cooling load, QC = ma (h1 - h2) (Nominal) h1 - h2 1 2 Cooler Battery

19 Real processes - Cooling & Dehum.
Cooling load, QC = ma (h1 - h2) (Nominal) h1 - h2 1 2 Cooler Battery

20 Contact Factor Cooling load, QC = ma (h1 - h2) h1 - h2 1 2 s ADP t

21 Real processes – Cooling with dehum
Plant Loads Example 2: A cooler battery takes a flow of 1.5 kg/s of air at 25oC d.b. with a moisture content of 11.3 g/kg and dehumidifies to obtain a moisture content of air leaving the battery of 8 g/kg. If the cooler contact factor is 85%, determine the apparatus dew point and the nominal cooling load in kW. Cooler Contact Factor,

22 Real processes - adiabatic humidifier
Adiabatic process - where no energy transfer occurs i.e. h1 = h2  Load = 0 2 1 Air Washer

23 Real processes - steam injection
 h 2 1 Steam humidifier

24 Humidifier saturation efficiency
ADP 2 1

25 Humidifier saturation efficiency,
Real processes – Humidification Plant Loads Example 3: Air enters an air washer at 31oC d.b., 14.4oC w.b. and leaves with a moisture content of kg/kg d.a. Determine the saturatiion efficiency of the air washer. What factors influence the saturation efficiency of humidifiers generally? Humidifier saturation efficiency,

26 Room heat loads Summer room loads:-
Sensible heat gain + Latent heat gain Sensible Heat Ratio 1 Room ratio line R S tR - tS

27 Room heat loads Winter room loads:-
Sensible heat loss + Latent heat gain Sensible Heat Ratio 1 Room ratio line R S tS - tR

28 Room heat loads Example 4: The room is to be kept at state 4 using a flow of 1.50 kg.s-1 of air at state 6. Determine the room sensible and latent loads in kW. The specific heat capacity of moist air is 1.02 kJ.kg-1K-1

29 Central plant AHU - 100% fresh air
Summer cycle 2 4 6

30 Central plant AHU - 100% fresh air
Summer cycle 2 Cooler battery 8 4 6

31 Central plant AHU - 100% fresh air
Summer cycle 2 Cooler battery + Re-heater battery 8 4 6

32 Central plant AHU - 100% fresh air
Summer cycle O Cooler battery + Re-heater battery C R S Room ratio line (RRL)

33 Central plant AHU - 100% fresh air
Winter cycle 3 7 5

34 Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery 3 7 5 10

35 Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery + steam humidifier 3 9 7 5 10

36 Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery + steam humidifier 3 + re-heater battery 9 7 5 10

37 Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery Room ratio line (RRL) + steam humidifier R + re-heater battery B S O A

38 Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery Room ratio line (RRL) + adiabatic humidifier R + re-heater battery B S O A

39 Mixing AM A xA BM M xM B xB tB tM tA

40 Real processes - Mixing
Example 5: Air in state 3 is mixed with air in state 4 to obtain mixed air, state M, with a dry bulb temperature of 25oC. If the mass flow rate of mixed air is 1.45 kg/s, determine the flow rates of consituent air flows.

41 Central plant AHU - recirculation air
2 6 4 C C’ M Summer cycle

42 Central plant AHU - recirculation air
S M Room ratio line (RRL) Winter cycle


Download ppt "Psychrometric analysis Revision of principles - Central plant"