Presentation is loading. Please wait.

Presentation is loading. Please wait.

What Is to Be Covered? Electrical Shock - Why Have GFCIs?

Similar presentations


Presentation on theme: "What Is to Be Covered? Electrical Shock - Why Have GFCIs?"— Presentation transcript:

1 Understanding GFCIs Developed by the NEMA 5PP Personnel Protection Technical Committee

2 What Is to Be Covered? Electrical Shock - Why Have GFCIs?
How GFCI’s Operate Proper Installation of a GFCI Wiring Errors Grounded Neutral Detection Testing GFCIs

3 Electrocutions Associated With Consumer Products
Note the significant decline. In the mid 1970’s time period there were more than 600 consumer product related electrocutions annually and today there are less than 1/3 that number. Agreement to leave as is for now, the TC is asked to find more recent data on electrocutions.

4 Effects of Electric Shock
20A 4 AMPERES AND OVER Heart Paralysis, Serious Tissue and Organ Burning 15A 50 mA - 4 Amps Fibrillation 10A 4A 50mA IEC RCD Standards Breathing Difficult, Fibrillation in children Muscles “Freeze” in 50% of the Population Let-Go Threshold 4-6 UL 943 Class A GFCI Trip Level Perception Level 30mA 15mA 10mA 4-6 mA 1mA

5 Electric Shock Prevention System
Isolation (Physical) Insulation Double Insulation Equipment Grounding GFCI (solves shortcomings of above systems) Isolation Not possible when using electrical equipment Insulation Deteriorates with age accidentally or deliberately circumvented Double Insulation doesn’t protect if equipment is submerged doesn’t protect cord Equipment Grounding deteriorates if not maintained GFCI newest part of the protection system does not depend on other elements of the system

6 Normal Circuit Operation
Equipment N 6A Equipment Grounding Conductor (EGC) Current flows on the line conductor from line to the load Current returns from the load on the neutral The same amount of current flows from line to load and returns from load to line The same amount of current flow from line to load and returns from load to line.

7 Ground – Fault (Indirect Contact)
EGC 5.94A Ground-Fault When a person contacts the grounded enclosure of equipment with a fault to the enclosure it is called “indirect contact” The equipment grounding conductor (EGC) is effective Current divides and flows to ground based on the impedance of the two fault paths EGC has low impedance … most of the fault current flows on it person has comparatively higher impedance … small amount of fault current flows through the person (may or may not “feel a shock”) .06 A

8 Ground – Fault (Direct Contact)
If ECG is absent (cut off prong on plug) then ALL the fault current will flow through the person. This is called direct contact. Amount of current determined by impedance of the person Dry hands or large person has higher impedance than wet hands or small person .1 A

9 How GFCIs Operate Knowing how GFCIs work will enable you to understand: Why GFCIs must be installed a certain way For Circuit Breaker GFCI: To prevent constant tripping, MUST connect Load Neutral to circuit breaker neutral terminal, NOT panelboard neutral. For Receptacle GFCI: If line and load conductors are reversed, per 2010 edition UL 943, no power is available at: Face terminals or Line terminals connected to downstream receptacles. Why do GFCIs trip under various circumstances Mis-wiring will cause GFCI to trip if: Ground current is flowing Neutral is grounded on load side of GFCI. Portable GFCIs will trip if open neutral is present on the line side of the GFCI. What conditions causes unexpected tripping Ground current exceeding 6 mA when a load is applied. Load neutral is not connected to correct terminals.

10 The Current “Adding Machine”
Load IIn IOut If the current out = current back, the differential current transformer shows no output. L N Differential Current Transformer Rrevise text in block to something like “I-out” and “I-in” instead. Label/point to the two 6A currents as I-in and I-out. Agree with addition of I-in and I-out. Agree to remove 6A. Show two leads coming from the transformer, and label them “Differential Current”. (Consider showing the transformer this way in all applicable slides). Do not support. Current OUT=Current BACK … differential current is zero

11 Current “Adding Machine”
240V Load IIN IOut L1 L2 Differential Current Transformer N 120/240V Load IIN IOut L1 L2 What about a 240V load… current out equals current back… differential current is zero Same is true for 120/240V systems… current out equals current back.. Differential current is zero 3 phase? - same principles apply Differential Current Transformer

12 Current “Adding Machine” Under Ground Fault Conditions
Load IIn = 6A IOut = 5.9A Ground-Fault .1A L N When a ground fault is introduced another return path is established Current out (6A) does not equal current returning (5.9A) because .1A is returning through the ground path The “differential current transformer” detects the difference… the differential current signals the electronics. Differential Current Transformer If I-out does not equal I-in, the differential current transformer creates an  output signal.

13 What’s in the GFCI? (Receptacle)
Reset Button Test Button Cover Tamper Resistant Mechanism (Optional) Bridge Face Contacts Middle Barrier Terminals Terminals Printed Circuit Board Base

14 GFCI circuitry with grounded neutral detection
What’s in the GFCI? (Receptacle) GFCI circuitry with grounded neutral detection 120V Trip Mechanism Push-to-test Button 15K Resistor Face Hot Load Hot Face Load Terminals Line Terminals Load Shown here is a GFCI receptacle Line Terminals where conductors from panelboard are terminated Double pole mechanical latching trip mechanism actuated by a 120 volt tripping coil Differential current transformer… detects differential current Electronic circuit asks and answers questions is differential current over 6mA is duration long enough screens out momentary surges, RF interference, etc. closes trip circuit if differential current exceeds 6ma. NOTE the EGC passes through, BUT is NOT involved in the detection circuitry Grounded Neutral detection circuit to detect a neutral on the load side of the GFCI Push to test button test circuit from line through differential transformer through an 15K or so resister (limits test to about 8mA) creates a differential current causing the GFCI to “detect and trip” Receptacle outlets on the LOAD side of the differential transformer Load side terminals for feed-thru capability Neutral Neutral EGC Receptacle Face

15 What’s in the GFCI? (Circuit Breaker)
Push-To-Test Button Over-Current trip Trip Solenoid Handle (ON-OFF) Printed Circuit Board Panel Neutral wire Trip Mechanism “Load Power” Terminal Primary Current-carrying Contacts Sensing Coil “Line” Terminal “Load Neutral” Terminal

16 What’s in the GFCI? (Circuit Breaker)
Electronic circuitry with Grounded Neutral detection Push-To-Test Button Trip Solenoid Test Resistor Trip Mechanism Sensing Coil “Line” Terminal “Load Power” Terminal “Load Neutral” Terminal Primary Current-carrying Contacts Panel Neutral wire

17 What’s in the GFCI? (Plug-in)
Electro-Mechanical Latching Device Current Imbalance and Grounded Neutral Sensors Principal difference is what is call “open neutral” protection required by UL on plug-in GFCI’s If you plug a portable GFCI into a cord or receptacle, its contacts must remain open if the circuit into which it is plugged has an open neutral If this were not required, a fault could exist and the GFCI would not trip Open neutral protection is generally accomplished using a normally energized solenoid coil which, once reset, maintains the contacts in the closed position. When power is removed by(either by both or one open conductor), the contacts open.

18 What’s in the GFCI? (Plug-in)
Push-to-test Button Electro Mechanical Latching Device Current Imbalance and Grounded Neutral Sensor 15k Resistor Load Hot Load Neutral EGC Principal difference is what is call “open neutral” protection required by UL on plug-in GFCI’s If you plug a portable GFCI into a cord or receptacle, its contacts must remain open if the circuit into which it is plugged has an open neutral If this were not required, a fault could exist and the GFCI would not trip Open neutral protection is generally accomplished using a normally energized solenoid coil which, once reset, maintains the contacts in the closed position. When power is removed by(either by both or one open conductor), the contacts open. Circuitry with Open and Grounded Neutral detection

19 Standard 120V Connection (GFCI Circuit Breaker)
120/240Vac Source L1 N L2 HOT GND NEUTRAL EQUIPMENT GROUND 1-POLE CIRCUIT BREAKER WITH GFCI DUPLEX RECEPTACLE 240 120 Breaker “plugged” into the panel for 120V power Note that the neutral pigtail is connected to the panelboard neutral (S/N). Load neutral must return to the circuit breaker load neutral terminal EGC could be unconnected and have no effect on the proper operation of the GFCI NOTE that the CB performs the standard functions of a breaker as well (overload, short circuit, etc.) Slide 21 – 29 – consider using “Line” instead of “Hot”, since in previous slides we use “L”. Alternatively, if “Hot” is preferred, then  update ALL slides as such, for consistency.

20 Standard 120 Volt Connection (GFCI Receptacle)
120/240Vac Source N L1 L2 Line Terminals Load Terminals Branch circuit from panelboard connected to the “line” terminals EGC connected as with any receptacle Branch circuit conductors feed other receptacles connected to “load” terminals Cover downstream receptacles with an appropriately marked plate N

21 240 Volt Load – No Neutral 120/240Vac Source L1 N L2 GND HOT B HOT A
EQUIPMENT GROUND 2-POLE CIRCUIT BREAKER WITH GFCI 250V DUPLEX RECEPTACLE 240 120 Note: Load neutral circuit not used in this circuit Breaker “plugged” into the panel for 120V power Note that the neutral pigtail is connected to the panelboard neutral (S/N). Load neutral must return to the circuit breaker load neutral terminal EGC could be unconnected and have no effect on the proper operation of the GFCI NOTE that the CB performs the standard functions of a breaker as well (overload, short circuit, etc.) Slide 21 – 29 – consider using “Line” instead of “Hot”, since in previous slides we use “L”. Alternatively, if “Hot” is preferred, then  update ALL slides as such, for consistency.

22 120/240 Volt Load 120/240Vac Source L1 N L2 GND HOT B HOT A NEUTRAL
EQUIPMENT GROUND 2-POLE CIRCUIT BREAKER WITH GFCI 240 120 NEUTRAL 120/240 VAC LOAD Breaker “plugged” into the panel for 120V power Note that the neutral pigtail is connected to the panelboard neutral (S/N). Load neutral must return to the circuit breaker load neutral terminal EGC could be unconnected and have no effect on the proper operation of the GFCI NOTE that the CB performs the standard functions of a breaker as well (overload, short circuit, etc.) Slide 21 – 29 – consider using “Line” instead of “Hot”, since in previous slides we use “L”. Alternatively, if “Hot” is preferred, then  update ALL slides as such, for consistency.

23 Single Phase 120V Circuit 1A L 120V 1A N
Remember - what goes out must equal what comes back If it doesn’t there is differential current. 1A

24 Multi-Wire Circuits One leg of multi-wire circuit in use 1A 1A 0A
120V 1A 120V Many are confused about GFCI’s applied on multi-wire circuits. Remember that as long as what goes out … comes back, the differential current is zero. In this drawing with one leg of the circuit open, the current flows out on the “hot” conductor and back on the neutral 0A Switch Open

25 Multi-Wire Circuits Both legs of multi-wire circuit in use 1A 120V 0A
When the switch is closed. If the load is balanced the “neutral” has zero and the differential is between the two “hot conductors” If the load is not balanced, there is some current on the neutral, but the differential current sensor still sees a total of what goes out versus what comes back regardless of the amounts of current in each wire. 1A If what goes out…. Comes back.. The GFCI sees zero total current on the circuit.

26 GFCI Circuit Breaker on Multi-Wire Circuits
120/240Vac Source L1 N L2 HOT B GND HOT A EQUIPMENT GROUND 2-POLE CIRCUIT BREAKER WITH GFCI 240 120 NEUTRAL DUPLEX RECEPTACLE Breaker “plugged” into the panel for 120V power Note that the neutral pigtail is connected to the panelboard neutral (S/N). Load neutral must return to the circuit breaker load neutral terminal EGC could be unconnected and have no effect on the proper operation of the GFCI NOTE that the CB performs the standard functions of a breaker as well (overload, short circuit, etc.) Slide 21 – 29 – consider using “Line” instead of “Hot”, since in previous slides we use “L”. Alternatively, if “Hot” is preferred, then  update ALL slides as such, for consistency.

27 GFCI Receptacle on Multi-Wire Circuits
Use two GFCI receptacles Junction Box T R Separate Neutrals R T GFCI Receptacles Downstream Receptacles Downstream Receptacles

28 This “Old House” Problem
GFCI installed on one circuit 6A L1 N ? GFCI installed on a circuit with a neutral “stolen” from another circuit 6A on L1 switch on L2 open… What does the current sensor see going back on the neutral? Since it sees 6A, what does the GFCI do? Nothing. Let’s close the switch on L2… with 6A on L1, but what is going back on the neutral? 0A is the correct answer (provided the loads are the same) What happens? The GFCI trips Every time the switch is closed, the GFCI trips Additionally, this multi-wire circuit doesn’t meet the code rules in NEC (keep all the circuit conductors together). NOTE: The following are two corrective actions to prevent tripping, either a) add GFCI to L2 with its separate neutral, or b) replace with a 2-pole GFCI device that will protect L1 & L2” . 6A L2 Second circuit installed and neutral “stolen” from a close-by circuit

29 Line and Load Reversal on Receptacles
Incorrect Wiring Correct Wiring To Downstream Receptacle To Panelboard To Panelboard To Downstream Receptacle If the branch circuit conductors from the panelboard are connected to the GFCI “load” side terminals and the downstream receptacles are connected to the “line” terminals ... what happens? When the GFCI is tripped A tester plugged into the downstream receptacles shows they are energized. When a tester is plugged into the GFCI receptacle… it is NOT de-energized.. even though the GFCI has tripped. This page needs to be updated to indicate that the GFCI Receptacle will not have power to the face and downstream terminals when miswired. it’s intended message is not clear. Consider adding some text/arrows etc. to point out that if the black wire from the Panel board is a) connected to the “LOAD” as shown, it’s “Incorrect,” and that b) if it is connected to the LINE side, that is “Correct”. UL 943 has been revised to prevent providing power to the face of downstream terminals in the event of a line-load miswire. In the case of incorrect wiring there will be no power at the face or downstream.

30 GFCI Circuit Breaker Miswiring
120/240Vac Source L1 N L2 HOT GND NEUTRAL EQUIPMENT GROUND 1-POLE CIRCUIT BREAKER WITH GFCI DUPLEX RECEPTACLE 240 120 Current does not return through the sensor in the circuit breaker Breaker “plugged” into the panel for 120V power Note that the neutral pigtail is connected to the panelboard neutral (S/N). Load neutral must return to the circuit breaker load neutral terminal EGC could be unconnected and have no effect on the proper operation of the GFCI NOTE that the CB performs the standard functions of a breaker as well (overload, short circuit, etc.) Slide 21 – 29 – consider using “Line” instead of “Hot”, since in previous slides we use “L”. Alternatively, if “Hot” is preferred, then  update ALL slides as such, for consistency.

31 Grounded Neutral Detection
GFCI Device 6A L ? N Leakage Current 1. With CB GFCI, load neutral must be connected to CB neutral terminal and not panelboard neutral. Otherwise, it will constant trip if circuit has load. 2. With receptacle GFCI, conforming to 2010 UL 943 Standard, reversing line and load conductors result in no power available at face terminals or line terminals connected to downstream receptacles. 3. GFCIs trip if miswired or ground current flowing or neutral grounded on load side of GFCI. Additionally, portable GFCIs trip if open neutral is present on the line side of the GFCI. 4. Occurs when ground current exceeding 6 mA. accompanies load start-up. Excessive ground current, (exceeds 6mA.) exists with load causes unexpected tripping. EGC ? Equipment Neutral grounded downstream

32 UL GFCI Tests Every GFCI must pass the following end-of- line manufacturing tests: no trip below 4mA (no load) must trip at 6mA (no load) no trip below 4mA (with load) at rated voltage must trip at 6mA (with load) at rated voltage must trip with 2 ohm grounded neutral must trip within 25 ms with a 500 ohm fault must trip with test button at +10/-15% rated voltage must not trip with noise test of GFCI Standard calibration test at +10/-15% rated voltage

33 GFCI Testers Why are testers used? Will not test:
verify operation of the GFCI check protection of downstream receptacles Will not test: GFCI calibration ALL types of improper installation Danger on 2-wire circuits Will test for some types of improper installation: line/load reversal which outlets are protected by GFCI reverse polarity presence of the equipment ground

34 Test and Reset Buttons (Receptacle)
Test and reset buttons verify proper functioning of the GFCI Test button will initiate end-of-life indication or power denial if product is no longer operational Push-to-test Button Reset Button Test button indicates proper functioning of the GFCI Does NOT indicate proper installation of the GFCI

35 GFCI Testers Plug-in testers divert current to the equipment grounding conductor What if there is not equipment ground....? Such as in a 406.3(D)(2)(b) and 406.3(D)(2)(c) application? The GFCI will not trip with the external tester. The test button must be used.

36 Benefits of UL943 (GFCI) vs. IEC (RCD)
Increased Safety Benefits UL943 Max 6 mA - threshold for “let-go” current. IEC Min 20 mA - threshold current for ventricular fibrillation. Receptacle End of Life indication Grounded Neutral protection Portable units - Load protection if both supply neutral and ground conductors are open together. UL943 Ground-Fault Circuit-Interrupters (GFCI) vs. IEC Residual Current Device (RCD) UL943 max 6 mA trips in a current range where human muscles can still “let go” and not contract creating safety concerns. The IEC 20 mA is approaching the ventricular fibrillation levels. UL943 Receptacles are required to deny power or give a visual indication when the GFCI is no longer providing ground fault protection. The IEC RCD’s do not have this requirement. UL 943 requires GFCIs to provide protection when the neutral conductor becomes connected to earth on the load side so that a fault current path at the user end could return through the neutral conductor rather than through earth or the ground conductor. Portable units - Load protection if both supply neutral and ground conductors are open together.

37 Summary GFCIs have contributed significantly to the reduction in the number of deaths due to electric shock GFCIs look at the current going out and compare it to the current coming back Remember that GFCIs detect ground to neutral connections downstream Test the GFCI by using the test button and a load GFCIs will not protect between line and neutral Only Class A GFCIs (6mA) protect from electrocution from “let-go” situations


Download ppt "What Is to Be Covered? Electrical Shock - Why Have GFCIs?"

Similar presentations


Ads by Google