Presentation is loading. Please wait.

Presentation is loading. Please wait.

Modern Control Systems (MCS)

Similar presentations


Presentation on theme: "Modern Control Systems (MCS)"β€” Presentation transcript:

1 Modern Control Systems (MCS)
Lecture-10 Lag-Lead Compensation Dr. Imtiaz Hussain Assistant Professor URL :

2 Lecture Outline Introduction to lag-lead compensation
Design Procedure of Lag-lead Compensator Case-1 Case-2 Electronic Lag-lead Compensator Mechanical Lag-lead Compensator Electrical Lag-lead Compensator

3 Introduction Lead compensation basically speeds up the response and increases the stability of the system. Lag compensation improves the steady-state accuracy of the system, but reduces the speed of the response. If improvements in both transient response and steady-state response are desired, then both a lead compensator and a lag compensator may be used simultaneously. Rather than introducing both a lead compensator and a lag compensator as separate units, however, it is economical to use a single lag–lead compensator.

4 Lag-Lead Compensation
Lag-Lead compensators are represented by following transfer function Where Kc belongs to lead portion of the compensator. 𝐺 𝑐 𝑠 = 𝐾 𝑐 𝑠+ 1 𝑇 1 𝑠+ 𝛾 𝑇 𝑠+ 1 𝑇 2 𝑠+ 1 𝛽𝑇 2 , (Ξ³>1 π‘Žπ‘›π‘‘ Ξ²>1)

5 Lag-Lead Compensation
𝐺 𝑐 𝑠 = 𝐾 𝑐 𝑠+1 𝑠 𝑠+0.4 𝑠+0.1

6 Design Procedure In designing lag–lead compensators, we consider two cases where Case-1: γ≠𝛽 Case-2: Ξ³=𝛽 𝐺 𝑐 𝑠 = 𝐾 𝑐 𝑠+ 1 𝑇 1 𝑠+ 𝛾 𝑇 𝑠+ 1 𝑇 2 𝑠+ 1 𝛽𝑇 2 , (Ξ³>1 π‘Žπ‘›π‘‘ Ξ²>1) 𝐺 𝑐 𝑠 = 𝐾 𝑐 𝑠+ 1 𝑇 1 𝑠+ 𝛽 𝑇 𝑠+ 1 𝑇 2 𝑠+ 1 𝛽𝑇 2 , (Ξ²>1)

7 Design Procedure (Case-1)
Step-1: Design Lead part using given specifications. Step-1: Design lag part according to given values of static error constant. 𝐺 𝑐 𝑠 = 𝐾 𝑐 𝑠+ 1 𝑇 1 𝑠+ 𝛾 𝑇 𝑠+ 1 𝑇 2 𝑠+ 1 𝛽𝑇 2 , (Ξ³>1 π‘Žπ‘›π‘‘ Ξ²>1)

8 Example-1 (Case-1) Consider the control system shown in following figure The damping ratio is 0.125, the undamped natural frequency is 2 rad/sec, and the static velocity error constant is 8 sec–1. It is desired to make the damping ratio of the dominant closed-loop poles equal to 0.5 and to increase the undamped natural frequency to 5 rad/sec and the static velocity error constant to 80 sec–1. Design an appropriate compensator to meet all the performance specifications.

9 Example-1 (Case-1) From the performance specifications, the dominant closed-loop poles must be at Since Therefore the phase-lead portion of the lag–lead compensator must contribute 55Β° so that the root locus passes through the desired location of the dominant closed-loop poles. 𝑠=βˆ’2.50±𝑗4.33

10 Example-1 (Case-1) 𝐾 𝑐 𝑠+ 1 𝑇 1 𝑠+ 𝛾 𝑇 1 = 𝐾 𝑐 𝑠+0.5 𝑠+5.02
The phase-lead portion of the lag–lead compensator becomes Thus 𝑇 1 =2 and 𝛾=10.04. Next we determine the value of Kc from the magnitude condition: 𝐾 𝑐 𝑠+ 1 𝑇 1 𝑠+ 𝛾 𝑇 1 = 𝐾 𝑐 𝑠+0.5 𝑠+5.02 𝐾 𝑐 (𝑠+0.5) 𝑠 𝑠(𝑠+0.5) 𝑠=βˆ’2.5+𝑗4.33 =1 𝐾 𝑐 = 𝑠(𝑠+5.02) 4 𝑠=βˆ’2.5+𝑗4.33 =5.26

11 Example-1 (Case-1) The phase-lag portion of the compensator can be designed as follows. First the value of 𝛽is determined to satisfy the requirement on the static velocity error constant 𝐾 𝑣 = lim 𝑠→0 𝑠 𝐺 𝑐 𝑠 𝐺(𝑠) 80= lim 𝑠→0 𝑠 𝑠+ 1 𝑇 2 𝑠 𝑠 𝑠+ 1 𝛽𝑇 2 80=4.988𝛽 𝛽=16.04

12 Example-1 (Case-1) Finally, we choose the value of 𝑇 2 such that the following two conditions are satisfied:

13 Example-1 (Case-1) 𝐺 𝑐 𝑠 =6.26 𝑠+0.5 𝑠+5.02 𝑠+0.2 𝑠+0.0127
Now the transfer function of the designed lag–lead compensator is given by 𝐺 𝑐 𝑠 =6.26 𝑠+0.5 𝑠 𝑠+0.2 𝑠

14 Example-1 (Case-2) Home Work

15 Home Work Electronic Lag-Lead Compensator
Electrical Lag-Lead Compensator Mechanical Lag-Lead Compensator

16 End of Lecture-10 To download this lecture visit
End of Lecture-10


Download ppt "Modern Control Systems (MCS)"

Similar presentations


Ads by Google