EACO News Magazine 2010 September. 2010-09: Topics DVM Plus III up compatibility New control devices –MIM-B16 –MIM-B17 –MIM-B18 How to change option code.

Similar presentations


Presentation on theme: "EACO News Magazine 2010 September. 2010-09: Topics DVM Plus III up compatibility New control devices –MIM-B16 –MIM-B17 –MIM-B18 How to change option code."— Presentation transcript:

1 EACO News Magazine 2010 September

2 2010-09: Topics DVM Plus III up compatibility New control devices –MIM-B16 –MIM-B17 –MIM-B18 How to change option code with MR-CH01 The next EACO News Magazine will be released 01 October 10

3 Compatibility table: DVM Plus III vs DVM Plus III up (1) Outdoor UnitIndoor Units Before: DVM Plus III Current DVM Plus III Indoor units After: DVM Plus III up New Wall Mounted with EEV included (NS~HHXEA) Compatible Not compatible

4 Compatibility table: DVM Plus III vs DVM Plus III up (2) So its not allowed to make a module system with a mix of DVM Plus III and DVM Plus III up outdoor units For our Digital Solution Devices there is a free compatibility between old and new outdoor units Before DVM Plus III After DVM Plus III up Module System DVM Plus III + DVM Plus III up NO!

5 Opto-isolated Interface with pulse-type watt hour meters for electricity billing system Max. 8 watt hour meters per interface module Total 8 WHM interface module per DMS1/DMS2 Pulse coefficient setting: 1Wh/pulse ~ 1000Wh/pulse Pulse width setting: 20ms~400ms in 1ms intervals Interval between pulses: minimum 3ms No support of pulse coefficient with decimal points Power data storage in non-volatile memory ( 8 channels) Data recovery from power failure Current time setting and display Configuration information display on LCD Error display (communication, out-of-range pulse width..) MIM-B16: WHM interface module (1) 5 Pulse signal Max. 8 watt hour meters

6 MIM-B16: WHM interface module (2) 6 MIM-B16 Max. 8 MIM-B16s Power Supply Power supply DMS2 RS485 Comm. Power supply Pulse signal Power box

7 MIM-B17: BACnet Gateway (1) Interface for BACnet management system Max. 256 indoor units/ERVs support with max. 16 interface modules Lower physical layer : RS485 Upper physical layer : BACnet/IP 7 ControlMonitoring On/Off controlOn/Off stateIn/out contact state Operation mode Emergency Stop Temperature settingSet/Room temperatureError code Fan speed/direction ERV operation mode ERV fan speed Filter alarm resetFilter alarm User control restriction Operation mode lockThermo Off/On Set temperature limitPower distribution Emergency stopOperation mode lock Output contact controlSet temperature limit

8 MIM-B17: BACnet Gateway (2) 8 Ethernet BACnet BMS Interface module RS485 Max. 16

9 MIM-B18: LonWorks Gateway (1) Interface for Lon-Connection to LonWorks management system Max. 128 indoor units/ERVs support Communication : RS485 to LonWorks Upper physical layer : FTT-10A Combinational use of LonWorks and S-NET3/S-NET mini 9 ControlMonitoring On/Off controlOn/Off stateIn/out contact state Operation mode Emergency Stop Temperature settingSet/Room temperatureError code Fan speed/direction ERV operation mode ERV fan speed Filter alarm resetFilter alarm User control restriction Operation mode lockThermo Off/On Set temperature limitPower distribution Emergency stopOperation mode lock Output contact controlSet temperature limit

10 MIM-B18: LonWorks Gateway (2) 10 FTT-10A LonWorks BMS Interface module RS485 Max. 16 Ethernet S-NET3S-NET mini

11 How to change option code with MR-CH01 (1) 1.Remove one battery from the wireless remote controller. 2.Press the Temp buttons together and put the battery back to enter the option code setting mode. 3.Set two digits of the option code respectively. And press Mode to change to the next two digits. 4.Press the On/Off power button to change the option code. 11 Initial display 24-bit option code setting

12 How to change option code with MR-CH01 (2) 12 24-bit option code setting Example : 027402 – 14221A – 200001 - 300000 4.Then OFF timer is displayed 5.Set the next 10 digits 6.Press On/Off to set the new option code 20 digits (blue) except the page digits must be set 1.Set the two digits using the Temp buttons 2.Press Mode to move to the next two digits. Indicator moves to the next operation mode icon 3.Press Mode to move to the third option code page


Download ppt "EACO News Magazine 2010 September. 2010-09: Topics DVM Plus III up compatibility New control devices –MIM-B16 –MIM-B17 –MIM-B18 How to change option code."