Presentation is loading. Please wait.

Presentation is loading. Please wait.

Background Information on Hurricane Matthew Event No.1 Event No.2

Similar presentations


Presentation on theme: "Background Information on Hurricane Matthew Event No.1 Event No.2"— Presentation transcript:

1 Transmission and Generation Misoperations During an Extreme Weather Event

2 Background Information on Hurricane Matthew Event No.1 Event No.2
Agenda Background Information on Hurricane Matthew Event No.1 Cause Analysis Event No.2 Discussion Conclusion

3 Category 5 hurricane during 2016-2017 hurricane season
Hurricane Matthew Category 5 hurricane during hurricane season Category 1 when it made landfall in the Carolinas Tropical storm-force winds in most of Duke Energy’s eastern territory Record-breaking rain and flooding (12-16 inches of rain in some areas) Historic level of impact (58 transmission circuits lost)

4 Line of interest is Line #1-1 between Station 1A and Station 1B.
Event #1 Line of interest is Line #1-1 between Station 1A and Station 1B. At Station 1A, there is an electromechanical line protection panel. Station 1A Line #2-1 G Station 1B Station 1C Line #1-1 Line #3-1

5 LL fault occurred on Line #1-1, between Station 1A and Station 1B.
Event #1 t = 0 seconds LL fault occurred on Line #1-1, between Station 1A and Station 1B. Station 1A Line #2-1 G Station 1B Station 1C Line #1-1 Line #3-1

6 Event #1 t = 0.05 seconds Breakers at Station 1B trip. They go through a normal reclose cycle and trip out again at t = seconds; fault propagates to 3PH fault. Line #2-1 Station 1A Station 1B Line #1-1 Line #3-1 Station 1C G

7 Event #1 t = seconds Generator breakers trip due to undervoltage condition on low side bus of the GSU. Line #2-1 Station 1A Station 1B Line #1-1 Line #3-1 Station 1C G

8 Backup protection on Line #2-1 trips.
Event #1 t = seconds Backup protection on Line #2-1 trips. Line #2-1 Station 1A Station 1B Line #1-1 Line #3-1 Station 1C G

9 Backup protection on Line #3-1 trips.
Event #1 t = seconds Backup protection on Line #3-1 trips. Line #2-1 Station 1A Station 1B Line #1-1 Line #3-1 Station 1C G

10 Event #1 t = seconds Fault changes and includes ground current. 67GC relay at Station 1A is able to issue trip and clear the fault. Station 1A Line #2-1 G Station 1B Station 1C Line #1-1 Line #3-1

11 Once the fault developed ground current, the 67GC tripped as normal.
Event #1 When the relay panel was investigated at Station 1A, it was found that there was only one line fault detector relay (50L). The 50L relay was required to assert for any of the phase distance elements to trip. The relay coil tested as an open circuit and could not assert for a fault. As such, the line effectively had no phase fault protection. Once the fault developed ground current, the 67GC tripped as normal.

12 Line of interest is Line #1-2 between Station 2A and Station 2B
Event #2 Line of interest is Line #1-2 between Station 2A and Station 2B At Station 2A, Feeder #1-2 and Line #1-2 can be tied together, and both have electromechanical relay protection. Station 2A Line #2-2 G Station 2B Station 2C Line #1-2 Line #3-2 Feeder #1-2 N.O.

13 This was not the intended purpose of the switch.
Event #2 During the event, the switch was mistakenly left closed with the breaker disconnect open, and the feeder breaker was being used to back up the line. This was not the intended purpose of the switch. Station 2A Line #2-2 G Station 2B Station 2C Line #1-2 Line #3-2 Feeder #1-2 N.O.

14 LL fault on Line #1-2 between Station 2A and Station 2B.
Event #2 t = 0 seconds LL fault on Line #1-2 between Station 2A and Station 2B. Relays at Station 2B detect fault, trip, reclose, and trip out again as designed. Station 2A Line #2-2 Station 2B Line #1-2 Line #3-2 N.O. G Feeder #1-2 Station 2C

15 Undervoltage condition causes generation facility to trip.
Event #2 t = 1.2 seconds Undervoltage condition causes generation facility to trip. Station 2A Line #2-2 Station 2B Line #1-2 Line #3-2 N.O. G Feeder #1-2 Station 2C

16 Reverse-looking backup protection successfully clears fault.
Event #2 t = 1.5 seconds Reverse-looking backup protection successfully clears fault. Station 2A Line #2-2 Station 2B Line #1-2 Line #3-2 N.O. G Feeder #1-2 Station 2C

17 The Zone 1 phase relay for the feeder could not see the fault.
Event #2 Since the station was left in an abnormal configuration, the feeder relays were responsible for protection. The Zone 1 phase relay for the feeder could not see the fault. The Zone 2 phase relay output contacts had developed resistance between them. Even though the Zone 2 relay detected the fault and successfully closed the contacts, the contacts couldn’t transmit the signal successfully.

18 The history behind each event
Discussion The history behind each event Event No.1: Original station design only had one set of CTs on the breaker available for the line protection panel. Event No.2: The intent was for the line to back up the feeder, not to have the feeder back up the line. How are these events different? Event No.1 is a true single point of vulnerability. Event No.2 is murkier. There was a single point of vulnerability, but only in the abnormal arrangement. Different types of relays (50L vs. 21P). How are these events similar? Electromechanical panels. Caused by a single relay failure. Trip failure exacerbated by the weakened system (why we lost generation).

19 Event No.2 would not have occurred if:
Discussion Neither of these events would have occurred with DEP’s standard microprocessor panel. Event No.1 would not have occurred if single point of vulnerability had been addressed when the breakers were replaced. Event No.2 would not have occurred if: The station had been in its normal arrangement. The station had been set up with the line protecting the feeder. The panel had been designed with the intent of protecting the line. The idea that an electromechanical panel inherently has more redundancy than a microprocessor panel is not true.

20 Number of relay failures to lose protection for: Forward Phase Faults
Discussion Number of relay failures to lose protection for: Forward Phase Faults MP: 2 EM: 2 Forward Ground Faults EM: 1 or 2 Reverse Phase Faults EM: 1 or 0 Reverse Ground Faults EM: 0 Number of relay failures to lose protection for: Forward Phase Faults MP: 2 EM: 1 Forward Ground Faults EM: 1 or 2 Reverse Phase Faults EM: 1 or 0 Reverse Ground Faults EM: 0 Line Prot 1 Line Prot 2 BF / CTRL DEP Microprocessor Panel 21-1 21-2 21-3R 21-3F 21-C 67G 67GC 50L 21-X DEP Electromechanical Panel 50L-2

21 Conclusion When upgrading station equipment, it is important to see if the previous design left single points of vulnerability and address them if you can. Electromechanical relay panels do not inherently provide more redundancy. Single points of vulnerability are not just limited to the relays on the panel; abnormal system arrangements can create them.

22 Special Thanks To Al Ward Mark Matthews Rod Smith John O Connor

23


Download ppt "Background Information on Hurricane Matthew Event No.1 Event No.2"

Similar presentations


Ads by Google