Presentation is loading. Please wait.

Presentation is loading. Please wait.

Training Presentation

Similar presentations


Presentation on theme: "Training Presentation"— Presentation transcript:

1 Training Presentation
MCS-MAGNUM EXV LOGIC Training Presentation Rev. I - 11/15/2018

2 MCS EXV CONTROL PRESENTATION
1. EXV CONTROLLER & VALVE a. Controller Description b. Wiring c. Specifications 2. BASIC CONTROLS (INFINITE CAPACITY) a. Set Points b. Control Zones 3. BASIC CONTROLS (STEP CAPACITY) a. Set Points b. Relay Outputs for steps 4. EXV ADAPTIVE CONTROL a. Rate of Change b. Load Adjust c. Low Suction Control

3 MCS EXV CONTROL PRESENTATION
Continued 5. LIQUID LEVEL CONTROL 6. EXV MODES, STATES & LOGIC CHART 7. FINE TUNING YOUR MCS-EXV-DRIVER

4 EXV CONTROLLER & VALVE - DESCRIPTION - WIRING DIAGRAM - SPECIFICATIONS

5 MCS-EXV-DRIVER Standard 110 to 240 VAC ±10% (50/60 Hz)
Option 24 VAC ± 10% (50/60 Hz) 2 position led display Auto / Manual operation Closes valve on power failure Eliminates need for Liquid Line Solenoid 33% faster valve operation CSA / UL approved

6 MCS EXV New Feature Firmware Version 6.7 VERSION 6.7 - HARDWARE 3.0
New Feature was added for MCS-EXV-DRIVER with firmware 6.7 or greater. OO= Steps to Overdrive when Opening OC= Steps to Overdrive when closing Both are separate variables and can be set with a value between 2 to 8% Old version of firmware was set to overdrive the valve fixed at 10% of total steps. By using the new feature settings, the valve will not have to be overdriven as much. These new overdrive parameters are just when the MCS-EXV-DRIVER is running and voltage asked for full open or full closed. When the MCS-EXV-DRIVER is powered up, the valve must still be overdriven the total steps + this overdrive amount. Have to assume worst case at power up, the valve is fully open.

7 MCS-EXV-DRIVER WIRING Sporlan
B L A C K W H I T E WHITE WIRE TO ANALOG OUTPUT BLACK & SHIELD TO ANALOG OUTPUT GROUND R E D GREEN W H I T B L A C K ELECTRIC EXPANSION VALVE BLACK TO LINE 120/240 VAC WHITE TO NETURAL 120/240

8 MCS-EXV-DRIVER WIRING Alco
B L A C K W H I T E WHITE WIRE TO ANALOG OUTPUT BLACK & SHIELD TO ANALOG OUTPUT GROUND B R O W N L U E H I T A C K ELECTRIC EXPANSION VALVE BLACK TO LINE 120/240 VAC WHITE TO NETURAL 120/240

9 MCS-EXV-DRIVER WIRING Danfoss
B L A C K W H I T E WHITE WIRE TO ANALOG OUTPUT BLACK & SHIELD TO ANALOG OUTPUT GROUND R E D GREEN W H I T B L A C K ELECTRIC EXPANSION VALVE BLACK TO LINE 120/240 VAC WHITE TO NETURAL 120/240

10 MCS-EXV-DRIVER WIRING Carel
B L A C K W H I T E WHITE WIRE TO ANALOG OUTPUT BLACK & SHIELD TO ANALOG OUTPUT GROUND G R E N Y L O W B H I T ELECTRIC EXPANSION VALVE BLACK TO LINE 120/240 VAC WHITE TO NETURAL 120/240

11 Specifications Display # of Steps ALCO Display # of Steps DANFOSS
750 EX4 & EX5 A2 1660 EX7 A3 2600 EX8 Display # of Steps DANFOSS D1 2625 ETS-12/25/50 D2 3530 ETS-100 D3 3810 ETS-250/400 Display # of Steps SPORLAN S1 1596 SEI 0.5 to 11 S2 SER 1.5 to 20 S3 3193 SEI 30; SDR –3, SDR-3x S4 2500 Sporlan SERI-G, -J, -K, -L Sporan SER-B, -C, -D, -F CDS -2, -4, -7 S5 6386 SEI-50, SEH (I)-100, -175, -400; CDS –9, -16, -17; SDR –4 Display # of Steps CAREL CL 500 E2V, E3V, E4V, E5V, E6V, E7V

12 (Infinite Capacity Control)
MCS EXV BASIC CONTROL (Infinite Capacity Control) - SET POINTS - CONTROL ZONES

13 MCS-EXV-DRIVER SET POINTS
(MCS CHILLER) # NAME VALUE TIME MAX TIME ALLOWED 9 SUPERHT TRGT 10.5 4 8 SH Target ± Ctl Zone 10 SPRHT + - 1.5 - 11 EXV LOAD ADJ 0.6 - 12 EXV FINE ADJ 0.2 - SH Fine & Course Adj 13 EXV COURSE ADJ 0.5 2 4 15 EXV MIN% 20.5 - EXV Min & MAX % 16 EXV MAX% 100 - 17 LO SUPERHEAT 1 - 18 LOSUCTPSIDLY 4 - Timing Ctl Set Points 19 EXV DELAY 60 - 20 EXV STRT TME 5 -

14 MCS-EXV-DRIVER SET POINTS
(MCS CHILLER) # NAME VALUE TIME MAX TIME ALLOWED 65 EXV ZONE X1 1.5 - Individual Zone Ctl 66 EXV ZONE X2 1.5 - 67 EXV rocZONE1 0.2 4 10 Individual ROC Ctl 69 EXV rocZONE2 0.3 5 10 70 EXV rocZONE3 0.4 5 10 71 EXV roc FAST 1 10 15 Zone 1 Speed Ctl 72 EXV roc CHG 0.8 10 15

15 EXV ABOVE & BELOW ZONES OPENING 4X COURSE ADJ * 2 @ QUARTER STEP DELAY
18 16 15 14 13 12 11 10 9 8 7 6 5 4 ABOVE ZONES > 15.0 OPENING 4X COURSE ADJ * QUARTER STEP DELAY ZONE 2 ABOVE SPT 66 = 1.5 13.5 TO 15.0 OPENING 2X COURSE HALF STEP DELAY S U P E R H A T ZONE 1 ABOVE SPT 65 = 1.5 12.0 TO 13.5 EXV IS OPENING FINE STEP DELAY TIME CONTROL ZONE SPT 9 = 10.5 SP 10 = 1.5 9.0 TO 12.0 EXV IS HOLDING ROC CONTROL ZONE 1 BELOW SP 65 = 1.5 7.5 TO 9.0 EXV IS CLOSING FINE STEP DELAY TIME ZONE 2 BELOW SPT 66 = 1.5 6.0 TO 7.5 CLOSING 2X COURSE HALF STEP DELAY BELOW ZONES < 6.0 CLOSING 4X COURSE ADJ * QUARTER STEP DELAY

16 (Step Capacity Control)
MCS EXV BASIC CONTROL (Step Capacity Control) - SET POINTS - RELAY OUTPUT SETUP FOR STEPS

17 MCS-EXV-DRIVER SET POINTS
# NAME VALUE TIME MAX TIME ALLOWED 9 SUPERHT TRGT 10.5 4 8 No Change 10 SPRHT + - 1.5 - 12 EXV FINE ADJ 0.2 - 13 EXV COURSE ADJ 0.5 - 14 EXV LOAD DIV 3 - With EXV Step Control the following Set Points are changed: SP 11, ‘EXV LOAD ADJUST’ is deleted SP 14, ‘EXV LOAD DIV’ is added As the Amp draw % changes this divides the EXV % change calculated as the ratio of slide movement to valve movement [(Max slide% – min slide%) / (Max vlv% - min vlv%)] +1

18 MCS-EXV-DRIVER SET POINTS
# NAME VALUE TIME MAX TIME ALLOWED 15 EXV MIN% 10 - No Change 16 EXV MAX% 100 - 17 LO SUPERHEAT 2 120 18 LOSUCTPSIDLY 4 - No Change 19 EXV DELAY 60 - 20 EXV STRT TME 5 10 The remaining set points remain active with the following changes: SP 17 TIME & MAX TIME ALLOWED are setup

19 MCS RELAY OUTPUT CFG SETUP
(Step Capacity Control) Cfg RO screen when Type = Step w\ EXV setup following: EXV Starting % when this compressor is the lead EXV Load Adjust %, the % increase to apply to the current EXV opening when this compressor is not the lead and is started EXV Unld adjust %, the % decrease to apply to the current EXV opening when this compressor is not the last compressor and is turned off

20 MCS RELAY OUTPUT MCS-CONNECT
EXV START WHEN LEAD COMPRESSOR STARTING % COMPRESSOR TIME IN STARTUP

21 EXV ADAPTIVE CONTROL - RATE of CHANGE - LOAD ADJUSTMENT
- LOW SUCTION CONTROL

22 MCS EXV ROC FUNCTION (MCS CHILLER) # NAME VALUE TIME MAX TIME ALLOWED 9 SUPERHT TRGT 10.5 4 8 - TIME field in set point 9 is the number of seconds to look at the slope of the superheat (ROC). - MAX TIME ALLOWED field is the maximum value the TIME field can be set to.

23 MCS EXV ROC FUNCTION (MCS CHILLER) # NAME VALUE TIME MAX TIME ALLOWED 67 EXV rocZONE1 0.2 4 10 69 EXV rocZONE2 0.3 5 10 70 EXV rocZONE3 0.4 5 10 - VALUE field in set points is the ROC allowed for that zone - TIME field is the minimum time the EXV is kept in the HOLDING state.

24 MCS EXV ROC FUNCTION Super Heat Above Control Zone-
(Special Action) Super Heat Above Control Zone- If above zones and the EXV ROC is negative and < then SP 70 then hold for number of seconds in time field. If in Zone 2 and the EXV ROC is negative and < then SP 69 then hold for number of seconds in time field. If in Zone 1 and the EXV ROC is negative and < then SP 67 then hold for number of seconds in time field. Super Heat Below Control Zone- If in Zone 1 and the EXV ROC is positive and > then SP 67 then hold for number of seconds in time field. If in Zone 2 and the EXV ROC is positive and > then SP 69 then hold for number of seconds in time field. If in Zone 3 and the EXV ROC is positive and > then SP 70 then hold for number of seconds in time field.

25 MCS EXV ROC FUNCTION EXV ROC FAST- EXV ROC CHG-
(Special Action) EXV ROC FAST- If we are opening or closing at 2x, if the absolute value of the super heat ROC is > than the value in SP 71 we will hold for the time in SP 71. EXV ROC CHG- If the super heat state is ‘EXV is HOLDING’ this value specifies the maximum value of the change % that can be made.

26 MCS EXV LOAD ADJ FUNCTION
(MCS CHILLER) # NAME VALUE TIME MAX TIME ALLOWED 9 SUPERHT TRGT 10.5 4 8 11 EXV LOAD ADJ 0.6 - - VALUE field, in EXV LOAD ADJ, is the value the EXV will be adjusted each time the compressor capacity is adjusted. Used on modulating compressors.

27 MCS EXV LOW SUCTION ADJUSTMENT
HOW IT NORMALLY OCCURS Condenser is sized for high ambient We have a low ambient condition Usually when the last stage of condensing is turned on WHAT NORMALLY HAPPENS Because of the pressure drop some of the liquid boils off before it gets to the EXV Now you have liquid and vapor mixed requiring the EXV to open This occurs within 1 minute and system returns to normal in about 3 minutes.

28 GRAPH OF LOW SUCTION OCCURING
Notice the 3rd stage of condensing comes on 15 seconds later the suction psi crashes

29 MCS EXV LOW SUCTION ADJUSTMENT
(MCS CHILLER) # NAME VALUE TIME MAX TIME ALLOWED 13 EXV COURSE ADJ 0.5 4 5 18 LOSUCTPSIDLY 2 - 19 EXV DELAY 60 - Once the Magnum has determined it is in a LOW SUCTION situation it will take the EXV COURSE ADJ and multiply it by the value in the TIME field of SP 13. It will continue to make this adjustment, based on the value in Set Point 56 ‘PULSE or CMP LOAD DELAY’ until the situation is cleared.

30 MCS-EXV FLOODED LEVEL CONTROL
# NAME VALUE TIME MAX TIME ALLOWED 9 REFR LVL TRG 41.5 2 10 REFR ZONE + - 1 12 EXV FINE ADJ 0.2 - 13 EXV COURSE ADJ 0.5 - No Change 15 EXV MIN% 10 - 16 EXV MAX% 100 - 18 LOSUCTPSIDLY 4 - 19 EXV DELAY 60 - 20 EXV STRT TME 5 10 EXV set points 9 & 10 now reflect refrigerant level EXV other set points remain same

31 MCS-EXV FLOODED LEVEL CONTROL
New Set Points # NAME VALUE TIME MAX TIME ALLOWED 9 REFR LVL TRG 41.5 2 109 HI REFR LEVEL 50.0 - 217 LOW REFR LEVEL 32.5 - Set point 9 & 217 specify the range that will be used to maintain and even refrigeration level when required. Set point 109 specifies the upper limit and will cause a safety shutdown.

32 EXV UNIT MODES & STATES - EXV DRIVER MODES - EXV STATES
- EXV LOGIC CHART

33 MCS EXV Unit Modes Auto Mode – The unit defaults to this mode after every power up. In this mode, the MCS-EVX-DRIVER-XX positions the valve according to the analog input control voltage. Manual Mode – When in auto mode, holding the ‘Auto/Manual’ key for 5 seconds, then entering the authorization number switches the unit into Manual mode. In this mode, the valve position is controlled with the keypad’s directional arrows. Power Down Mode – If the main power is disconnected, the controller switches to the power down mode. In this mode, the controller uses internal power to close the expansion valve.

34 MCS EXV Controller States
DESCRIPTION LOCKED OUT The compressor is in a Lockout state. EXV IS CLOSED The associated compressor is OFF and the valve is closed. PRE-PMPDWN The valve has been in a closed state while the system goes through a pump down. EXV IN STARTUP At startup the valve will remain in this state for the time in Set Point #20. At that time the state will be changed to holding, at this point the valve control logic will position the valve. EXV AT 100% This state will be entered when the valve opening reaches 100%. EXV IS HOLDING Refer to EXV Logic Chart, superheat is in control zone and ROC is acceptable. EXV IS OPENING Refer to EXV Logic Chart, superheat is in control zone but rising too fast, ROC less than 1.0. EXV IS CLOSING Refer to EXV Logic Chart, superheat is in the control zone and the rate of change is acceptable, ROC greater than -0.5. LOW SPRHT Refer to EXV Logic Chart, force a course valve adjustment.

35 EXV State Controller States (Continued)
DESCRIPTION OPENING 4x Refer to EXV Logic Chart, superheat is above control zone. OPENING 2x Refer to EXV Logic Chart, superheat is in control zone but rising too fast, the ROC is greater than 1.0. LO PSI OPN Refer to EXV Logic Chart, state indicates that a low suction pressure condition exists. The suction pressure is less than Set point #77 “LOW SUCTION” plus twice the value of Set point #79 “LOW SUCT RELOAD” and the superheat is greater than Set point #9 “SUPERHT TRGT” plus twice the value of Set point #10 “SPRHT ZONE+-.” CLOSING 2x Refer to EXV Logic Chart, superheat is in the control zone and the rate of change is acceptable, the ROC is less than -0.5 and greater than -1.0. CLOSING 4x Refer to EXV Logic Chart, superheat is in control zone but falling too fast, ROC less than -1.0.

36 EXV State Controller States (Continued)
DESCRIPTION HI LVL CLS This state indicates that a high refrigerant level. This state is entered if Set point #109 “HiRefLevel” is active and the superheat is greater than the value of this Set point. EXV MOP CLS Refer to EXV Logic Chart. Maximum operating pressure option is active and it is forcing the EXV to close. In this state the EXV valve’s opening will be reduced. EXV MOP HLD Refer to EXV Logic Chart. Maximum operating pressure option is active and it is forcing the EXV to hold.

37 EXV LOGIC CHART

38 FINE TUNING YOUR MCS-EXV-DRIVER
Part 1 Verify what has been done. Completed the MCS EXV DRIVER setup specifying valve type. Completed the setup for starting valve position in cfg. If a modulating compressor verify starting % is set. Using MCS-Connect, review start up. Set history sample rate at 1 sec Place RUN/STOP switch to RUN

39 FINE TUNING YOUR MCS-EXV-DRIVER
Part 2 Normal MCS CONTROLLER start up. At 2 to 3 minutes from compressor starting, suction superheat should be between ± Control Zone 1. If above Control Zone 1 increase starting valve opening %. If below Control Zone 1 decrease starting valve opening %. At end of startup Discharge temperature should be 110°F or higher. If less than 105°F and we have a modulating compressor and the load is adequate increase the startup speed. Otherwise increase the startup time. Watch changing capacity, if superheat is moving too much as capacity changes, lower LOAD ADJUST set point. Pull Graph at about 15 minutes after starting, this will allow you to review startup results. If Unit is stable but EXV is hunting check time in superheat target. The length of time to calculate superheat ROC should be no less then 3 and no higher than 8. If hunting lower by 1 and watch results.

40 For additional information please visit our website www. mcscontrols
For additional information please visit our website Or call MCS at


Download ppt "Training Presentation"

Similar presentations


Ads by Google