Presentation is loading. Please wait.

Presentation is loading. Please wait.

Chapter 7: STEADY STATE HEAT FLOWS

Similar presentations


Presentation on theme: "Chapter 7: STEADY STATE HEAT FLOWS"— Presentation transcript:

1 Chapter 7: STEADY STATE HEAT FLOWS
Agami Reddy (rev Dec 2017) Elements of sensible loads Sol-air temperature Soil temperature model Below grade heat transfer -basement walls, floor, slab-on-grade 5. Internal heat gains - occupants, lighting, equipment 6. Steady-state heat balance 7. Treatment of unconditioned spaces 8. Zoning in buildings: need and common design practice HCB 3- Chap 7: Steady State Heat Flows

2 HCB 3- Chap 7: Steady State Heat Flows
Heat flows affecting room air temperature Climatic factors Landscaping Size, shape of building Materials used Window size and orientation Type of construction Type of equipment Occupant behavior Equipment sizing: like choose cloth Figure 7.1 The heat flow terms in a load calculation. HCB 3- Chap 7: Steady State Heat Flows

3 Recall: Overall heat loss coefficient of an element
A thermal network is used to represent the heat flow process through an element such as a stud wall HCB 3- Chap 7: Steady State Heat Flows

4 HCB 3- Chap 7: Steady State Heat Flows
Sol-Air Temperature Figure 7.2 Heat flows on a sunlit opaque wall. HCB 3- Chap 7: Steady State Heat Flows

5 HCB 3- Chap 7: Steady State Heat Flows
Sol-Air Temperature By including the radiation heat loss to the sky, we define the sol-air temperature as: HCB 3- Chap 7: Steady State Heat Flows

6 HCB 3- Chap 7: Steady State Heat Flows
Sol-Air Temperature ASHRAE Clear Sky Conditions - Phoenix, AZ Figure 7.3 Diurnal variation of sol–air temperatures (in °C) for a dark- and a light-colored horizontal surface for 2 days in Phoenix, AZ, using TMY3 climatic data. (a) For January 21. (b) For July 21. The corresponding horizontal global radiation (in W/m2) and the ambient dry-bulb temperature (in °C) are also plotted. HCB 3- Chap 7: Steady State Heat Flows

7 HCB 3- Chap 7: Steady State Heat Flows
Basement Heat Losses 2-Dimensional heat transfer problem Ground coupling- heat transfer between basement floor slab and ground Several methods- but these disagree somewhat Troublesome for residences and single-story buildings Soil properties vary widely due to diff types of soil, moisture,… Figure 7.6 Radial isotherms for basement heat loss assumed in the ASHRAE method. HCB 3- Chap 7: Steady State Heat Flows

8 HCB 3- Chap 7: Steady State Heat Flows
Basement (Below grade) For the part that is above ground (grade) : use equations discussed in Chap 2 For the part that is below ground (grade): use ASHRAE method Outside Temperature : surface soil temperature (discussed next) Indoor Temperature: If the basement is heated – indoor air temperature If the basement is not heated – then the basement temperature has to be calculated as discussed later on If the basement has certain heat sources (boiler or hot pipe is in basement), then these have to be considered as well Tb HCB 3- Chap 7: Steady State Heat Flows

9 Soil Temperature Model
HCB 3- Chap 7: Steady State Heat Flows

10 HCB 3- Chap 7: Steady State Heat Flows
For example: Washington DC has a average annual temp. = 45.7o F From figure, Amplitude= 18o F Figure 7.4 Map of amplitude of annual soil temperature swings used for ground coupling calculations (°F). For amplitude in SI units, divide by 1.8°F/K. HCB 3- Chap 7: Steady State Heat Flows

11 HCB 3- Chap 7: Steady State Heat Flows
…….. HCB 3- Chap 7: Steady State Heat Flows

12 HCB 3- Chap 7: Steady State Heat Flows
7.7 7.8 HCB 3- Chap 7: Steady State Heat Flows

13 HCB 3- Chap 7: Steady State Heat Flows
=11.1 oC, The annual variations for three different depths shown in Fig. 7.5 Surface soil temperature varies the greatest with an amplitude of about 10 0C. At 3 m depth, the amplitude is 3.5 0C with a 3 month phase shift HCB 3- Chap 7: Steady State Heat Flows

14 HCB 3- Chap 7: Steady State Heat Flows
Fig. 7.5 Soil Temperatures for Tempe, AZ HCB 3- Chap 7: Steady State Heat Flows

15 HCB 3- Chap 7: Steady State Heat Flows
Heat Losses from Basement Walls Basement wall Basement floor HCB 3- Chap 7: Steady State Heat Flows

16 HCB 3- Chap 7: Steady State Heat Flows

17 HCB 3- Chap 7: Steady State Heat Flows

18 HCB 3- Chap 7: Steady State Heat Flows
use Eq.(7.9 for) Use Eq.(7.10) HCB 3- Chap 7: Steady State Heat Flows

19 HCB 3- Chap 7: Steady State Heat Flows
Floor on ground (or Slab on grade) No crawl space, no basement. Heat loss is greatest near perimeter Heat loss is proportional to perimeter length rather than area where Fp is edge or perimeter heat loss coefficient BTU/h-°F-ft P is the perimeter or total length of outside edges of floor, ft Figure 7.7 Schematic diagram of method of insulating slabs and foundations. HCB 3- Chap 7: Steady State Heat Flows

20 HCB 3- Chap 7: Steady State Heat Flows

21 HCB 3- Chap 7: Steady State Heat Flows
Crawlspace Heat Loss Crawl space: A shallow space below the living quarters of a house without a basement normally enclosed by the foundation wall. Or, a shallow space below the roof. It is used for visual inspection and access to pipes and ducts- often vented Need ventilation to prevent moisture condensation and mold! HCB 3- Chap 7: Steady State Heat Flows

22 Internal Loads- Occupants
HCB 3- Chap 7: Steady State Heat Flows

23 HCB 3- Chap 7: Steady State Heat Flows
Internal Loads- Lighting Based on installed lighting systems 7.13 PL = total installed lighting power FUL = lighting use factor (or diversity factor) [0,1] FSA = special allowance factor - fraction of power consumed by fixture to that of light - for incandescent lamps = 1 - for fluorescent fixture = 1.2 (in general) Based on space area. This is a simpler approach used during design phase. Simply assume max allowable lighting power densities (LPD) for the space as stipulated by ASHRAE 90.1 (2010). Some typical values are shown in Table 7.7 For offices LPD about 12 W/m2 (1.1 W/ft2) HCB 3- Chap 7: Steady State Heat Flows

24 HCB 3- Chap 7: Steady State Heat Flows

25 HCB 3- Chap 7: Steady State Heat Flows
Equipment Loads Heat gains from appliances, motors, computers, copiers are quite subjective, intermittent and harder to estimate 7.14 FUM = motor use factor or fraction of time operated FLM = load factor or fraction of rated motor power delivered under condition analyzed HCB 3- Chap 7: Steady State Heat Flows

26 HCB 3- Chap 7: Steady State Heat Flows
Discretion and caution should be exercised when using such tables HCB 3- Chap 7: Steady State Heat Flows

27 HCB 3- Chap 7: Steady State Heat Flows

28 Treatment of One-Zone Spaces
7.18 7.19 7.21 HCB 3- Chap 7: Steady State Heat Flows

29 HCB 3- Chap 7: Steady State Heat Flows

30 HCB 3- Chap 7: Steady State Heat Flows
Almost 50% Note: - Solar loads neglected - Inefficiency of lights and equipment adversely impact building electric use in two ways: direct cost of electricity and additional cooling electricity HCB 3- Chap 7: Steady State Heat Flows

31 Unconditioned Attached Spaces
Figure 7.11 Sketch for Example 7.11 of an unheated attached garage. HCB 3- Chap 7: Steady State Heat Flows

32 HCB 3- Chap 7: Steady State Heat Flows
7.29 The garage temperature is quite close to the outdoor temperature because of the poorer insulation. Heat lost through garage = 0.1 x 200 x ( ) = 759 Btu/h With no garage, heat lost = 0.1 x 200 x (70-30) = 800 Btu/h, a 5% difference HCB 3- Chap 7: Steady State Heat Flows

33 HCB 3- Chap 7: Steady State Heat Flows
Zoning of Spaces Two common design practices: Interior/exterior Building orientation Definition: An air conditioning zone is a room or group of rooms in which comfortable conditions can be maintained by a single controlling device Best to zone areas with similar thermal disturbance (weather, solar, internal) and close to each other Zones share one set of Sensor, Controller, AC system Figure 7.12 Example of recommended zoning. Thick lines represent zones, labeled 1 through 5. Dashed lines represent subzones. Each zone has one thermostat Zoning necessary because heat gains from different directions are non-uniform HCB 3- Chap 7: Steady State Heat Flows

34 HCB 3- Chap 7: Steady State Heat Flows

35 HCB 3- Chap 7: Steady State Heat Flows

36 HCB 3- Chap 7: Steady State Heat Flows
Outcomes Knowledge of the various heat flows affecting room temperature Understanding of sol-air temperature concept and how to calculate it Familiarity with the soil temperature model and its application Understanding of the ASHRAE method to calculate below grade heat losses from basements and slab-on-grade construction Knowledge of how to calculate internal loads from occupants, lighting and equipment Be able to determine total heat transmission coefficient of a building Be able to perform steady-state analysis of a space to evaluate relative contributions of various heat gains Be able to analyze heat flow interactions in unconditioned spaces Understanding of why interior spaces have to be zoned and common design practice HCB 3- Chap 7: Steady State Heat Flows


Download ppt "Chapter 7: STEADY STATE HEAT FLOWS"

Similar presentations


Ads by Google