Download presentation
1
1
2
Fluke Corporation European Headquarters Eindhoven, the Netherlands
Corporate Headquarters near Seattle, WA, USA
3
Fluke Corporation Founded in basement of John Fluke’s home in Springdale, Connecticut, USA in 1948 2,400 employees worldwide Offices in 21 countries around the world Distributed in more than 100 countries Manufacturing facilities in Everett (USA), the Netherlands, the U.K. and China
4
Measurements for Power Quality maintenance
5
Industry trends Growing concern for personal safety
complexity of today’s systems, bring over voltage risks international & national regulations (& guidance) Increased attention on power related issues deregulation of power distribution Increasing loads on power systems Shift from reactive maintenance to preventive maintenance More work by fewer people Decreasing maintenance budget More complex equipment
6
History of Maintenance Practices
20 years ago… The primary goal of maintenance was loss prevention and the fundamental requirement was to provide the basic need at minimum cost. Today… Companies are researching all possible means to extend the productive life Tool use by application* Scheduled Thermal Imaging Ultrasonic testing Vibration Analyzers Recorders/Loggers Motor/Circuit Test Oil Testers Predictive TREND PQ Analyzers IR Temperature Insulation testers Preventive Network Test Scope Meters Loop Cal. Clamp Meter DMM Simple Testers Reactive
7
Types of Maintenance Break-down Reactive Cost Maintenance
Time Cost Reactive Maintenance Repair it when it fails Preventive Maintenance Maintenance at regular intervals Time Cost Time Cost Predictive Maintenance Problem detected before predicted failure. Maintenance planned ahead
8
Power Quality Effects of bad power quality are not immediately obvious
Bad power quality can come from anywhere Consequences could be severe (production loss) Power quality problems are a root cause: Malfunction Shutdown Excessive energy cost Decreased lifetime of equipment
9
Example
10
Example This manufacturer is the third biggest power consumer of the local energy supplier. They produce fiber materials for sports equipment. A new heating system was installed on a key process During a routine check with a thermographic camera it was discovered there had been an increase in temperature of the neutral conductor. Check with a current clamp revealed 20A Phase currents & 40A Neutral current
11
Example A power quality logger was used to gather the needed data.
Connection was only possible on the distribution board connection, fused with 250A, not at the heater due to safety reasons. This makes analysis a bit more complex since the heater represents a small part of the total load
12
Results Current trend Neutral current
Question: Why does the neutral carry 60A and not only 6A which would be the difference between currents in L1, L2 and L3?
13
Results 2 Conclusion; there is a third harmonic present in the neutral
14
Conclusion Further analysis showed that:
The reason for the neutral conductor overload clearly is the heating installation, which generates high triplen harmonics More unbalances present so further more measurements would be very helpful. What was the cause? Regulators built into the heating system require harmonic filters which were not installed 10A fund 35A 3rd
15
Conclusion Thermal survey gives early warning of a problem
Addition of new equipment can introduce problems which are not obvious or visible Performing system check “before” and “after” can prevent future failures “Balanced” loads still can have harmonic content running in the neutral
16
Measurement of Electrical Systems
17
Measurement Safety Power Quality Measurement
The effect of distortion on simple test tools Measurement of Harmonics Measurement Specifications Typical measurements Power Quality Measurement Equipment Basic Measurements Test equipment types
18
Measurement Safety Power Quality Measurement
The effect of distortion on simple test tools Measurement of Harmonics Measurement Specifications Typical measurements Power Quality Measurement Equipment Basic Measurements Test equipment types
19
Safety of Measurement Example DMM fitted with low energy fuse used incorrectly on a high energy circuit
20
EN61010 LV Directive Implemented in 1998
All instruments have to be tested by an independent test house (2004) Each instrument must be marked with an Overvoltage Category ( CAT I, II, III, IV ) As well as a voltage level (300, 600, 1000 Volts) 35 7 7
21
Category Rating CAT IV - Electricity meters and primary connection
CAT III - Permanent connection to the fixed installation. CAT II - Appliances, portable tools etc. CAT I - Protected electronic circuits. 17 11 11 39
22
Voltage Rating per Category Test Impulse Rating
37 9 9
23
IEC 1010 / EN61010 Regulations are not an option
Second edition EN61010 ( 2004 ) requires independent testing Remember Test leads are CAT rated ...
24
Available from Fluke Free Safety DVD Not sales focused
Information on EN61010 Interview with an arc blast survivor
25
Measurement Seminar Safety Power Quality Measurement
The effect of distortion on simple test tools Measurement of Harmonics Measurement Specifications Typical measurements Power Quality Measurement Equipment Basic Measurements Test equipment types
26
Harmonics Distorted waveforms
Harmonic frequencies combine with the fundamental sine wave to form non-sinusoidal (distorted) waveforms. =
27
Effect of distortion on test tools
28
59.2 A AC 40.5 A AC Measurement Methods
Both Clamp Meter’s are calibrated and functioning correctly 59.2 A AC 40.5 A AC
29
Measurement Sinewave How does a measurement device measure the effective value of a waveform ? Two Methods - Averaging & True RMS
30
Averaging Measurement
Effective (RMS) value = 1.11 X Average value.
31
Non-linear Loads Switching Power Supply
Volts Amps What happens to the measurement device if the waveform is distorted by non-linear loads ?
32
Measurement Distorted Waveform
Effective (RMS) value = 1.85 x Average value. An averaging measurement device (1.11 x) would read up to 40 % too low. RMS AVG
33
Averaging Measurement
Nuisance tripping at 60A ? True RMS Measurement Averaging Measurement 59.2 A AC 40.5 A AC
34
True RMS Measurement True RMS / Harmonics
A True RMS meter calculates the effective heating value of the distorted waveform This will include all harmonics .
35
Crest Factor Peak value = X RMS value. 1.414 = Crest Factor.
36
Crest Factor Distorted Waveform
Peak value = 2.9 X RMS Value. 2.9 = Crest Factor. Peak RMS
37
Crest Factor Distorted Waveforms
C.F. = 1.43 C.F. = 2.39 C.F. = 4.68 Professional Multimeters usually rated at CF <3 High Quality units rated at CF of 6 Power Quality Analyzer CF >11 .
38
Power Measurement Two Power Factors
Screen Shots from a Fluke 43 Single Phase and a Fluke 434 Three Phase analyser
39
Power Measurement System with no Harmonic content
True Power (W) Reactive power (kVAr) Cos φ (dpf) = true power (fundamental) Apparent power (kVA)
40
Power Measurement System with Harmonic content Reactive power (kVAr)
True Power (W) Reactive power (kVAr) Reactive power (Harmonic component) Cos φ (dpf) : true power/Reactive power (fundamental) PF: true power/reactive power (incl harmonics) Apparent power including harmonics (kVA)
41
Power Measurement Two Power Factors !
Screen Shots from a Fluke 43 Single Phase and a Fluke 434 Three Phase analyser
42
Measurement where Harmonics are present
Always use True RMS Check the crest factor rating When measuring power be aware of PF vs Cos φ/(DPF) C.F. = 1.43 C.F. = 2.39 C.F. = 4.68
43
2) Measurement of Harmonics
44
VIRTUALLY ALL HARMONIC PROBLEMS ARE GENERATED “IN HOUSE”
EN50160 Harmonics Upper limits for individual harmonic voltages at the supply terminals in % of nominal voltage. 95% of 10-minute average Vrms over 1 week must be below limits Odd harmonics Even Harmonics Not multiples of 3 Multiples of 3 Order h Relative voltage 5 6 % 3 5 % 2 2 % 7 9 1.5 % 4 1 % 11 3.5 % 15 0.5 % 6…24 13 3 % 21 17 19 23 25 VIRTUALLY ALL HARMONIC PROBLEMS ARE GENERATED “IN HOUSE”
45
IEC 61000-4-30 specification Test Equipment
Class A Class B Measurement Interval Accuracy Power frequency Hz 10 sec ± 10mHz Manufacturer to indicate Magnitude supply voltage Vrms 10 cycles ± 0.1% Flicker (IEC ) Plt 2 hr ± 5% Voltage dips, swells and interruptions, rapid voltage changes ½ cycle Vrms 10 ms ± 0.2% Unbalance (method of symmetrical components) Vrms fundamental ± 0.15% (uncert.) Harmonics (IEC ) THD, Harm V, A, Inter harmonics ± 1-5% Transients (not specified) V peak 50 μ sec (200KS/s) Mains signaling Inter harmonic Flagging Dip, swells, interruptions might create unreliable readings of Hz, Vrms, Unbalance and Harm. Therefore Must be re flagged (dirty) to avoid miss interpretation Not specified Time synchronization External clock; GPS 1 period
46
Harmonic Measurement For troubleshooting Check the harmonics present
Check for the levels of the harmonics Look for recognizable patterns 50 Hz 100 Hz 150 Hz 200 Hz
47
Harmonic Measurement – PC Load
V, A, Hz Measurement Harmonic Measurement 3rd Harmonic Content
48
Elec. Fluorescent Lighting Ballast
Harmonic Measurement PC / IT Load Elec. Fluorescent Lighting Ballast 6 Pulse Bridge 12 Pulse Bridge
49
Measurement Seminar Safety Power Quality Measurement
The effect of distortion on simple test tools Measurement of Harmonics Measurement Specifications Typical measurements Power Quality Measurement Equipment Basic Measurements Test equipment types
50
Types of Measurement Tools
Power Quality Troubleshooting / Survey tools Devices designed as a measurement tool Simple to use / Immediate measurements Troubleshooting / Survey tool / some logging Power Quality “Logging” Devices designed for long term monitoring Record every parameter for detailed analysis Predictive Maintenance
51
Power Quality Troubleshooting & Surveys
Measurements Volts Amps & Frequency Power Harmonics Dips & Swells Transients Unbalance Flicker Inrush Temperature
52
1) Volts, Amps & Frequency
Using a Power Quality Analyser View all of the main parameters at point of connection Graphical as well as numeric display can help highlight potential problems Scope Vector Trend
53
2) Power Measurement Typical power measurement information
Shows the sides of the triangle
54
3) Three Phase Harmonic Measurement
55
4) Transient Measurement
Cause….. interference Difficult to capture Triggering of ‘scopes difficult…width, timing, peak value ? Modern power quality analyzers purpose built for the job Envelope trigger Accurate real time stamping is essential +X% 240V - X%
56
5) Dips and Swells Recording of upstream and downstream sags can indicate loads causing problems Upstream Sag Downstream Sag
57
6) Unbalance The phase diagram gives a quick indication of phase relationships and balance In this example voltage unbalance is very small, but current unbalance is nearly 19%.
58
7) Flicker Measurements
A reading greater than 1 means that most people will perceive flicker in an incandescent bulb Measurement Pst (1 min): Short-term flicker over 1 minute Pst: Short-term flicker over 10 minutes Plt: Long-term flicker over 2 hours
59
Three Phase Inrush Measurement
Inrush Current Measurement Momentary peak of current during switch on. Current clamps can capture peak reading Analyzers can give time measurement Screen Shot of a PQA showing start-up current generated by a cooling system Three Phase Inrush Measurement
60
9) Temperature Many power quality problems initially result in an increase in temperature of components, connectors, cables and machinery Infra red non contact measurement is the ideal way to locate this type of problem
61
Why infrared non-contact measurement?
1) Measurement from distance Dangerous to contact (Electrical) Difficult to reach Moving objects 2) Measurement without contact Very hot objects Where contact would damage, contaminate or change temperature (Food & Chemical)
62
Example Substations
63
Substations Both qualitative and quantitative inspections are Required to determine a fault
64
Electrical connections
The connections on this evaporator pump read over 50 degrees hotter on phase 3
65
Electrical connections
The temperature readouts show that connection on the centre phase of this main lighting disconnect are hot, suggesting an unbalanced load
66
Electrical connections
A PVC cable should not exceed 70 C in Europe, meaning 40 C for max ambient temperature and 30 C for overheating above ambient. Note. In the USA made application notes the value mention for overheating is 40 C, not 30 C
67
Electrical unbalance or overload?
68
Electrical unbalance or overload?
Where is the increased resistance? On the left or on the right contact? A hot spot is not necessarily a faulty connection!
69
Fluke Power Quality
70
Single Phase Troubleshooting
Fluke 345 Power Clamp Fluke 43B Analyzer
71
Three Phase Troubleshooting
Fluke 435 Power Quality Troubleshooter Fluke 1735 Power Logger
72
Fluke 1740 Series Power Quality Logger Fluke 1760 Power Quality Logger
Power Quality Logging Fluke 1740 Series Power Quality Logger Fluke 1760 Power Quality Logger
73
FlukeTi40 & Ti50 Advanced Camera’s FlukeTi20 Thermal Imaging Camera
74
More information Fluke Power Quality Data available in the exhibition area DVD’s Thermal Imaging Application DVD Safety DVD – EN61010 Power Quality Measurement DVD Fluke Website Short term requirement ?
Similar presentations
© 2025 SlidePlayer.com Inc.
All rights reserved.