Presentation is loading. Please wait.

Presentation is loading. Please wait.

AC500 High Availability System – CI590 Overview

Similar presentations


Presentation on theme: "AC500 High Availability System – CI590 Overview"— Presentation transcript:

1 AC500 High Availability System – CI590 Overview
Redundant CS31- FieldBus – Interface 16 digital configurable channels Potential isolated Input delay: 0.1ms,1ms, 8ms,32ms typical: 8ms Input delay defined by PLC configuration Fast counter with 9 modes Internal power supply by I/O- bus For TU551 and TU552 Error indication by LED and CPU

2 AC500 High Availability System – CI590 Overview
CI590 Module Parameters

3 AC500 High Availability System – CI590 Overview
19/05/2018 AC500 High Availability System – CI590 Overview CI590 LED Details PWR LED ON CI590 Power ON OFF CI590 Power OFF PWR CS31-A S- ERR I/O ERR RUN A RUN B SYNC ERR CS31-B DRAFT

4 AC500 High Availability System – CI590 Overview
19/05/2018 AC500 High Availability System – CI590 Overview CI590 LED Details Xxx ERR Led ON PLCs have sent different configurations PWR CS31-A CS31-B S- ERR I/O ERR RUN A RUN B SYNC ERR OFF - Blink slow Switchover has happened Blink fast CI590 is not parameterized DRAFT

5 AC500 High Availability System – CI590 Overview
19/05/2018 AC500 High Availability System – CI590 Overview CI590 LED Details CS31-A / B LEDs ON PLC A/B is available PWR CS31-A CS31-B S- ERR I/O ERR RUN A RUN B SYNC ERR OFF PLC A/B is not available Blink No bit life from PLC A/B DRAFT

6 AC500 High Availability System – CI590 Overview
19/05/2018 AC500 High Availability System – CI590 Overview CI590 LED Details PWR CS31-A CS31-B S- ERR I/O ERR RUN A RUN B SYNC ERR SUM ERROR Same functioning as DC551 I/O BUS COMMUNICATION DRAFT

7 AC500 High Availability System – CI590 Overview
19/05/2018 AC500 High Availability System – CI590 Overview CI590 LED Details RUN A / B LEDs PLC A PLC B OFF ON PLC A Primary PWR CS31-A CS31-B S- ERR I/O ERR RUN A RUN B SYNC ERR OFF ON PLC B Primary ON Two primary information received. Primary PLC selected is the one corresponding to LED ON. Blink } ON Blink OFF } No primary information received. Primary PLC selected is the one corresponding to LED blinking. Blink OFF Blink DRAFT

8 AC500 High Availability System – CS31 Bus Connection
19/05/2018 AC500 High Availability System – CS31 Bus Connection COM1 OF THE AC500 CPU 1 2 3 4 5 6 7 8 9 CPU A / B – COM1 CS31 Connection CPU A / B - OUT Term. P RxD/TxD-P RxD/TxD-N Term. N RTS TxD SGND RxD CTS 120 Ω DRAFT

9 AC500 High Availability System – CS31 Bus Connection
19/05/2018 AC500 High Availability System – CS31 Bus Connection LINE A / B OF THE CI590 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 1.8 2.8 3.8 4.8 CI590 1.9 2.9 3.9 4.9 2 x CS31 16DC Input 24VDC Output 24VDC 0.5A UP 24VDC 200W CH-ERR4 CH-ERR3 C12 C8 C9 C10 C11 UP ZP C14 C15 R11 C13 R12 B1 1 2 FE R21 C4 C0 C1 C2 C3 C6 C7 C5 ADDR x10 ADDR x1 5 B2 R22 PWR CS31-1 CS31-2 S- ERR I/O ERR RUN1 RUN2 Xxx ERR 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 R1 R2 B1 B2 FE UP ZP 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 R1 R2 B1 B2 FE UP ZP CPU B - IN CPU A - IN CPU B - OUT CPU A - OUT Connection Line A Connection Line B DRAFT

10 AC500 High Availability System – CS31 Bus Connection
19/05/2018 AC500 High Availability System – CS31 Bus Connection LINE A / B OF LAST CI590 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 1.8 2.8 3.8 4.8 CI590 1.9 2.9 3.9 4.9 2 x CS31 16DC Input 24VDC Output 24VDC 0.5A UP 24VDC 200W CH-ERR4 CH-ERR3 C12 C8 C9 C10 C11 UP ZP C14 C15 R11 C13 R12 B1 1 2 FE R21 C4 C0 C1 C2 C3 C6 C7 C5 ADDR x10 ADDR x1 5 B2 R22 PWR CS31-1 CS31-2 S- ERR I/O ERR RUN1 RUN2 Xxx ERR 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 R1 R2 B1 B2 FE UP ZP 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 R1 R2 B1 B2 FE UP ZP CPU B - END CPU A - END Connection Line A Connection Line B DRAFT


Download ppt "AC500 High Availability System – CI590 Overview"

Similar presentations