1 Chapter 8: The Cooling Load Cooling load is the rate at which energy must be removed from a space to maintain the temperature and humidity at the design values. Cooling load is determined by internal and external heat gains as well as structure variable heat storage, all of which are transient in nature Instantaneous heat gain is the heat received by the space being conditioned. Instantaneous cooling load is the heat gain by the air in the space

2 The Cooling Load This figure is for solar heat gain (TSHG: total solar heat gain) and the associated cooling load. A heavy weight (HW) construction has the benefit of reducing the peak cooling load, which reduces the size of required coolers. Cooling load attributed to lights. Actual cooling load will approach the heat gain if lights remain on for a sufficiently long time.

3 Heat Gains

4

5 Internal Heat gain -People Adjusted heat gain is a nominal value, based on the normal percentage of men, women, and children for the application listed.

6 Internal Heat Gain-Lights/Miscellaneous Equipment Miscellaneous Equipment include motors, appliances, kitchen installation, lab facilities, office equipment, etc.

7 External Heat Gain-Radiation Solar radiation (short wavelength radiation):

8 Solar-Irradiation on a Surface (Google)

9 Thermal Radiation (long wavelength)

10 Images of Radiation Heat Transfer between surfaces (Google)

11 Thermal Radiation (long wavelength)

12

13 Exterior Convection

14

15 Image of Convection Heat Transfer between a surface and a fluid (Google)

16 Overview of the Heat Balance Method

17 Heat Balance on the jth exterior surface at a given time

18 Heat Balance on jth Interior surface at a given time

19 Heat Balance on the Zone Air

20 Design Condition Indoor design conditions: For average jobs in the United States and Canada, a condition of 75 F or 24 C dry bulb temperature and relative humidity of 50% is typical when activity and dress of the occupants are light. Outdoor design temperatures would depend on the selection of the high end temperatures that equal or exceed a percentage of the hours that occurred during a year. A smaller percentage may result in a greater excess cooling capacity to be installed. (Table B-1 (1a: English/1b: SI): MWS = mean coincident wind speed, MWD = mean coincident wind direction, MWB = mean coincident wet bulb temperature, MDB = mean coincident dry bulb temperature, HR: humidity ratio, in grains of water per pound of air (7000 grains equal 1 pound), Range = daily range of db temperature (the difference between the average maximum and average minimum for the warmest month).

21 HvacLoadExplorer Software Based on the heat balance method (HBM). It allows a user to run a cooling or heating load calculation for an entire building to determine the cooling or heating loads and airflow rate of all the rooms in a building or zone. It allows a user to calculate the conduction transfer function coefficients, response factors, radiant time series factors. For purposes of load calculations, a building may be thought of as being organized in a hierarchical fashion. That is, a building is made up of zones, zones are made up of rooms, and rooms are made up of walls, roofs, floors, and other heat gain elements such as people, lighting, equipment, and infiltration. Zones are collections of one or more rooms, all controlled to the same air temperature to allow the user to compute total loads for collections of rooms. A user may wish to include all rooms served by a particular cooling coil in a single zone so that the peak load on the coil can be readily determined. Double-clicking on a zone will show all of the rooms in the zone; double-clicking on a room will show all of the heat gain elements in the room.

22 Quick Start Guide First, to start describing a new building, go to the File menu and select “New”. This will ask you to specify a file name. After this step, zones may be added to the building, rooms may be added to the zone, and heat gain elements may be added to the room, with the “Add Node” button shown in Figure 1.1. Jumping ahead (assuming many of the additional steps are intuitive) users need to be aware that when they specify a wall, roof, or floor, it is important to specify an external boundary condition, as shown in Fig. 1-2. “TOS” should be used for exterior surfaces; “TA” for interior surfaces SW absorptivity = short wave absorptivity, related to solar irradiation LW emissivity = long wave emissivity, related to thermal radiation

23 Main view

24 Tree view First, to start describing a new building, go to the File menu and select “New”. This will ask you to specify a file name. After this step, zones may be added to the building, rooms may be added to the zone, and heat gain elements may be added to the room, with the “Add Node” button shown in Figure 1.1. Jumping ahead (assuming many of the additional steps are intuitive) users need to be aware that when they specify a wall, roof, or floor, it is important to specify an external boundary condition, as shown in Fig. 1-2. “TOS” should be used for exterior surfaces; “TA” for interior surfaces SW absorptivity = short wave absorptivity, related to solar irradiation LW emissivity = long wave emissivity, related to thermal radiation