Problem Solving using Error Code Saijo Denki Inverter R-410A

Similar presentations


Presentation on theme: "Problem Solving using Error Code Saijo Denki Inverter R-410A"— Presentation transcript:

1 Problem Solving using Error Code Saijo Denki Inverter R-410A

2 Error Detection using Error Code from 7-SEG
01/11/10 Error Detection using Error Code from 7-SEG 2

3 7-SEG display at indoor unit
Error Code Detection Saijo Denki Inverter air conditioner can show error code in 2 ways 7-SEG display at the indoor unit. We can check Error code by pressing CLR button in the remote control 4 times continuously in 3 seconds. Get Error Code from smart phone application “Saijo Denki Inverter – Engineer”. 7-SEG display at indoor unit Show Error

4 LED Display at indoor unit
01/11/10 LED Display at indoor unit LED POWER. OFF : AC OFF ON : AC ON BLINK 3 times: Room temperature thermistor fail BLINK 4 times: Indoor Inlet temperature sensor fail LED COMP. ON : Compressor ON BLINK very frequently : Indoor unit can not communicate with Outdoor unit BLINK slowly: Air Conditioner in Error. Please press CLR button at remote control 4 times in 3 seconds to check Error Code at 7-SEG of indoor unit

5 Error Code Table is at every indoor unit.
01/11/10 Error Code Table is at every indoor unit. Status Number of LED’s blink Hot Cool LED comp/ power Water floating ID inlet fail ID room tmp fail OD comp top tmp fail OD inlet tmp fail OD discharge tmp fail OD coil tmp fail OD comp over OD ctrl fail OD comp wire fail Sys liq qt fail OD cooling fail Water floating OD comp current fail ID cooling fail Restore the status by turn off air condition and press “CLR” 4 time at remote Clear error code by press “CLR” 10 time consciously 5

6 Sensor Fail Error from Sensor Fail Status 01/11/10 6
Number of LED’s blink Hot Cool LED comp/ power Water floating ID inlet fail ID room tmp fail OD comp top tmp fail Error from Sensor Fail OD inlet tmp fail OD discharge tmp fail OD coil tmp fail OD comp over OD ctrl fail OD comp wire fail Sys liq qt fail OD cooling fail Water floating OD comp current fail ID cooling fail Restore the status by turn off air condition and press “CLR” 4 time at remote 6

7 Resistance of Sensor is 5K at 25 c temperature
01/11/10 Error 3,4,5,13,14,15: Room Temperature Sensor Ambient sensor Discharge sensor Sensor is broken or damage Replace / Connect Sensor to indoor unit Mid coil sensor Room temp sensor Yes No Mid cooling coil sensor Check Sensor Resistance Change Room temperature sensor Change Indoor PCB Board Normal Abnormal Resistance of Sensor is 5K at 25 c temperature 7

8 Error 17: Compressor Overload
01/11/10 Error 17: Compressor Overload Outdoor PCB detects Overcurrent to compressor Air Flow at outdoor unit is good or not ? Make sure that outdoor unit has good air flow; remove obstacle or clean condenser coil No Yes Check too much refrigerant in the system ? Decrease refrigerant in the air conditioner Too much Normal 8

9 Error 17: Compressor Overload (Cont)
01/11/10 Error 17: Compressor Overload (Cont) Outdoor PCB detects Overcurrent to compressor Check Power Line: Supply Voltage is between 175–260 V ? Make sure supply voltage is between 175 – 260 V No Supply Voltage must be between V Yes Replace Outdoor Control Box 9

10 Replace Outdoor Control Box
01/11/10 Error 11,18,19: Error in Outdoor control box Error in Outdoor Control Box Check if Electrical wiring from compressor to outdoor control box is tight and U V W is in order Make tight wiring and ensure U V W is in order No Yes Replace Outdoor Control Box Problem at outdoor control box Work Properly Problem at compressor No 10

11 Replace Outdoor Control Box
01/11/10 Error 21: Wiring to compressor loosen Error in Outdoor Control Box Check if Electrical wiring from compressor to outdoor control box is tight and U V W is in order Make tight wiring and ensure U V W is in order No Yes Replace Outdoor Control Box Problem at outdoor control box Work Properly Problem at compressor No 11

12 Check (1) Too low refrigerant (2) Clog in refrigerant line ?
01/11/10 Error 22,31 Discharge Over Temperature t Temperature at Discharge Pipe is more than 100 c Check Outdoor Air Flow ? Make sure outdoor air flow is good and condenser coil is clean Not good Good Check (1) Too low refrigerant (2) Clog in refrigerant line ? Make sure refrigerant amount is properly charge and no clog in this system Remark: if refrigerant too low, also check leakage in the system Yes ไม่ 12

13 Check Resistance of Discharge Pipe Sensor, ok ?
01/11/10 Error 22,31 Discharge Over Temp. (Cont.) t Temperature at Discharge Pipe is more than 100 c Check Resistance of Discharge Pipe Sensor, ok ? NO Replace Discharge Pipe sensor OK Replace Outdoor Control Box Normal Resistance (Ω) of sensor Temperature Resistance 25 c K ohm 30 c K ohm 35 c K ohm 13

14 Error 23: Outdoor Mid Coil temperature too high
01/11/10 Error 23: Outdoor Mid Coil temperature too high Temperature at Mid Coil Sensor is more than 60 c Check Outdoor motor Replace Outdoor Motor Abnormal Normal Check Outdoor Air Flow Improve Outdoor Air Flow; remove obstacle to air flow of outdoor unit and/or clean condenser coil Abnormal Normal 14

15 Check too much refrigerant ?
01/11/10 Error 23: Outdoor Mid Coil temperature too high (Cont.) Temperature at Mid Coil Sensor is more than 60 c Condenser block Clean Condenser Yes No Check too much refrigerant ? Make sure refrigerant amount is properly charge Yes No 15

16 Temperature at Mid Coil Sensor is more than 60 c
01/11/10 Error 23: Outdoor Mid Coil temperature too high (Cont.) Temperature at Mid Coil Sensor is more than 60 c Check resistance of outdoor mid coil temperature sensor Replace Outdoor Mid Coil Temperature Sensor Abnormal Normal Replace Outdoor Control Box 16

17 Current is 130% of nominal current input
01/11/10 Error 24: Overcurrent t Current is 130% of nominal current input Check Outdoor Air Flow is normal Improve Outdoor Air Flow; remove obstacle to air flow of outdoor unit and/or clean condenser coil Abnormal Normal Check refrigerant amount is too much or not ? Make sure refrigerant amount is properly charge Yes No 17

18 Check current input of compressor is 130% of nominal current input ?
01/11/10 Error 24: Overcurrent t Current is 130% of nominal current input Check current input of compressor is 130% of nominal current input ? Replace Outdoor Control Box No Yes Replace Compressor 18

19 Check Indoor Air Flow is blocked ?
01/11/10 Error 26,27: Indoor Coil Frost t Indoor Inlet Temperature is equal or below 0 c Check Indoor Fan motor ? Replace Indoor Fan Motor Fail Normal Check Indoor Air Flow is blocked ? Make sure Indoor Air Flow is good; clean evaporator and/or clean indoor filter Block No 19

20 Check Resistance of Indoor Inlet Sensor, ok ?
01/11/10 Error 26,27: Indoor Coil Frost t Indoor Inlet Temperature is equal or below 0 c Check Resistance of Indoor Inlet Sensor, ok ? NO Replace Discharge Pipe sensor OK Replace Outdoor Control Box Normal Resistance (Ω) of sensor Temperature Resistance 25 c K ohm 30 c K ohm 35 c K ohm 20

21