Presentation is loading. Please wait.

Presentation is loading. Please wait.

Lecture 09Electro Mechanical System1 Chapter 11 Special Transformers.

Similar presentations


Presentation on theme: "Lecture 09Electro Mechanical System1 Chapter 11 Special Transformers."— Presentation transcript:

1 Lecture 09Electro Mechanical System1 Chapter 11 Special Transformers

2 Lecture 09Electro Mechanical System2 Dual-voltage distribution transformer  Transformers that supply electric power to residential areas generally have two secondary windings, each rated at 120 V.  The windings are connected in series, and so the total voltage between the lines is 240 V while that between the lines and the center tap is 120 V. The center tap, called neutral, is always connected to ground.  These kind of transformers are still used in industry where two voltages are required.

3 Lecture 09Electro Mechanical System3 Autotransformer  On some occasions it is desirable to change voltage levels by small amount  For example, it may be necessary to increase a voltage from 110 to 120 V or from 13.2 to 13.8 kV.  These small rises may be made necessary by voltage drops that occur in power systems a long way from the generators.  In such circumstances, it is wasteful and excessively expensive to wind a transformer with two full windings, each rated at about the same voltage.  A special-purpose transformer, called an autotransformer, is used instead for such increase/decrease.

4 Lecture 09Electro Mechanical System4 Autotransformer  When we connect load at output CA  I 2 immediately causes I 1 to flow  BC will carry current I 1 and CA will carry current I 2 – I 1  The mmf due to I 1 must be equal to mmf due I 2 – I 1  Which can be further reduced to  Neglecting transformer losses and excitation current.Power drawn by the load must be equal to supplied power Home Work: Page 227 Example 11-1

5 Lecture 09Electro Mechanical System5 Conventional transformer as Autotransformer  Conventional two-winding transformer can be converted into autotransformer by connecting primary and secondary windings in series following rules apply: 1.Currents should not exceed nominal rating 2.Voltages should not exceed nominal rating 3.If rated current flows in one winding rated current automatically flows in other winding (ampere-turn ratio of the windings are always equal) 4.If rated voltages exists in one winding rated voltage automatically appears across other winding (ampere-turn ratio of the windings are always equal) 5.If current in one winding flows from H 1 to H 2, current in other winding should flow from X 2 to X 1 6.Voltages add with opposite polarity (H 1 & X 2, or H 2 & X 1 ) and subtracts with same polarity (H 1 & X 1, or H 2 & X 2 )

6 Lecture 09Electro Mechanical System6 Example A standard single phase transformer 15kVA, 600V/120V,60Hz Connect it as autotransformer to obtain following voltages a)600 V primary to 480 V secondary b)600 V primary to 720 V secondary c)120 V primary to 480 V secondary Also calculate maximum load in each case Nominal current of 600 V winding is I 1 = S/E 1 = 15000/600 = 25 A Nominal current of 600 V winding is I 2 = S/E 2 = 15000/120 = 125 A a) For 480 V, secondary 120 V must subtract from primary voltage 600. to obtain we must connect same polarity together.

7 Lecture 09Electro Mechanical System7 Example….cnt. current in 120 V winding is the same as that of load i.e nominal current rating of 125 A. Max. power drawn by the load is: S a = 125 A x 480 V = 60 kVA Current 125 A flows from X1 to X2. Current 25 A must flows from H2 to H1 Leaving 100 A to flow from the source Power supplied by the source is: S = 100 A x 600 V = 60 kVA

8 Lecture 09Electro Mechanical System8 Example….cnt. b) For 600 V/720 V, secondary 120 V must be added to the primary voltage 600. to obtain we must connect opposite polarity together (H 1 and X 2 ) Current in secondary is same 125 A Max. power drawn by the load is: S b = 125 A x 720 V = 90 kVA Autotransfarmer can supply a load of far greater capacity than original transformer c) For 120V/480V, same connections as solution In part a, source at X 1 & X 2 Load current cannot exceed 25 A Max. power drawn by the load is: S c = 25 A x 480 V = 12 kVA

9 Lecture 09Electro Mechanical System9 Voltage transformers  Measure/Monitor the voltage on a transmission line  Isolate metering equipment from the line  High-precision transformers in which the ratio of primary to secondary current is a known constant.  Secondary voltage is in phase with the primary voltage.  Rated secondary voltage is usually 115 irrespective of what the rated primary voltage may be  Similar to conventional transformers, the insulation must be to withstand full line voltage on HV side


Download ppt "Lecture 09Electro Mechanical System1 Chapter 11 Special Transformers."

Similar presentations


Ads by Google