ATCA COOLING PROJECT INTERSHIP FINAL PRESENTATION Piotr Koziol.

Slides:



Advertisements
Similar presentations
Goals and status of the ATLAS VME Replacement Working Group Markus Joos, CERN Based on slides prepared by Guy Perrot, LAPP 19/09/2012.
Advertisements

Electrical distribution for ALICE experiment & Electronic Rack Control S. Philippin.
CSC upgrade for LS1 USA-15 rack: layout, construction and installation 11 th February 2013.
The 5-slot 4U DC chassis is one of a line of products that Asis has developed over the years with it’s vas experience in the ATCA field. Asis AdvancedTCA.
The 5-slot 5U AC Chassis,fully field deployable chassis with AC power supply for full redundancy. AsisAdvancedTCA Class Asis AdvancedTCA Class.
EVOLUTION® Hands-On Demo This guide is meant to help lead a hands-on demo or presentation. The items listed are a suggestion for things to review, please.
Asis AdvancedTCA Class Fan Tray Fan tray is a component responsible of supplying sufficient shelf cooling According to the Parameters send from the shelf.
Asis AdvancedTCA Class Asis Shelf manager The Asis ATCA shelf manager is designed to comply with all relevant ATCA Specifications, including the IPMI 1.5.
3U ATCA Shelf October Proprietary and Confidential-
Enclosures & ComponentsBackplanesSystem PlatformsSwitches, Knobs & LEDsCabinets ATCA Systems Technology Meeting CERN Genève.
Asis AdvancedTCA Class Air Filter The air filter purpose is to block particles to enter the shelf thru the air inlet and Damage the fans or the blades.
Asis AdvancedTCA Class. What is PICMG? PICMG - The PCI Industrial Computers Manufacturer's Group Is a consortium of over 450 industrial computer product.
September 26, 2013 xTCA work group Evaluation results from AC/DC converters for xTCA Collaboration (CERN PH-ESE-BE) Vincent Bobillier, Matteo Di Cosmo,
“Introduction of the software for the thermal tests” Ioannis Kossyvakis (University of Patras, Greece) Mateusz Sosin (CERN) 19/09/2011.
Building an Application Server for Home Network based on Android Platform Yi-hsien Liao Supervised by : Dr. Chao-huang Wei Department of Electrical Engineering.
Techniques for establishing and maintaining constant temperature in ICT systems in order to reduce energy consumption Mihail Radu Cătălin Truşcă, Ş. Albert,
Mounting Direction Water Cooler Best solution OK Risk of air bubbles in the system Heatsink Water channels Inlet Outlet.
1 The Support Structural System for Sicbar and EC Detector of SciBooNE FermiLab/PPD/MD May 08, 2006 Edward Chi.
Robert Gomez-Reino on behalf of PH-CMD CERN group.
About Samway Electronic SRL Founded in 2005 in Bucharest, Romania Focused on management and monitoring solutions for telecom/industrial computers Active.
21/01/02 - ECAL Cooling - Arnaud Hormiere ST/CV 1 Development of ECAL COOLING PLANT Application to a Super Module.
Sensor-Based Fast Thermal Evaluation Model For Energy Efficient High-Performance Datacenters Q. Tang, T. Mukherjee, Sandeep K. S. Gupta Department of Computer.
JCOP Workshop September 8th 1999 H.J.Burckhart 1 ATLAS DCS Organization of Detector and Controls Architecture Connection to DAQ Front-end System Practical.
V. Bobillier1 Long distance cable installation status Calorimeter commissioning meeting.
1 5 December 2012 Laurent Roy Infrastructure / Electronics Upgrade -Cabling (long distance) -Rack and Crate (space, electrical distribution, cooling) -Detector.
Redundant IOC with ATCA(HPI) support Utilizing modern hardware for better availability Artem Kazakov, KEK/SOKENDAI.
A water-cooling solution for PC-racks of the LHC experiments  The cooling concept  Rack Model  Cooling Test  Rack Performance  Failure Tests  Future.
Thermal-aware Issues in Computers IMPACT Lab. Part A Overview of Thermal-related Technologies.
Dealing with Hotspots in Datacenters Caused by High-Density Computing Peter Hannaford Director of Business Development EMEA.
M. Joos, PH/ESE1 ATCA for ATLAS - status Activities of the working group PH/ESE xTCA evaluation project Next steps.
Software Architecture for Dynamic Thermal Management in Datacenters Tridib Mukherjee Graduate Research Assistant IMPACT Lab ( Department.
-Proprietary and Confidential-
The 2-slot 2U DC chassis is one of a line of products that Asis has developed over the years with it’s vast experience in the ATCA field. Asis AdvancedTCA.
U81X0 Downloading Tool Manual 1 ( Version 2.0) FlashRW For U81X0 Version 4.0.0(Build #100V) April 2004 LG Electronics Inc.
Activities related to Experiments during TS3 and YETS th November, 2015 M. Bernardini, M. Barberan With the support of S. Chemli and Experiments.
Pixel power R&D in Spain F. Arteche Phase II days Phase 2 pixel electronics meeting CERN - May 2015.
Clara Gaspar, December 2012 Experiment Control System & Electronics Upgrade.
60kW Thermosiphon control system
XLV INTERNATIONAL WINTER MEETING ON NUCLEAR PHYSICS Tiago Pérez II Physikalisches Institut For the PANDA collaboration FPGA Compute node for the PANDA.
ATCA cooling tests Claudio Bortolin (PH-ADO) Damian Dyngosz (PH-DT) George Glonti (PH-UAT) Julian Maxim Mendez (PH-ESE) Lukasz Zwalinski (PH-DT) xTCA IG.
Asis AdvancedTCA Class Asis Shelf manager The Asis ATCA shelf manager is designed to comply with all relevant ATCA Specifications, including the IPMI 1.5.
1 13 Octobre 2011 Laurent Roy ATCA Crate / Infrastructure in place -Rack in D3: dimension -Electrical power availability -Tell1 racks running in D3 (air.
RRB scrutiny Report: Muons. Internal scrutiny group for RRB report Internal scrutiny group composition – J. Shank, G. Mikenberg, F. Taylor, H. Kroha,
R. Fantechi. Shutdown work Refurbishment of transceiver power supplies Work almost finished in Orsay Small crisis 20 days ago due to late delivery of.
Aachen Status Report: CO 2 Cooling for the CMS Tracker at SLHC Lutz Feld, Waclaw Karpinski, Jennifer Merz and Michael Wlochal RWTH Aachen University, 1.
Status of integration in USA15. Status of rack layout 20/03/2015FTK Italia - A. Lanza2 Rack Y A2 equipped with turbine cooling system and nominal.
DSLAM Configuration in a Cabinet Heat and Noise testing December 2008.
News on FTK rack infrastructure A. Lanza – INFN Pavia FTK Italy meeting –
Summary of IAPP scientific activities into 4 years P. Giannetti INFN of Pisa.
FTK crates, power supplies and cooling issues 13/03/20131FTK-IAPP workshop - A. Lanza  Racks, crates and PS: requirements  Wiener crates  Rittal crates.
S A Griffiths CM42 June 2015 Electrical & Control.
ATLAS ATCA cooling evaluation project Claudio Bortolin (EP-ADO-PO) Michal Kalinowski (EP-ADO-PO) Lukasz Zwalinski (EP-DT-FS) ATLAS cooling team – 2016.
Power consumption (Watts) LBB27 ROS18 TSC50 TIM8 1 SC crate416 Alignment20 TOTAL per rack906~1 kW X2J22X2J02 With a water flow of 10 l/min, it should.
Thermal Analysis of the SKA Electronics Cabinets
Chapter 1: Introduction to the Personal Computer
Status of the CERN ATCA specification and tender
T-simulation OUTLINE Inputs to the T-simulation: chips, boards, crate mechanics and fan T-simulation performed into two steps: On large scale: simple AM.
ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: kW.
Rack Design Proposal as of 01/03/2013
FTK infrastructure in USA15 Status and plans for 2015 A
The Hardware keep away from water!
Correct blade installation
How SCADA Systems Work?.
Aachen Status Report: CO2 Cooling for the CMS Tracker
Proposal of a specification for ATCA shelves for experiments at CERN (for phase 1) Vincent Bobillier, Stefan Haas, Markus Joos, Julian Mendez, Sylvain.
Instructor Materials Chapter 1: Introduction to the Personal Computer
PowerValue 11 RT Sales Presentation
Motivation Performance of power plants using ACC may largely be affected by wind conditions Up to 10% reduction in net plant power output for 10 m/s wind[1]
Aachen Status Report: CO2 Cooling for the CMS Tracker
Rapid Automation Design
Presentation transcript:

ATCA COOLING PROJECT INTERSHIP FINAL PRESENTATION Piotr Koziol

Project description 13/01/2016PIOTR KOZIOL 2  ATCA boards will dissipate a significantly larger power (4x) with respect to the actual equipment. The cooling capabilities of the LHC rack need to be checked.  Identify potential in-rack bottlenecks and airflow resistance sources. Propose possible alternatives/fixes to remove them and test these adaptations. If required and possible run complementary simulations to confirm solution improvement.  Mechanical improvements of the rack or the crates to optimize the cooling performance (i.e.: removal of turbine chassis, modification of crate’s fan system, etc…) For historical reasons the electronics equipment in the so called LHC racks are cooled by a closed vertical recirculating airflow system from bottom to top  The AdvancedTCA (ATCA) telecom industry standard has been selected as the hardware platform for the “Phase II upgrade” of the back-end electronics systems for ATLAS

My tasks in this project Optimization of the program to manage larger number of data Graphic User Interface (GUI) improvement LabVIEW Sensors Installation: Temperature and Velocity ATCA crates Communication with standard PC LHC standard Rack 52U setup Vertical Air Cooling (Different loads and configurations) Horizontal Air Cooling Comparison Vertical vs Horizontal air cooling Cooling Tests Data analysis using Diadem and Excel Data Analysis 13/01/2016PIOTR KOZIOL 3 3 Rack 52U 14 U 15 U Temperature sensors Velocity sensors

Load blades layout and connection schema 13/01/2016PIOTR KOZIOL 4 Connection of the devices architecture Number of sensors: Old Load Blades 14x7 temperature sensor. New Load Blades 14x6 temperature sensors. Agilent data acquisition device which is connected to 30 PT100 sensors. 8xUAS1200PC velocity sensors connected with USB IN Out

Communication With the horizontal cooling crates (16U) it has been required to setup a new communication system It has been prepared using RS232 port and terminal program. In this connection we need to login to the U-boot multi-platform where I was needing to setup IP using clia commands. Then I connected it directly by Ethernet to shelf manager. LabVIEW communicate with chassis using IPMItool external program by IPMI commands. New blades are not fully debugged and they are not working with IPMI commends. Company provide to us very simple program made in JAVA and it is working only with ShMM-500R. We are still waiting for the new firmware from company to new load blades. 13/01/2016 PIOTR KOZIOL 5 Shelf manager with ShMM-500R and ShMM-700R Used for communication with load blades

Graphical user interface 13/01/2016PIOTR KOZIOL 6 Turn on/off fans Turn on/off Load Menu for Velocity/Temperature single Measurements Turn on/off program Air Temperature with rack layout

Vertical cooling test campaign ATCA 1 full load and ATCA 2 only fans ATCA 1 only fans and ATCA 2 full load ATCA 1&2 7+7 ATCA 1&2 full load (to be done) Comparison with simulations carried out by the company 4 heat exchangers & 3 heat exchangers Bottom fans influence Enhanced HX surface exchange Verification of air distribution adding gaps below and above each heat exchanger Vertical configuration 13/01/2016PIOTR KOZIOL 7 TURBINE ATCA2 GAP Heat Exchanger 2 GAP ATCA1 GAP Heat Exchanger 1 GAP Heat Exchanger 3 Air Deflector

Horizontal cooling test campaign 13/01/2016PIOTR KOZIOL 8 ATCA 1 Full load ATCA 2 off ATCA 2 Full load ATCA 1 off ATCA 1&2 7+7 ATCA 1&2 full load (to be done) Bottom fans influence Horizontal configuration ATCA2 GAP ATCA1 Cooling Door GAPGAP GAP Side view of the rack. Air is going like arrows in this picture.

13/01/2016PIOTR KOZIOL 9 Measurements for Horizontal & Vertical tests Air temperature in each slot Crate air temperature and velocity inlet outlet Cooling door water (Horizontal) or cooling water going to heat exchangers, inlet and outlet (Vertical) Water flow measurements Rear door air temperature (outlet), only Horizontal Heat exchangers air temperature outlet, only Vertical Velocity speed of the turbine, only Vertical Taken Measurements Cooling door Water Temp sensor Horizontal crate with velocity sensors (inlet)

Vertical performance 13/01/2016PIOTR KOZIOL 10 W = with WOUT – without G = gaps BF = bottom fans FSHE = full surface of heat exchangers Significant lower Temperatures removing the bottom fans trays -> improved flow distribution Limit: stay below 50 o C!!!!

Measurements of air velocity for vertical cooling 13/01/2016PIOTR KOZIOL 11 HEAT EXCHANGER 2 HEAT EXCHANGER 3 HEAT EXCHANGER 1 AIR DEFLECTOR s04s04 S06S06 s08s08 s10s10 s12s12 s14s14 s09s09 s07s07 s05s05 s03s03 s01s01 s02s02 s13s13 s11s11 s04s04 S06S06 s08s08 s10s10 s12s12 s14s14 s09s09 s07s07 s05s05 s03s03 s01s01 s02s02 s13s13 s11s11 TURBINE v7v7 v1v1 v5v5 TOP FANS BOTTOM FANS TOP FANS BOTTOM FANS v4v4 v7v7 v6v6 v6v6 v6v6 v6v6 v4v4 v4v4 v3v3 v3v3 v7v7 v7v7 v2v2 v4v4 v3v3 Velocity sensors are quite sensitive to Temperature changes

Horizontal measurements crates size comparison 13/01/2016PIOTR KOZIOL 12 16U crate more effective: PH-ESE bought one to be used for future development and tests Limit: stay below 50 o C!!!!

Measurements of air velocity for horizontal cooling 13/01/2016PIOTR KOZIOL 13

Vertical vs. Horizontal 13/01/2016PIOTR KOZIOL 14 Limit: stay below 50 o C!!!!

Conclusions 13/01/2016 PIOTR KOZIOL 15 Increase the number of gaps between chassis or using full surface of the heat exchanger does not change anything in the results for vertical cooling. Without bottom fans trays both vertical and horizontal crates provides similar performance 16U crate is more effective than 14U crate for horizontal cooling. 16U crate for horizontal cooling and crate for vertical cooling without bottom fans have similar effectiveness of cooling

Thanks for your attention 13/01/2016PIOTR KOZIOL 16