UPS network perturbations in SX2 Vincent Chareyre EN-EL-SN ALICE Technical Coordination Meeting 7 May 2010.

Slides:



Advertisements
Similar presentations
André Augustinus 15 March 2003 DCS Workshop Safety Interlocks.
Advertisements

QUALITY AND TECHNOLOGY
Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.
 UK Power Networks. All rights reserved Distribution Network Visibility Low Carbon Networks Fund Tier 1 project UK Power Networks & PPA Energy Omer.
LP-31 Series Uninterruptible Power Supply Product Management GE Consumer & Industrial Power Protection.
A3016 and MAO test at CAEN Pigi, A. Boaino & CAEN.
Inspection & Test Overview suite412.
LP33 Series UPS kVA 400Vac/CE
LHC UPS Systems and Configurations: Changes during the LS1 V. Chareyre / EN-EL LHC Beam Operation Committee 11 February 2014 EDMS No /02/2014.
Electrical Distribution: How to Ensure Safe Powering and High Availability for LHC Machine Protection Systems? V. Chareyre / EN-EL Machine Protection Panel.
20 10 School of Electrical Engineering &Telecommunications UNSW UNSW 10 Author: Simon Lewis Supervisor: Iain MacGill Industry Supervisor:
Delta Confidential DES UPS introduction UPS training June 2006 Markus Schwab.
Failure mode impact studies and LV system commissioning tests
Data centres are dynamic computer environments. In recent years the increasing mix of old and new computer technologies is causing the overall power factor.
PowerPoint ® Presentation Chapter 12 Utility Interconnection Distributed Generation Generators Inverters Interconnection Codes and Standards Interconnection.
Electrical power distribution in experiments W.Iwanski.
The primary objective in the implementation of a UPS system is to improve power reliability to the limits of technical capability, the ultimate aim being.
GE Critical Power © 2010 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part, without prior.
F. Ferrandis_SP_ALPHA 2_BLOCK 2_Paper 35_Presentation Barcelona May POWER FACTOR CORRECTION WITHIN INDUSTRIAL SITES EXPERIENCES REGARDING.
Power Distribution Harmonics Case Study of 285-3F Chiller Plant Michael W. Harmon Principle Engineer Savannah River Nuclear Solutions, LLC Savannah River.
By A.D.Thirumoorthy Tamil Nadu Electricity Board India.
Trouble shooting Before starting to work on a problem, first we have to understand the problem Once the problem is understood, we will try to “isolate”
InnovationValueTeamwork SHENZHEN INVT ELECTRIC CO., LTD.
CV activities on LHC complex during the long shutdown Serge Deleval Thanks to M. Nonis, Y. Body, G. Peon, S. Moccia, M. Obrecht Chamonix 2011.
 Interconnecting DER With Electric Power Systems POWER SYSTEM 2002 CONFERENCE -- IMPACT OF DISTRIBUTED GENERATION Image.
1 Copper Stabilizer Continuity Measurement Project CSCM Mini Review Powering Implementation H. Thiesen 30 November 2011.
1. There are different assistant software tools and methods that help in managing the network in different things such as: 1. Special management programs.
Non-Residential Network Computer Power Management UES Measure Update Regional Technical Forum July 16, 2013.
Operating and maintenance of generator. Operating Generator If it is manually operated generator, whenever power goes off, before starting the generator,
112/09/2013. Summary  Events on the network  Incidents  Network reconfigurations  Network operation  Update on activities  Tests  Projects and.
Modular Inverter.
LAFA Food Distribution
Diagnostics of photovoltaic power plants operation
Claudio Bortolin. 1 st June: PT100 electrical connection failure (Temp Chiller water In&Out) 1) it required an access to the cavern to be fixed 2) access.
ELECTRONIC IDEAS UPS INNOVATIVE ALTERNATE POWER TECHNOLOGY DAWN – ELECTRONIC IDEAS INNOVATIVE ALTERNATE POWER TECHNOLOGY ELECTRONIC IDEAS.
Electromagnetic Compatibility Test for CMS Experiment. Authors C. Rivetta– Fermilab F. Arteche, F. Szoncso, - CERN.
Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.
Associated detection/extinction systems D. Swoboda.
Simulation results for powering serial connected magnets Daniel Siemaszko, Serge Pittet OUTLINE : Serial configuration of full rated converters.
BA6 Cooling Towers Test Day Process Control Functionality and Performance Tests TCR – PCR Monitoring.
Control, monitoring and safety aspects of electrical distribution in the Atlas experiment W.Iwanski PH/ESE-BE.
A common 400 Hz AC Power Supply Distribution System for CMS FEE. Authors C. Rivetta– Fermilab. F. Arteche, F. Szoncso, - CERN.
ATC/ABOC Days, 22 January 2007 The safety electrical networks at CERN Anne Funken, TS-EL.
Overview of the main events related to TS equipment during 2007 Definition Number and category of the events Events and measures taken for each machine.
Diagnostics of photovoltaic power plants operation Vitezslav Benda, CTU Prague, Faculty of Electrical Engineering.
Quality assurance - documentation and diagnostics during interventions Corrective maintenance seen from the Technical Infrastructure operation Peter Sollander,
LP Series 400V CE GE Consumer & Industrial September 2004.
Conclusions on UPS powering test and procedure I. Romera Acknowledgements: V. Chareyre, M. Zerlauth 86 th MPP meeting –
ATC / ABOC 23 January 2008SESSION 6 / MTTR and Spare Parts AB / RF GROUP MTTR, SPARE PARTS AND STAND-BY POLICY FOR RF EQUIPMENTS C. Rossi on behalf of.
E.Sbrissa EP/TA3 - IC ATLAS EDR_MAG Magnet Project Fault analysis, QA & Failure rate.
POWER QUALITY AND NETWORK DISTURBANCES in CERN’s electrical network K. KAHLE, TS-EL Diploma students R. Sternberger, M. Neubert 1 st TS Workshop Archamps,
TECHNICAL PAPER ON SIMULTANEOUS AC-DC POWER TRANSMISSION
Interventions on electrical distribution and racks’ infrastructure still to be done during LS1 and their impact W.Iwanski.
Electricity. TYPES OF CIRCUITS Individual electrical circuits normally combine one or more resistance or load devices. The design of the automotive electrical.
A DSP based on on-line UPS R.Padamaja G.Mamatha Reddy EEE EEE S.V.C.E S.V.C.E BY.
André Augustinus P2 events & perturbations 07 May 2010 ALICE Technical Coordination Meeting.
POWER FACTOR CORRECTION
151 Richmond St. S.W., PO Box 519, Hensall, ON, N0M 1X0
Power Quality at Solar Distributed Generation Facilities
APFC-03 Reactive Power Compensation Method & Settings
Technical Services: Unavailability Root Causes, Strategy and Limitations Data and presentation in collaboration with Ronan LEDRU and Luigi SERIO.
Management Of Tulkarm Electrical Network
LV Safe Powering from UPS to Clients
Grid feeding monitoring relay
PowerValue 11/31 T Sales Presentation
Measures to Improve Power Quality in Distribution System
Indian Grid Code and Commissioning Test Procedure Dr
Presentation transcript:

UPS network perturbations in SX2 Vincent Chareyre EN-EL-SN ALICE Technical Coordination Meeting 7 May 2010

Outline UPS identification and technology Electrical distribution in November 2009 Request for modifying UPS power supply of EOD1/2X and EOD1/20 Current electrical distribution Perturbations on EOD1/2X Investigations Attempts for identifying the problem Perturbations measurements MGE UPS Systems intervention Stand-by service intervention Current situation Conclusion

UPS identification and technology Equipments concerned: EBS106/2X (80 kVA) and EBS128/2X (60 kVA) MGE EPS 2000 Double Conversion EOD1/2X EBS106/2X EBD106/2X Network 1 and 2 are the same: EBD

Electrical distribution in November 2009 EBS106/2X 80 kVA EOD1/20 EBS128/2X 60 kVA EOD1/2X Harmonic compensator filter EOF106/2X

Request for modifying UPS power supply of EOD1/2X and EOD1/20 November 2009: Stop of EBS128/2X Reason: UPS (60 kVA) loaded at more than 100% Temporary solution: 10 kW removed from the switchboard EOD1/2X Observations: –60 kVA UPS powering EOD1/2X loaded at 100% –80 kVA UPS powering EOD1/20 loaded at 50% Request for modifying the UPS distribution and balancing UPS loads: Cross UPS power supply of EOD1/2X and EOD1/20 EN-EL study, see EDMS report No Current distribution not balanced on the 3 phases Phase balancing does not solve the problem Green light to cross UPS power supplies Works planned in January 2010, done on 28 January 2010

Current electrical distribution New distribution: –UPS EBS106/2X (80 kVA) powers EOD1/2X –UPS EBS128/2X (60 kVA) powers EOD1/20 Both UPSs loaded at around 70% EN-EL recommendation: current phase balancing! Both switchboards generate high rate of current harmonics THDI around 23% rejected on UPS THDI significantly reduced by compensation filter Exact reason for having a filter on the UPS 80 kVA: unknown! Decision to keep the filter attached to EOD1/20 in order to avoid overloading the UPS 60 kVA

Current electrical distribution EBS106/2X 80 kVA EOD1/20 EBS128/2X 60 kVA EOD1/2X Harmonic compensator filter EOF106/2X

Perturbations on EOD1/2X Perturbation on EOD1/2X powered by EBS106/2X (80 kVA) First event on 2 February 2010 Power cut on a few computers powered via three feeders of EOD1/2X No breaker opened No alarm at the level of the Electrical Network Supervisor (ENS) Next weeks: more events at random frequency Always a few computers OFF powered via some feeders No breaker opened, no alarms, other loads never impacted

Investigations Power network analyzer connected on the feeder EOD102/2X One example: 4 events over one week-end! Voltage Current Voltage drop Inrush current

Attempts for identifying the problem Power network analyzer not sufficient to localize the problem Several wrong leads followed due to coincidences in facts: –Cooling pumps in UX25 –Additional PLC in UX25 commissioned in February Investigations not simple: –Random event occurrence –No access to UX25 –Many computers and systems powered via EOD1/2X Bypass of the UPS not allowed by ALICE management! UPS EBS106/2X could not be suspected or dismissed!

Perturbation measurements Voltage on EOD1/2X recorded by perturbation analyzer at point 2 Perturbation on the output voltage Significant duration Voltage after the drop is not clean, still UPS output?

MGE UPS Systems intervention Request of MGE UPS Systems intervention for checking the UPS Intervention done on 25 March 2010, authorization to bypass the UPS All maintenance tests performed on UPS EBS106/2X: OK One parameter “masque de limitation” enabled on UPS EBS106/2X Same parameter disabled on the UPS EBS128/2X (60 kVA) Limitation mask: Inrush current at the level of the load, current limited to 1.5 În (245 A) without switching to static bypass (network 2) Conclusion: parameter disabled on 25 March 2010 Parameter not visible on UPS control display Only MGE UPS Systems can check and modify this parameter! Feedback from MGE UPS Systems: –Parameter never enabled on this type of UPS! –Potential source of problems! Why had this parameter been modified in the past?

Stand-by service intervention (1/3) CCC phone call on Saturday 27 March 2010, alarms from EBS106/2X UPS OFF, output fuses 1 and 3 melted, loads on static by-pass No power cut of the loads according to ALICE control room Request of MGE UPS Systems intervention –Change of fuses on phases L1 and L3 –UPS switch on not loaded, EOD1/2X switched to manual by-pass –UPS OFF, output fuses 1 and 2 melted, inverter #2 broken down –Change of the inverter and fuses –UPS restarted, tests OK, EOD1/2X switched back to UPS According to MGE UPS Systems: –Failure not related to previous perturbations –Inverter may have been overstressed by inrush currents generated by loads. No switch to static by-pass since the limitation mask was enabled.

Stand-by service intervention (2/3) Internal failure of the UPS

Stand-by service intervention (3/3) Voltage on EOD1/2X recorded by perturbation analyzer at point 2 Perturbation on the output voltage Duration shorter than previous cases Voltage after the drop is clean, corresponds to network 2?

Current situation No perturbation detected since 27 March 2010 Both UPS have the same configuration with limitation mask disabled Current measured with a precise power network analyzer Maximum peak current measured during 2 weeks: 193 A (< 245 A)

Conclusion Problem solved by disabling the limitation mask on the UPS? Lack of data before the deactivation of the mask However we have never measured a load current exceeding 1.5 În Needs to continue measurements? LHC and experiments in operation: NO interventions on UPS networks! MGE UPS Systems investigations in order to analyze UPS behavior when the limitation mask was enabled For the future: –Adding new loads to this UPS would be risky –End of service foreseen in 2013 (manufacturing start date: 1987, end of manufacturing date: 1997)