HYDRONIC HEATING AQUASTATS

Slides:



Advertisements
Similar presentations
Heating, Ventilation, and Air-Conditioning (HVAC) Systems
Advertisements

Air Conditioners and Heaters
E1 – Electrical Fundamentals
Thermostats, Pressure Switches, and Other Electric Control Devices
HEAT PUMPS.
BUrners TRAining CEntre GAS BURNERS N 900 H/L N 900 H/L series.
The Home Inspection Book: A Guide for Professionals By Marcia Darvin Spada Copyright, Thomson/South-Western, 2003, Revised, 2006.
Unit 206: Domestic hot water systems
TYPES OF MECHANICAL SYSTEMS
AQ2511B0 Boiler Reset Panel – for Whole House Heating Control – Immediate Retrofit Opportunity !
Basic Refrigeration Cycle
Heating Control Devices
Objective of the session.
HVACR312 - Refrigeration Metering Devices.
Unit 206: Domestic hot water systems
BUrners TRAining CEntre GULLIVER BLU HYDRAULIC SCHEME.
Engineer Presentation
Unit 206: Domestic hot water systems
Product Introduction.
Gas Furnace Controls Part 2.
STEAM HEATING.
Hydronic Mechanical Controls
Oil Safety Control.
1 HVAC 214 Electricity For Oil Heat Fan Center Relays.
Troubleshooting Electric Control Devices
Air-Source Heat Pumps I North Seattle Community College HVAC Program Instructor – Mark T. Weber, M.Ed. Airsource Heat Pump 1.
HVAC523 Basic Subsystems.
Air Conditioning Heating Refrigeration
Operation Sabbath Mode - SELECT PROGRAM - Lights, alarms and fans Normal Sabbath Overview.
BAKE BROIL - SELECT PROGRAM - CONV BAKE CONV BROIL SELF CLEAN On any diagram screen, double click any of the following components to bring you to a description.
Presentation on Feed and Expansion Cistern. Central Heating At the end of this part you should be able to: Identify general system methods of feed and.
1 HVACR317 - Refrigeration Operating Controls 1 Thermostats Operating Controls 1 Thermostats.
1 HVACR317 – Core for Refrigeration Operating Controls 1 Thermostats Operating Controls 1 Thermostats.
Zoning Hydronic Systems. Zone Control Divides the Space to be Heated 1.Each with its own heating needs and control systems 2.There are several reasons.
BUrners TRAining CEntre GAS BURNERS N 120, 200, 400 N 120, 200, 400 series.
Page A5 Schematic Analysis for Sequence of Operation (AUTOMATIC Spark Ignition System)
Control Systems: Circuitry Electricity for Refrigeration, Heating and Air Conditioning 7th Edition Chapter 16 Control Systems: Circuitry and Troubleshooting.
We apply 120 VAC to the HM Unit (Remember to check polarity!) Our primary step down T/X provides power to terminal “X” and “COM” on the ignition control.
AIR CONDITIONING (COOLING)
E3 HVACR Controls and Devices
Unit 13 Oil-Burning Equipment
Unit 7 Gas Heat: Natural and LP
How to Draw a Systems Diagram
Section 6: Air-Conditioning (Heating And Humidification)
E3 HVACR Controls and Devices
Outcome 4 Mechanical central heating controls Unit 208: Central heating systems.
Student CD for Commercial Refrigeration for A/C Technicians Chapter 12 Ice Machines.
Hot water Systems Heaters.
Presentation transcript:

HYDRONIC HEATING AQUASTATS

I. TERMS A. HYDRONIC 1. SYSTEMS THAT USE THE CIRCULATION OF HOT WATER THROUGH PIPES TO HEAT CONDITIONED SPACE B. HIGH LIMIT 1. STOPS THE BURNER IF THE TEMPERATURE OR PRESSURE IS TO HIGH 2. MAY BE MANUAL OR AUTO RESET C. CIRCULATOR 1. PUMP USED TO MOVE WATER

D. CIRCULATOR RELAY 1. TURNS THE PUMP ON AND OFF 2. ALLOWS A LOW VOLTAGE THERMOSTAT TO CONTROL THE LINE VOLTAGE PUMP E. LOW LIMIT 1. TURNS THE BURNER ON WHEN THE BOILER TEMPERATURE IS BELOW SET POINT 2. TURNS BOILER OFF WHEN TEMPERATURE INCREASES TO SET POINT

F. CIRCULATOR CONTROL 1. USED IN SYSTEMS WHICH HAVE DOMESTIC COILS 2. PREVENTS THE CIRCULATOR FROM RUNNING IF BURNER IS OUT ON LOW LIMIT a. KEEPS THE BOILER FROM GETTING TO COLD FOR DOMESTIC HOT WATER

II. AQUASTATS A. AQUASTAT RELAY (COMBINATION CONTROL) 1. SENSES WATER TEMPERATURE IN A HYDRONIC BOILER 2. HAS A LIMIT CONTROL, RELAY, AND TRANSFORMER. ALL MOUNTED TOGETHER IN ONE DEVICE 3. HAS CONNECTIONS FOR THERMOSTAT, CIRCULATOR, BURNER AND MAIN POWER 4. ONE TYPE OF AQUASTAT PROVIDES LOW VOLTAGE POWER FOR A GAS BURNER WHILE ANOTHER TYPE OF AQUASTAT PROVIDES HIGH VOLTAGE POWER FOR AN OIL BURNER

5. MAKE SURE YOU HAVE THE CORRECT. AQUASTAT FOR THE TYPE OF BURNER 5. MAKE SURE YOU HAVE THE CORRECT AQUASTAT FOR THE TYPE OF BURNER THAT THE BOILER USES B. SEQUENCE OF OPERATION – COLD START BOILER 1. THERMOSTAT CALLS FOR HEAT, GAS BURNER TURNS ON 2. THE WATER HEATS UP. HIGH LIMIT SETTING KEEPS THE WATER FROM GETTING TO HOT (“BOILING” 180- 200) 3. CIRCULATOR IS ENERGIZED. IF AQUASTAT HAS A LOW LIMIT SETTING CIRCULATOR WILL NOT RUN UNTIL LOW LIMIT SETTING IS REACHED. 160 f

4. WHEN BOILER IS UP TO TEMPERATURE CIRCULATOR RUNS CONSTANTLY. BURNER MAY CYCLE ON AND OFF 5. WHEN THERMOSTAT IS SATISFIED CIRCULATOR STOPS, BURNER SHUTS OFF

C. AQUASTAT ELECTRICAL CONNECTIONS 1. L1 & L2 CONNECTIONS FOR 120 V POWER SUPPLY 2. TV & T ARE 24V THERMOSTAT CONNECTIONS 3. C1 & C2 ARE CIRCULATOR MOTOR CONNECTIONS 4. B1 & B2 ARE BURNER CONNECTIONS 5. VOLTAGE CHECKS CAN BE MADE AT ALL THESE CONNECTIONS D. AQUASTAT VARIATIONS 1. ANOTHER TYPE OF AQUASTAT IS DESIGNED TO MAINTAIN CONSTANT BOILER TEMPERATURE

2. THE BURNER WILL CYCLE ON AND OFF TO 2. THE BURNER WILL CYCLE ON AND OFF TO MAINTAIN 180deg WATER TEMPERATURE EVEN WHEN THERE IS NO CALL FOR HEAT 3. THIS TYPE OF AQUASTAT CAN BE FOUND IF THE BOILER IS ALSO PROVIDING DOMESTIC HOT WATER WITH A TANKLESS COIL LOCATED IN THE BOILER 4. A TANKLESS COIL IS NOTHING MORE THAN A COIL OF COPPER TUBING SITTING IN THE HOT BOILER WATER. THE COLD WATER FROM A COLD WATER LINE GOES IN AND COMES OUT HOT 5. WITH A TANKLESS COIL THERE IS NO LARGE STORAGE CAPACITY OF HOT WATER

III. AQUASTAT CONTROLLERS A. HIGH AND LOW LIMIT CONTROLLERS 1. AS A HIGH LIMIT, THE CONTROLLER WORKS LIKE THE HIGH LIMIT IN A WARM AIR SYSTEM a. A SAFETY DEVICE TO TURN OFF THE BURNER IF TEMPERATURES ARE TO HIGH 2. AS A LOW LIMIT, THE CONTROLLER WILL TURN ON THE BURNER WHEN THE TEMPERATURE DROPS TO LOW a. MAINTAINING A MINIMUM BOILER WATER TEMPERATURE

3. USES A BULB AND CAPILLARY TO SENSE. TEMPERATURE / CHANGES BELLOWS 3. USES A BULB AND CAPILLARY TO SENSE TEMPERATURE / CHANGES BELLOWS POSITION 4. THE BELLOWS EXPANDS AND CONTRACTS, OPENING AND CLOSING A SWITCH B. CIRCULATOR CONTROL 1. WHEN THE WATER TEMPERATURE DROPS THE CIRCULATOR WILL TURN OFF. THIS PREVENTS EXCESS RUN TIME WHILE THE BOILER HEATS UP C. DUAL AQUASTAT CONTROLLER 1. THE FUNCTION OF THE HIGH LIMIT, LOW LIMIT & CIRCULATOR CONTROLLERS ARE COMPLETED WITH ONE CONTROL

2. A SPDT SWITCH IS USED AS THE LOW LIMIT AND CIRCULATOR CONTROL a. WHEN THE BOILER TEMPERATURE IS BELOW THE SET POINT THE R-B CONTACTS ARE CLOSED (LOW LIMIT), THE R-W CONTACTS ARE OPEN (CIRCULATOR) b. WHEN THE TEMPERATURE IS ABOVE THE SET POINT THE CONTACTS CHANGE POSITION D. COMBINATION AQUASTAT CONTROLLER 1. AQUASTAT RELAY 2. TRIPLE AQUASTAT RELAY

E. AQUASTAT RELAY 1. COMBINES THE FUNCTION OF A SWITCHING RELAY FOR CIRCULATOR AND TEMPERATURE CONTROL OF THE SYSTEM 2. USED WITH SYSTEMS THAT “DO NOT” HAVE DOMESTIC HOT WATER COILS 3. CONTAIN: a. TRANSFORMER FOR CONTROL VOLTAGE 24vac b. RELAY TO CONTROL BURNER AND CIRCULATOR c. TEMPERATURE CONTROL FOR HIGH AND LOW LIMIT OPERATIONS 4. THE BOILER DOES NOT RUN WHEN THE SYSTEM HAS NO CALL FOR HEAT

F. TRIPLE AQUASTAT RELAY 1. USED IN SYSTEMS WHICH ARE REQUIRED TO PROVIDE DOMESTIC HOT WATER 2. SOME PROVIDE ZONE CONTROL 3. THERE ARE SINGLE ZONE MODELS FOR GAS, AND OIL-FIRED APPLICATIONS a. A MILLIVOLT MODEL IS AVAILABLE FOR GAS SYSTEMS 4. MULTI ZONE MODELS ARE ALSO AVAILABLE

a. IN THIS SYSTEM THE TRIPLE AQUASTAT CONTROLLER PROVIDES HIGH LIMIT b. LOW LIMIT/CIRCULATOR CONTROL c. RELAY SWITCHING FOR THE OIL PRIMARY OR GAS VALVE (THROUGH THE HIGH LIMIT) d. POWER FOR THE ZONE CIRCULATOR. CONTROL IN ZONE 2 IS PROVIDED BY AN ADDITIONAL RELAY