Average Power and Power Factor ET 242 Circuit Analysis II Electrical and Telecommunication Engineering Technology Professor Jang.

Slides:



Advertisements
Similar presentations
Introductory Circuit Analysis Robert L. Boylestad
Advertisements

Each of the circuit elements will have a different ac current response to an applied ac voltage. We need to look at each of these elements. Resistor:
Chapter 12 RL Circuits.
The Basic Elements and Phasors
1 Electrical Engineering BA (B), Analog Electronics, Lecture 2 ET065G 6 Credits ET064G 7.5 Credits Muhammad Amir Yousaf.
ELECTRIC CIRCUIT ANALYSIS - I
Department of Electronic Engineering BASIC ELECTRONIC ENGINEERING Steady-State Sinusoidal Analysis.
Alternating Current Circuits
Series AC Circuits Analysis
Phasors ET 242 Circuit Analysis II Electrical and Telecommunication
Response of Basic Elements to AC Input ET 242 Circuit Analysis Electrical and Telecommunication Engineering Technology Professor Jang.
Selected Network Theorems for AC Circuits
Parallel AC Circuits Analysis ET 242 Circuit Analysis II Electrical and Telecommunication Engineering Technology Professor Jang.
Series Resonance ET 242 Circuit Analysis II
Parallel Resonance ET 242 Circuit Analysis II Electrical and Telecommunication Engineering Technology Professor Jang.
Ohm’s Law ET 162 Circuit Analysis Electrical and Telecommunication Engineering Technology Professor Jang.
Network Theorems (AC) ET 242 Circuit Analysis II
R,L, and C Elements and the Impedance Concept
SINUSOIDAL ALTERNATING WAVEFORMS
Lesson 24 AC Power and Power Triangle
Series Circuits ET 162 Circuit Analysis Electrical and Telecommunication Engineering Technology Professor Jang.
Methods of Analysis ET 162 Circuit Analysis Electrical and Telecommunication Engineering Technology Professor Jang.
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Chapter 7 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
ELECTRIC CIRCUIT ANALYSIS - I
ELECTRIC CIRCUIT ANALYSIS - I
Fundamentals of Electric Circuits Chapter 11
Series and Parallel AC Circuits
ELECTRICAL CIRCUIT ET 201 Define and explain characteristics of sinusoidal wave, phase relationships and phase shifting.
Fundamentals of Electric Circuits Chapter 11
Kent Bertilsson Muhammad Amir Yousaf. DC and AC Circuit analysis  Circuit analysis is the process of finding the voltages across, and the currents through,
Chapter 14 – The Basic Elements and Phasors
Series and Parallel Networks ET 162 Circuit Analysis Electrical and Telecommunication Engineering Technology Professor Jang.
EE2010 Fundamentals of Electric Circuits Lecture 13 Sinusoidal sources and the concept of phasor in circuit analysis.
AC POWER ANALYSIS Instantaneous & Average Power
Chapter 7 AC Power Analysis
1 Alternating Current Circuits Chapter Inductance CapacitorResistor.
Alpha College of Engg & Tech Khatraj, Gandhinagar EEE( ) 1 st SEM EE-A Group 5 1 KOTADIA SMIT SATISHKUMAR ( ) 2 BHANUSHALI SHREYABEN.
Chapter 15 – Series & Parallel ac Circuits Lecture 19 by Moeen Ghiyas 11/10/
CHAPTER 33) ALTERNATING-CURRENT CIRCUITS 33.1 : AC SOURCES AND PHASORS An ac circuit consists of circuit elements and a generator that provides athe alternating.
Series & Parallel AC Circuits Analysis ET 242 Circuit Analysis II Electrical and Telecommunication Engineering Technology Professor Jang.
Copyright ©2011 by Pearson Education, Inc. publishing as Pearson [imprint] Introductory Circuit Analysis, 12/e Boylestad Chapter 14 The Basic Elements.
1 ET 201 ~ ELECTRICAL CIRCUITS COMPLEX NUMBER SYSTEM  Define and explain complex number  Rectangular form  Polar form  Mathematical operations (CHAPTER.
Transformers ET 242 Circuit Analysis II
DC & AC BRIDGES Part 2 (AC Bridge).
1 ELECTRICAL TECHNOLOGY EET 103/4  Define and explain sine wave, frequency, amplitude, phase angle, complex number  Define, analyze and calculate impedance,
1 ELECTRICAL TECHNOLOGY ET 201  Define series impedances and analyze series AC circuits using circuit techniques.
Chapter 17 Power in AC Circuits.
1 ELECTRICAL TECHNOLOGY EET 103/4  Define and explain sine wave, frequency, amplitude, phase angle, complex number  Define, analyze and calculate impedance,
Unit 8 Phasors.
ELECTRICAL TECHNOLOGY EET 103/4
Slide 1Fig 33-CO, p Slide 2Fig 33-1, p the basic principle of the ac generator is a direct consequence of Faraday’s law of induction. When.
Chapter 14 – Basic Elements and Phasors Lecture 17 by Moeen Ghiyas 13/12/
1  Explain and calculate average power, apparent power, reactive power  Calculate the total P, Q and S and sketch the power triangle. ELECTRICAL TECHNOLOGY.
AC POWER ANALYSIS. 2 Content Average Power Maximum Average Power Transfer Complex Power Power Factor Correction.
Series and Parallel ac Circuits.
AC POWER & POWER FACTOR. Lesson Objectives  Compute and define apparent, reactive, and average power for capacitors, inductors, and resistors.  Compute.
Chapter 15 Principles of Electric Circuits, Conventional Flow, 9 th ed. Floyd © 2010 Pearson Higher Education, Upper Saddle River, NJ All Rights.
Chapter 13 The Basic Elements and Phasors. Objectives Be able to add and subtract sinusoidal voltages or currents Use phasor format to add and subtract.
Chapter 10 RC Circuits.
1 AC Circuit Theory. 2 Sinusoidal AC Voltage Waveform: The path traced by a quantity, such as voltage, plotted as a function of some variable such as.
Chapter 14 Series and Parallel AC Circuits. Objectives Become familiar with the characteristics of a series and parallel ac circuit Find the total impedance.
RC Circuits (sine wave)
Chapter 13 The Basic Elements and Phasors. Objectives Be able to add and subtract sinusoidal voltages or currents Use phasor format to add and subtract.
ELECTRICAL TECHNOLOGY EET 103/4
Lecture 07 AC POWER & POWER FACTOR.
AC POWER & POWER FACTOR.
Sinusoidal Excitation of Circuits
Parallel AC Circuits Analysis
Chapter 15.
Presentation transcript:

Average Power and Power Factor ET 242 Circuit Analysis II Electrical and Telecommunication Engineering Technology Professor Jang

Acknowledgement I want to express my gratitude to Prentice Hall giving me the permission to use instructor’s material for developing this module. I would like to thank the Department of Electrical and Telecommunications Engineering Technology of NYCCT for giving me support to commence and complete this module. I hope this module is helpful to enhance our students’ academic performance.

OUTLINES  Polar Form  Complex Numbers  Rectangular Form  Average Power and Power Factor ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 2  Conversion Between Forms Key Words: Average Power, Power Factor, Complex Number, Rectangular, Polar

Average Power and Power Factor A common question is, How can a sinusoidal voltage or current deliver power to load if it seems to be delivering power during one part of its cycle and taking it back during the negative part of the sinusoidal cycle? The equal oscillations above and below the axis seem to suggest that over one full cycle there is no net transfer of power or energy. However, there is a net transfer of power over one full cycle because power is delivered to the load at each instant of the applied voltage and current no matter what the direction is of the current or polarity of the voltage. ET 242 Circuit Analysis – Response of Basic Elements Boylestad 3 To demonstrate this, consider the relatively simple configuration in Fig where an 8 V peak sinusoidal voltage is applied across a 2 Ω resistor. When the voltage is at its positive peak, the power delivered at that instant is 32 W as shown in the figure. At the midpoint of 4 V, the instantaneous power delivered drops to 8 W; when the voltage crosses the axis, it drops to 0 W. Note that when the voltage crosses the its negative peak, 32 W is still being delivered to the resistor. Figure Demonstrating that power is delivered at every instant of a sinusoidal voltage waveform.

ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 2 In total, therefore, Even though the current through and the voltage across reverse direction and polarity, respectively, power is delivered to the resistive lead at each instant time. If we plot the power delivered over a full cycle, the curve in Fig results. Note that the applied voltage and resulting current are in phase and have twice the frequency of the power curve. The fact that the power curve is always above the horizontal axis reveals that power is being delivered to the load an each instant of time of the applied sinusoidal voltage. Figure Power versus time for a purely resistive load.

In Fig , a voltage with an initial phase angle is applied to a network with any combination of elements that results in a current with the indicated phase angle. The power delivered at each instant of time is then defined by P = vi = V m sin(ω t + θ v )·I m sin(ω t + θ i ) = V m I m sin(ω t + θ v )·sin(ω t + θ i ) Using the trigonometric identity the function sin(ωt+θ v )·sin(ωt+θ i ) becomes Figure14.31 Determining the power delivered in a sinusoidal ac network. Fixed value Time-varying (function of t) ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 5

The average value of the second term is zero over one cycle, producing no net transfer of energy in any one direction. However, the first term in the preceding equation has a constant magnitude and therefore provides some net transfer of energy. This term is referred to as the average power or real power as introduced earlier. The angle (θ v – θ i ) is the phase angle between v and i. Since cos(–α) = cosα, the magnitude of average power delivered is independent of whether v leads i or i leads v. ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 6

Resistor: In a purely resistive circuit, since v and i are in phase, ׀θ v – θ i ׀ = θ = 0°, and cosθ = cos0° = 1, so that Inductor: In a purely inductive circuit, since v leads i by 90°, ׀θ v – θ i ׀ = θ = 90°, therefore Capacitor: In a purely capacitive circuit, since i leads v by 90°, ׀θ v – θ i ׀ = θ = ׀–90° ׀ = 90°, therefore ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 7

Ex Find the average power dissipated in a network whose input current and voltage are the following: i = 5 sin(ω t + 40° ) v = 10 sin(ω t + 40° ) ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 8

Ex Determine the average power delivered to networks having the following input voltage and current: a. v = 100 sin(ω t + 40° )i = 20 sin(ω t + 70° ) b. v = 150 sin(ω t – 70° )i = 3sin(ω t – 50° ) ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 9

ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 2 In the equation P = (V m I m /2)cosθ, the factor that has significant control over the delivered power level is the cosθ. No matter how large the voltage or current, if cosθ = 0, the power is zero; if cosθ = 1, the power delivered is a maximum. Since it has such control, the expression was given the name power factor and is defined byPower factor = F p = cosθ Power Factor For a purely resistive load such as the one shown in Fig , the phase angle between v and i is 0° and F p = cosθ = cos0° = 1. The power delivered is a maximum of (V m I m /2)cosθ = ((100V)(5A)/2)(1) = 250W. For purely reactive load (inductive or capacitive) such as the one shown in Fig , the phase angle between v and i is 90° and F p = cosθ = cos90° = 0. The power delivered is then the minimum value of zero watts, even though the current has the same peak value as that encounter in Fig Figure14.33 Purely resistive load with F p = 1. Figure14.34 Purely inductive load with F p = 1.

For situations where the load is a combination of resistive and reactive elements, the power factor varies between 0 and 1. The more resistive the total impedance, the closer the power factor is to 1; the more reactive the total impedance, the closer power factor is to 0. The terms leading and lagging are often written in conjunction with the power factor. They are defined by the current through the load. If the current leads the voltage across a load, the load has a leading power factor. If the current lags the voltage across the load, the load has a lagging power factor. In other words, capacitive networks have leading power factor, and inductive networks have lagging power factors. ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 11

Ex Determine the power factors of the following loads, and indicate whether they are leading or lagging: a. Fig b. Fig c. Fig Figure Figure 14.35Figure ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 12

ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 13 Complex Numbers In our analysis of dc network, we found it necessary to determine the algebraic sum of voltages and currents. Since the same will be also be true for ac networks, the question arises, How do we determine the algebraic sum of two or more voltages (or current) that are varying sinusoidally? Although one solution would be to find the algebraic sum on a point-to-point basis, this would be a long and tedious process in which accuracy would be directly related to the scale used. It is purpose to introduce a system of complex numbers that, when related to the sinusoidal ac waveforms that is quick, direct, and accurate. The technique is extended to permit the analysis of sinusoidal ac networks in a manner very similar to that applied to dc networks. Figure Defining the real and imaginary axes of a complex plane. A complex number represents a points in a two- dimensional plane located with reference to two distinct axes. This point can also determine a radius vector drawn from the original to the point. The horizontal axis called the real axis, while the vertical axis called the imaginary axis. Both are labeled in Fig

ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 14 Rectangular Form The format for the rectangular form is C = X +jY As shown in Fig The letter C was chosen from the word “complex.” The boldface notation is for any number with magnitude and direction. The italic is for magnitude only. In the complex plane, the horizontal or real axis represents all positive numbers to the right of the imaginary axis and all negative numbers to the left of imaginary axis. All positive imaginary numbers are represented above the real axis, and all negative imaginary numbers, below the real axis. The symbol j (or sometimes i) is used to denote the imaginary component. Two forms are used to represent a point in the plane or a radius vector drawn from the origin to that point. Figure Defining the rectangular form.

ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 15 Ex Sketch the following complex numbers in the complex plane. a. C = 3 + j4b. C = 0 – j6c. C = –10 –j20 Figure Example (a) Figure Example (b) Figure Example (c)

ET 242 Circuit Analysis – Response of Basic Elements Boylestad 16 Polar Form Z indicates magnitude only and θ is always measured counterclockwise (CCW) from the positive real axis, as shown in Fig Angles measured in the clockwise direction from the positive real axis must have a negative sign associated with them. A negative sign in front of the polar form has the effect shown in Fig Note that it results in a complex number directly opposite the complex number with a positive sign. Figure Defining the polar form. Figure Demonstrating the effect of a negative sign on the polar form.

ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 17 Ex Sketch the following complex numbers in the complex plane: Figure Example (a) Figure Example (b) Figure Example (c)

Conversion Between Forms The two forms are related by the following equations, as illustrated in Fig Figure Conversion between forms. ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 18

ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 2 Ex Convert the following from rectangular to polar form: C = 3 + j4(Fig ) Figure Ex Convert the following from polar to rectangular form: C = 10ے45°(Fig ) Figure 14.50

ET 242 Circuit Analysis II – Average power & Power Factor Boylestad 20 Ex Convert the following from rectangular to polar form: C = –6 + j3(Fig ) Ex Convert the following from polar to rectangular form: C = 10ے230°(Fig ) Figure Figure 14.52