Synchronous Motors When a synchronous machine is used as a motor, it is not self-starting. If the rotor field poles are excited by the field current and.

Slides:



Advertisements
Similar presentations
ENERGY CONVERSION ONE (Course 25741)
Advertisements

Synchronous Machines (AC Generators)
ENERGY CONVERSION ONE (Course 25741) CHAPTER SIX ……SYNCHRONOUS MOTORS.
Induction Motor •Why induction motor (IM)?
Power System Fundamentals
Chapter 4 Synchronous Generators
SYNCHRONOUS MACHINES SUBMITTED BY: Ms. APOORVA KANTHWAL
EE20A - Electromechanical Energy Conversion Induction Machine
Synchronous Machines.
SYNCHRONOUS GENERATORS
Synchronous Machine The stator is similar in construction that of a induction motor The rotor can be Salient or Non-Salient (cylindrical rotor) Field excitation.
AC Machine.
SEE 3433 MESIN ELEKTRIK SYNCHRONOUS MACHINES - Equivalent circuit - - Phasor diagrams -
Synchronous Motors and Generators
SEE 3433 MESIN ELEKTRIK SYNCHRONOUS MACHINES Basic principles.
ECE 4411 Induction Generators Same basic construction as squirrel-cage induction motors Drive at a speed greater than the synchronous speed Not started.
Lesson 37 AC Generators II
Induction motor1 AC Machine Stator ‘a’ phase axis ‘b’ phase axis ‘c’ phase axis
Synchronous Generator
SYNCHRONOUS MACHINES SUBMITTED BY: Ms. JASPREET KAUR
Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.
Department of Electrical and Computer Engineering
ENERGY CONVERSION ONE (Course 25741) CHAPTER SIX (& S.G. parallel op. with Pow. Sys. of chapter 5) SYNCHRONOUS MOTORS.
Synchronous Induction
ENERGY CONVERSION ONE (Course 25741) CHAPTER SIX …. Synchronous Motor Starting.
5.1 INTRODUCTION TO POLYPHASE SYNCHRONOUS MACHINES
Lecture 32Electro Mechanical System1 Assignment 9 Page 373 Problems 16-13, 16-16, and Due Date: Tuesday 19 th April, 2011 Quiz No.5 Next Week Quiz.
Lecture 32Electro Mechanical System1 Synchronous Reactance  The value of X S can be determined by measurements of the open-circuit and short-circuit tests.
1 Motors and Generators ©Dr. B. C. Paul More Fun with Flux Mechanically Rotated Shaft Slip Rings Wires with brush contacts to slip rings Electromagnetic.
Power Factor Improvement Lecture 9. Normally, the power factor of the whole load on a large generating station is in the region of 0·8 to 0·9. However,
Performance Characteristics
Induction Machine The machines are called induction machines because of the rotor voltage which produces the rotor current and the rotor magnetic field.
EET 221 Synchronous Machines Rafiqi.
Chapter 6 Synchronous Motors
AC Machine CHAPTER 3 EKT 415. AC Machine  Alternating current (ac) is the primary source of electrical energy.  It is less expensive to produce and.
Magnetic field due to an electric current
BASIC ELECTRICAL TECHNOLOGY DET 211/3
SMJE 2103 Induction Motor.
SMJE 2103 Synchronous Generator. Scope of discussion 1)Construction 2)Rotation speed 3)Generated voltage 4)Equivalent circuit 5)Power and Torque 6)Testing.
SMJE 2103 Induction Motor.
Synchronous Machines.
Synchronous Motors Introduction An alternator may operate as a motor by connecting its armature winding to a 3-phase supply. It is then called a synchronous.
Synchronous Generator
EEE223 Energy Conversion II Md. Asif Uddin Khan Lecturer, EEE BRAC University.
Lesson 12a: Three Phase Induction Motors
Hafizism february 2007 EMT462 Electrical System Technology LECTURE V mohd hafiz ismail level II jejawi.
CHAPTER 10 SYNCHRONOUS MOTOR Electrical Machines.
SYNCHRONOUS GENERATOR
Lesson 18 Synchronous Motor Operation and Applications
Voltage Regulation.
Under load-simple calculations
Lesson 34: AC Generators II
Module G1 Electric Power Generation and Machine Controls
Principle of Operation
Induction Generators Same basic construction as squirrel-cage induction motors Drive at a speed greater than the synchronous speed Not started as a motor.
AC MACHINE Hasnizah Aris.
Synchronous Motor Principle and basics.
Synchronous Motors and Generators
ELECTRICAL ENGINEERING: PRINCIPLES AND APPLICATIONS, Third Edition, by Allan R. Hambley, ©2005 Pearson Education, Inc. Chapter 17 AC Machines.
UNIT II SYNCHRONOUS MOTOR.
Electrical Machines-II
Some practice problems
Synchronous Machines.
SYNCHRONOUS MACHINES Basic principles
EE216 Electrical Engineering
Principle of Operation
EET 306 Synchronous Machines
Electrical Machines (EELE 3351)
Chapter 38 Synchronous Motor. Chapter 38 Synchronous Motor.
Presentation transcript:

Synchronous Motors When a synchronous machine is used as a motor, it is not self-starting. If the rotor field poles are excited by the field current and the stator terminals are connected to the ac supply, the motor will not start; instead, it vibrates. Let consider two-pole synchronous machine connected to a 3, 60 Hz ac supply. Stator currents will produce a rotating field that will rotate at 3600 rpm in the air gap. At start (t=0), Fig. a, the rotor will therefore experience a clockwise torque, making it rotate in the direction of the stator rotating poles. At t=t1 , let the stator poles move by half a revolution, shown in Fig (b). The rotor poles have hardly moved, because of the high inertia of the rotor.

Synchronous Motors Therefore, at this instant the rotor experiences a counterclockwise torque tending to make it rotate in the direction opposite to that of the stator poles. The net torque on the rotor in one revolution will be zero, and therefore the motor will not develop any starting torque. The stator field is rotating so fast that the rotor poles cannot catch up or lock onto it. The motor will not speed up but will vibrate. Because it not self-started, two methods are normally used to start a synchronous motor: Use a variable-frequency supply Start the machine as an induction motor.

Start with Variable-Frequency Supply By using a frequency converter, a synchronous motor can be brought from standstill to its desired speed. The motor is start with a low-frequency supply. This will make the stator field rotate slowly so that the rotor poles can follow the stator poles. Afterwards, the frequency is gradually increased and the motor brought to its desired speed. This method is expensive since the frequency converter is a costly power conditioning unit. inverter

Start as an Induction Motor For this purpose, a damper or amortisseur winding, which resembles the cage of an induction motor, is mounted on the rotor. To start the motor the field winding is left unexcited. If the motor terminals are now connected to the ac supply, the motor will start as an induction motor. The motor will speed up and will approach synchronous speed. The rotor is then closely following the stator field poles, which are rotating at the synchronous speed. Now if the rotor poles are excited by a field current from a dc source, the rotor poles will be locked to them. The rotor will then run at synchronous speed.

Synchronous Generator Equivalent Circuit Model An equivalent circuit model can be used to study the performance characteristics with sufficient accuracy. Since the steady-state behavior will be studied, the circuit time constant of the field and damper windings need not be considered. The equivalent circuit will be derived on per-phase basis. The excitation current If in the field winding produces a flux f in the air gap. The current Ia in the stator winding produces flux a. Flux a consists of leakage flux al (link with stator winding only) and armature reaction flux ar (link with field winding)

Equivalent Circuit Model Er - Ear = Ef a1= leakage flux ar= armature reaction flux Ef induced by f, Ear induced by ar Ra=effective resistance=1.5 Rdc

Equivalent Circuit Model Generally Ra << Xs, in most cases Ra is neglected Xs=Xar+Xa1 = synchronous reactance Zs = Ra + jXs = synchronous impedance Nre = effective field winding resistance Nse = effective stator phase winding resistance

Determination of The Synchronous Reactance The synchronous reactance is an important parameter in the equivalent circuit of the synchronous machine. It can be determined by performing two tests, open-circuit test and short circuit test.

Determination of The Synchronous Reactance Explain OCC & SCC graphs

Determination of The Synchronous Reactance

Determination of The Synchronous Reactance - Saturated Neglect the drop Ra and Xa1 Zs Machine connected to infinite bus bar If If chance, Ef changes along the line oc (modified air gap line), not on OCC line. For calculation of voltage regulation, Zs is determine at Isc = 2 x full load

Phasor Diagram with Ra generator motor Indicate relationship between voltage and currents Power angle=  generator motor  - magnetic angle between stator and rotor axis

Without Ra generating motoring Ef = Vt + Ia.jXs Ef = Vt - Ia.jXs  vt vt    IajXs Ia Ia generating motoring Ef = Vt + Ia.jXs Ef = Vt - Ia.jXs Using sine rules Pe  Iacos

Effect on generating voltage with power factor If the generator drive lagging load power factor, the main air gap flux (Fr) is reduced since the flux from armature current (Fa) is opposing the excitation flux (Ff) . This reduced the generated voltage, Er. If the generator drive leading power factor, the main air gap flux (Fr) is increased since the flux from armature current (Fa) is aiding the excitation flux (Ff) . This increased the generated voltage. The better the power factor, the higher the generated voltage, Er. vt IaRa Ef   Ia IaX1 IaXar Er Fa Fr Ff vt IaRa Ef   Ia IaX1 IaXar Er Fa Fr Ff Lagging p factor, Er<Ef Leading p factor, Er>Ef

Voltage Regulation When a synchronous generator is connected to a load, the terminal voltage may vary to a certain extent. The amount of variation is known as the voltage regulation. The voltage regulation can be determined by

Based on phasor diagram, at lagging power factor, the voltage Ef also can be calculated as Based on phasor diagram also, at leading power factor, the voltage Ef also can be calculated as

Example 6.2 The following data are obtained for 3-phase, 10 MVA,14 kV star connected synchronous machine. Ra is given as 0.07 /phase If OC (kV) line to line Air gap voltage(kV) line to line SC current (A) 100 9 150 12 200 14 18 490 250 15.3 300 15.9 350 16.4 Find the unsaturated and saturated value of the syn. reactance (in ohm and p.u) Find the field current required if syn. Generator is connected to infinite bus and delivers rated MVA at 0.8 lagging power factor If generator in (b) is disconnected from infinite bus without changing the field current, find the terminal voltage Sen pg. 312 Sol-Pg17SM

Power and Torque Characteristics A synchronous machine is normally connected to a fixed-voltage bus and operates at constant speed. There is a limit on the power a synchronous generator can deliver to the infinite bus and on the torque can be applied to the synchronous motor without losing synchronism. Analytical expressions for the steady-state power transfer between the machine and the constant-voltage bus or the torque developed by the machine will be derived.

Power and Torque Per phase equivalent circuit Complex power S Complex phasor diagram

Power and Torque (VA) (Watt) (VAr)

Power angle / torque angle Power and Torque Zs=Xs, s = 90o Power angle / torque angle Both power and torque vary sinusoidal with power angle,  Machine can be loaded gradually up to Pmax (static stability limit) Beyond 90 degree, machine loss synchronism Field current (Ef) need to be increase if the machine loss synchronism

Example A 3, 5 kVA, 208 V, 4-pole, 60Hz star connected synchronous generator has negligible stator winding resistance and a synchronous reactance of 8 ohms/phase at rated terminal voltage. a) Determine the excitation voltage and power angle when machine delivers rated kVA at 0.8 lagging PF. Draw the phasor diagram b) If the field current is increased by 20% (fixed prime Mover), find the stator current, power factor, and reactive kVA supplied by the machine. c) With field current as in (a), the prime mover is slowly increased. What is steady state stability limit ? Sol_pg22_SM Sen 319

Example 1 The synchronous machine in example 6.3 is operated as a synchronous motor from the 3, 208 V, 60Hz power supply. The field excitation is adjusted so that the power factor is unity when the machine draws 3 kW from the supply. Find the excitation voltage and the power angle. Draw the phasor diagram for this condition. If the field excitation is held constant and the shaft load is slowly increased, determine the maximum power & torque that the motor can deliver. Sen pg. 322 Ans: 137.35< -29o V, 6185 W, 32.8 Nm

The Effect of Changing Excitation Current at Constant Power Output When connected to infinite bus bar Generator output power (W) control by the amount of steam applied. Pe = VIcos , i.e. Pe proportional to Icos  (fixed) Assume the generator operates in lagging power factor Ia = Iacos  + jIasin  vt Ia1jXs Ef1   Ia1 Constant power output Ef2 Limit of instability changed Over-excited (lagging p f) under-excited Power factor = unity (1) Ia2 Ia3 Ef3 Excitation voltage(E) slides on the constant power line Under excited = If small Over excited = If big fixed **Remarks: Reactive Power delivered by the generator can be controlled by the excitation/field current, in over excitation machine supplies inductive reactive power**

The Effect of Changing Excitation Current at Constant Power Output When connected to infinite bus bar Example : The star-connected synchronous machine has synchronous reactance of 20 ohm/phase. It supplies load current of 150 A with power factor 0.8 lagging to an infinite bus bar. The bus bar voltage is 11 kV. If the supply steam to the machine prime mover is fixed, calculate the percentage change in excitation voltage if the load power factor load is 0.8 leading. Neglect power losses. Ans: Eo1 = 8497 < 16.41o, Eo2 = 5145<21.8o; -39%

Limit of stability of Pmax The effect of Changes the Output Power on Infinite Bus Bar at Fixed Excitation Current vt Ia1jXs Ef1 1  Ia1 Constant power lines power output varies, P  Iacos Ef2 Ef3 |Ef1|=|Ef2|=|Ef3| Ia2jXs Ia3jXs Limit of stability of Pmax 2 Excitation voltage(E) swings from one the constant power line to another Unity pf line Ia = Iacos  + jIasin  changed fixed **Remarks: Active Power delivered by the generator can be controlled by the steam supplied into prime mover**

Example 2 Page 371, Q: 6.2 The excitation voltage per phase. A 3, 250 hp, 2300 V, 60Hz, Y-connected non-salient rotor synchronous motor has a synchronous reactance of 11  per phase. When it draws 165.8 kW the power angle is 15 electrical degrees. Neglect ohmic losses. Determine: The excitation voltage per phase. The supply line current. The supply power factor. (0.77 leading) If the mechanical load is thrown off and all losses become negligible, Determine the new line current and supply power factor. Draw the phasor diagram for the condition in (i). By what percent should the field current If be changed to minimize the line current? (75 %) Page 371, Q: 6.2

Complex Power Locus/ Capability Curve Define the bounds within which generator can work safely MVA loading < gen. rating (-- stator/armature heating) MW-loading < turbine rating (MVA x power factor) Save from steady state stability limit (  < 90 o) 4. Max. field current < specified by rotor heating Neglect Ra, multiply each phasor by Vt/Xs vt IajXs Ef   Ia 0’ XsIasin M N VtIa   0’ M Q VtIacos P XsIacos VtIasin

0’

Power Factor Control An outstanding feature of the synchronous machine is that the power factor of the machine can be controlled by the field current. The field current can be adjusted to make the stator (or line) current lagging or leading as desired. The power factor characteristic can be explained by drawing phasor diagrams of machine voltages and currents.

Power Factor Control Vt=Ef + jIaXs Ef =Vt - jIaXs Unity p factor Leading pf Lagging pf Under-excited Over-excited Normal -excited Vt=Ef + jIaXs Ef =Vt - jIaXs Utilize field current to stator current leading or lagging

Power Factor Control The unique feature of power factor control by the field current can be utilized to improve the power factor of a plant. In a plant most of the motors are normally induction motors, which draw power at lagging power factors. Synchronous motors can be installed for some drives in the plant and made to operate in an overexcited mode so that these motors operate at leading power factors. This will compensate the lagging power factor of the induction motors and thereby improving the overall power factor of the plant.

Example: 2009/10 Q5: (a) Discuss briefly the effect of the generated voltage when synchronous generator operates in lagging and leading power factor. (b) Draw a per phase equivalent circuit of a synchronous machine. Label all parameters clearly. Derive the real power generated output of that machine. (c) A three phase, 1500 kVA, 12 kV, six pole, 50 Hz, star connected synchronous generator has a synchronous resistance and synchronous reactance of 2 W/phase and 35 W/phase respectively. If the generator is connected to a load of 120 kW, determine the voltage regulation if the load is operated at a power factor of i. 0.8 lagging. ii. 0.8 leading. Sol_pg33-SM

Example 07/08-2 Sol-pg34