1 Voltage Collapse Animation (AC) Created by Peter W. Sauer Department of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.

Slides:



Advertisements
Similar presentations
Announcements Homework 6 is due on Thursday (Oct 18)
Advertisements

EE369 POWER SYSTEM ANALYSIS
SYNCHRONOUS MACHINES.
Lecture 2 Complex Power, Reactive Compensation, Three Phase Dr. Youssef A. Mobarak Department of Electrical Engineering EE 351 POWER SYSTEM ANALYSIS.
Voltage Collapse Animation (DC) Created by Chad Thompson and Pete Sauer of The University of Illinois at Urbana-Champaign Based on a previous animation.
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems Prof. Hao Zhu Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Let us now use this realistic view of a battery in a simple circuit containing a battery and a single resistor. The electric potential difference across.
EE 369 POWER SYSTEM ANALYSIS
Announcements Be reading Chapter 6, also Chapter 2.4 (Network Equations). HW 5 is 2.38, 6.9, 6.18, 6.30, 6.34, 6.38; do by October 6 but does not need.
Basic Laws of Electric Cicuits Fundamentals Lesson 1.
1 PS ERC Reactive Power and Voltage Control Peter W. Sauer Department of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 333 Renewable Energy Systems Lecture 13: Per Unit, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
Lecture 27Electro Mechanical System1  The fact that power is always positive reveals that it always flows from the generator to the resistor.  This is.
NETWORK OPERATING DIVISION Operating Effectiveness Phase Shifters What is a Phase Shifter These transformers create a difference in phase angle between.
SEMICONDUCTORS Zener diodes.
EE369 POWER SYSTEM ANALYSIS
Unit 6 Series Circuits.
1 Cheng-Ting Hsu Chao-Shun Chen Islanding Operations for the Distribution Systems with Dispersed Generation Systems Department of Electrical Engineering.
1 Chapter 11 AC Power Analysis 電路學 ( 二 ). 2 AC Power Analysis Chapter Instantaneous and Average Power 11.2Maximum Average Power Transfer 11.3Effective.
BJT Amplifiers (cont’d)
Electrical Resistance and Ohm’s Law Electric circuits are used to convert electrical energy into some other form of energy we need.
10/9/20151 General Physics (PHY 2140) Lecture 10  Electrodynamics Direct current circuits parallel and series connections Kirchhoff’s rules Chapter 18.
Announcements Please read Chapter 4 HW 1 is due now
Chapter 11 AC Power Analysis
Review 1. Review of Phasors Goal of phasor analysis is to simplify the analysis of constant frequency ac systems: v(t) = V max cos(  t +  v ), i(t)
Announcements Homework #4 is due now Homework 5 is due on Oct 4
Series wiring means that the devices are connected in such a way that there is the same electric current through each device. One loop only for the flow.
Unseparated charges separated charges Work or Energy must be done to separate positive and negative charges Voltage is the energy per unit charge created.
2 But what makes the electrons flow? Any electrical circuit requires three things 1.A source 2.A load 3.A means of transmission A definition of a current.
Chapter 17 Power in AC Circuits.
ERCOT Wind Survey Leo Villanueva. Abilene Mc Camey Big Spring.
ECE 476 Power System Analysis Lecture 11: Ybus, Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
MAXIMUM POWER TRANSFER THEOREM
PS ERC 1 Reactive Power Considerations in Linear Load Flow with Applications to Available Transfer Capability Pete Sauer (With a lot of help from Santiago.
ECE 476 Power System Analysis Lecture 8: Transmission Line Parameters, Transformers Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.
ECE 476 Power System Analysis Review 1 Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign
Lecture 13 Newton-Raphson Power Flow Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Announcements Please read Chapters 1 and 2
Lecture 11 Power Flow Professor Tom Overbye Special Guest Appearance by Professor Sauer! Department of Electrical and Computer Engineering ECE 476 POWER.
ECE 476 Power System Analysis Lecture 14: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
CH Model of a real battery A real battery can be modeled as an ideal battery (i.e. voltage source) and an internal resistance r. The voltage across.
Optimal Power Flow- Basic Requirements For Real Life.
ECE 476 Power System Analysis Lecture 18: LMP Markets, Symmetrical Faults and Components Prof. Tom Overbye Dept. of Electrical and Computer Engineering.
ECE 476 Power System Analysis Lecture 13: Power Flow Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems Prof. Hao Zhu Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems Prof. Hao Zhu Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
ELEN 3441 Fundamentals of Power Engineering Spring Instructor: Dr. Gleb V. Tcheslavski Contact: Office Hours:
0 Balanced 3 Phase (  ) Systems A balanced 3 phase (  ) system has three voltage sources with equal magnitude, but with an angle shift of 120  equal.
Abilene Mc Camey Big Spring. Far West Abilene Area All the values are based on returned ERCOT survey results Total number of Wind Powered Generation.
1 Chapter 3 AC Power Analysis. 2 AC Power Analysis Chapter 3 3.1Instantaneous and Average Power 3.2Maximum Average Power Transfer 3.3Effective or RMS.
RESISTORS IN SERIES - In a series circuit, the current is the same
Announcements Please read Chapter 6
Components Motors and Generators.
Components Motors and Generators.
Announcements For lectures 7 to 9 please be reading Chapter 5.
ECE 476 POWER SYSTEM ANALYSIS
SIMULATION AND IMPLEMENTATION OF FC-TCR
ECEN 460 Power System Operation and Control
ECE 476 Power System Analysis
ECE 476 POWER SYSTEM ANALYSIS
ECEN 460 Power System Operation and Control
Introduction To Reactive Power
General Physics (PHY 2140) Lecture 10 Electrodynamics
Automatic Generation Control (AGC)
Voltage Collapse Animation (DC)
ECEN 460 Power System Operation and Control
ECEN 460 Power System Operation and Control
Unseparated charges separated charges
ECEN 460 Power System Operation and Control
Power system operation and control
Presentation transcript:

1 Voltage Collapse Animation (AC) Created by Peter W. Sauer Department of Electrical and Computer Engineering University of Illinois at Urbana-Champaign © 2003 Peter W. Sauer PS ERC

2 Introduction The following slides simulate a voltage collapse in a simple power system. The West generator has unlimited VAR (or reactive power) supply capability so it is able to keep the voltage at its bus constant at 1.0 per unit (or at the rated voltage). The East generator can only supply up to 1,200 MVARs (or 1,200 million VARs). There are 6,000 MWs of real power load and 1,000 MVARs of reactive power load at each bus. The West generator is transferring 3,000 MW to the East to help serve the 6,000 MW load in the East. Therefore, the outputs of the West and East generators are 9,000 MW and 3,000 MW respectively. Six identical lines are initially in service and the 3,000 MWs of real power transfer are divided equally across the lines. The generators in the West and East are supplying reactive power (or VARs) to their local loads plus VARs to the transmission lines to support the transfer. The lines are assumed to be lossless (that is, they do not absorb real power). We have assumed that the individual line capacities (or thermal ratings) exceed 3,000 MW so the real power transfer could occur on one line if maintaining voltage (through sufficient VAR supply) is not a problem. Circuit breakers can open (or trip) the lines.

3 Symbols in the Simulation Window Buses: heavy dark lines (East and West) where the generators, loads and transmission lines interconnect Transmission lines: lines connecting the two buses Generators: circles with “dog bone rotors” Loads: arrows connected to the buses Circuit breakers: red boxes Line flows: arrows on the transmission lines (more easily seen in the last three simulations that follow) indicate the direction and magnitude of power flow

4 Simulating an AC System Voltage Collapse Suppose the lines fail (that is, trip out) one at a time for any reason. Case 1: No Lines Out. Bus voltages at 1.0 per unit (or rated voltage). Both bus voltages are being controlled by their respective generator VAR supplies. Case 2: One Line Out. Bus voltages at 1.0 per unit (or rated voltage). Both bus voltages are being controlled by their respective generator VAR supplies. Case 3: Two Lines Out. Bus voltages at 1.0 per unit (or rated voltage). Both bus voltages are being controlled by their respective generator VAR supplies although the East generator has just hit its VAR limit. Case 4: Three Lines Out. East bus voltage at 0.99 per unit because East generation is at its reactive power supply limit. West generation still has unlimited reactive power supply capability. Case 5: Four Lines Out. East bus voltage drops to 0.97 per unit. East generation at its reactive power supply limit. West reactive power generation continuing to rise. Case 6: Voltage collapse! With five lines out, the simulation fails – which indicates that it is not possible to transfer 3,000 MW without additional reactive power support in the East even if West generation has excess reactive power supply capacity!

5 Case 1: All Lines In-Service 3,000 MW transfer – 500 MW per line Voltage is 100% of rated voltage. (300 MVARs required by lines). East generator is below 1,200 MVAR limit. 5

6 Case 2: One Line Out 3,000 MW transfer – 600 MW per line Voltage is 100% of rated voltage (362 MVARs required by lines). East generator is below 1,200 MVAR limit. 6

7 Voltage is 100% of rated (453 MVARs required by lines). East generator is at 1,200 MVAR limit. Case 3: Two Lines Out 3,000 MW transfer – 750 MW per line 7

8 Voltage is only 99% of rated (611 MVARs required by lines). East generator is at 1,200 MVAR limit. Case 4: Three Lines Out 3,000 MW transfer – 1,000 MW per line 8

9 Voltage has dropped to 97% of rated voltage (957 MVARs required by lines). East generator is at 1,200 MVAR limit. Case 5: Four Lines Out 3,000 MW transfer – 1, 500 MW per line 9

10 This simulation could not solve the case of 3,000 MW transfer with five lines out. Numbers shown are from the model’s last attempt to solve. The West generator’s unlimited supply of VARs is still not sufficient to maintain the voltage at the East bus. Case 6: Five Lines Out Voltage Collapse 10