Dimensioning of CO 2 cooling pipes in detector structures Pipe dimensioning & Flow distribution Detector Mechanics Forum Oxford, 20 June 2013 Bart Verlaat.

Slides:



Advertisements
Similar presentations
1 Ann Van Lysebetten CO 2 cooling experience in the LHCb Vertex Locator Vertex 2007 Lake Placid 24/09/2007.
Advertisements

Using Copper Water Loop Heat Pipes to Efficiently Cool CPUs and GPUs Stephen Fried President Passive Thermal Technology, Inc.
So Far: Conservation of Mass and Energy Pressure Drop in Pipes Flow Measurement Instruments Flow Control (Valves) Types of Pumps and Pump Sizing This Week:
1 Nikhef Activities on CO 2 Cooling Bart Verlaat, Nikhef Introduction meeting with FOM director W. van Saarloos 1 Picture: LHCb-VELO evaporator.
A.P.Colijn1 CO2 Cooling for an ATLAS upgrade Plant requirements CO 2 : Properties CO 2 : Consequences of the properties CO 2 : From LHCb to ATLAS (or the.
Experimental Verification of Gas- Cooled T-Tube Divertor Performance L. Crosatti, D. Sadowski, S. Abdel-Khalik, and M. Yoda ARIES Meeting, UCSD (June 14-15,
LHCb-VELO evaporator CoBra Calculation and feed through ideas. 18 February 2015 Bart Verlaat 1.
Lesson 15 Heat Exchangers DESCRIBE the difference in the temperature profiles for counter-flow and parallel flow heat exchangers. DESCRIBE the differences.
Novel technologies and materials for thermal management
IBL temperature analyses Bart Verlaat 22 April
Heat Pipes Heat Exchangers P M V Subbarao Professor Mechanical Engineering Department I I T Delhi Heat Exchange through Another Natural Action….
CO 2 return pressure drop budget and pipes from PP2 to tracker Georg Viehhauser.
Heat and Mass Transfer Laboratory
RF-Accelerating Structure: Cooling Circuit Modeling Riku Raatikainen
ME421 Heat Exchanger and Steam Generator Design Lecture Notes 6 Double-Pipe Heat Exchangers.
1 CO 2 cooling of an endplate with Timepix readout Bart Verlaat, Nikhef LCTPC collaboration meeting DESY, 22 September
CO 2 Development of the Velo Thermal Control System (VTCS)
Status overview of the cooling 31 August 2015 Bart Verlaat, Raphael Dumps 1.
Heat Transfer Equations For “thin walled” tubes, A i = A o.
Lesson 8 SECOND LAW OF THERMODYNAMICS
LHCb CO 2 cooling meeting Burkhard Schmidt – February 18,
20 th June 20111Enrico Da Riva, V. Rao Project Request and Geometry constraints June 20 th 2011 Bdg 298 Enrico Da Riva,Vinod Singh Rao CFD GTK.
So Far: Conservation of Mass and Energy Pressure Drop in Pipes Flow Measurement Instruments Flow Control (Valves) Types of Pumps and Pump Sizing This Week:
Update on UT cooling specifications and status of activities LHCb CO2 cooling meeting 8/7/2015 Simone Coelli For the Milano UT group INFN milano 1 Istituto.
By: Narendra Babu N M110247ME THERMAL ANALYSIS OF MICROPROCESSOR.
JCOV, 25 OCT 2001Thermal screens in ATLAS Inner Detector J.Godlewski EP/ATI  ATLAS Inner Detector layout  Specifications for thermal screens  ANSYS.
30 th June 20111Enrico Da Riva, V. Rao Parametric study using Empirical Results June 30 th 2011 Bdg 298 Enrico Da Riva,Vinod Singh Rao CFD GTK.
LHCb VELO Meeting LHCb VELO Cooling System Bart Verlaat (NIKHEF) 25 February 2003.
26 May 2010Hans Postema - CERN Status and plan for the development and construction of CO2 Cooling System for Pixel Upgrade 1.
1 GL th IIF/IIR Gustav Lorentzen Conference on Natural Working Fluids Bart Verlaat National Institute for Subatomic Physics (NIKHEF) Amsterdam, The.
TSV-Constrained Micro- Channel Infrastructure Design for Cooling Stacked 3D-ICs Bing Shi and Ankur Srivastava, University of Maryland, College Park, MD,
Convection: Internal Flow ( )
LHCb-VELO Microchannel fracture safety system and evaporator concept 26 June 2015 Bart Verlaat 1.
CO 2 Cooling: Overview over CMS activities Jennifer Merz RWTH Aachen University, 1. Physikalisches Institut B May CEC General Meeting, Karlsruhe.
UT cooling discussion 3 december 2014
PRESENTATION OF CFD ACTIVITIES IN CV GROUP Daniel Gasser.
1 Monophase Measurements on Prototype Pixel Structures D. Bintinger, M. Gilchriese, J. Taylor and J. Wirth and contributions from D. Cragg, E. Perrin and.
Heat Transfer Equations For “thin walled” tubes, A i = A o.
M. Gomez Marzoa1 WG4 Meeting - 12th December 2012 Update on stave thermal testing Claudio BORTOLIN Enrico DA RIVA Corrado GARGIULO Manuel GOMEZ MARZOA.
Cooling System Solutions
CO2 cooling in CMS General overview 30 July 20101Hans Postema - CERN.
Refrigeration Cycles A Carnot cycle in reverse QL QH T s 2
Phase 1 FPix Cooling Tube Testing Erik Voirin, C.M. Lei, Harry Cheung, Stefan Gruenendahl (FNAL) Kirk Arndt, Qiuguang Liu (Purdue) Phase 1 FPIX cooling.
Limits of CO 2 Cooling A clear explanation that anyone can understand (the goal) Hans Postema & Joao Noite PH-CMX-DS1.
News on the CO 2 cooling developments at CERN DT CMS Tracker Upgrade Cooling and Mechanics meeting Bart Verlaat 13 October
Analysis of Flow Boiling
CO 2 Controlling a 2-phase CO2 loop using a 2-phase accumulator
CO2 Cooling For the CMS Pixel detector 11 November 20081Hans Postema & Antti Onnela.
COOLING BY EVAPORATION OF PERFLUOROCARBONS Why evaporate? 1. To enhance the heat transfer per unit area The heat transfer coefficient increases significantly.
LHCb-UT and Velo Upgrade Road to a system EDR in Q June 2015 Bart Verlaat 1.
Aachen Status Report: CO 2 Cooling for the CMS Tracker at SLHC Lutz Feld, Waclaw Karpinski, Jennifer Merz and Michael Wlochal RWTH Aachen University, 1.
Heat Transfer by Convection
A two-stage system for the future cooling system.
High Granularity Calorimeter Workshop Ideas for cooling of a high granularity calorimeter Nick Lumb, IPN-Lyon 02/02/2015.
7 February 2012 Annekathrin Frankenberger (HEPHY Vienna) Open CO 2 Cooling System at the beam test Belle II SVD-PXD Meeting.
Heat Transfer Su Yongkang School of Mechanical Engineering # 1 HEAT TRANSFER CHAPTER 11 Heat Exchangers.
Chapter 12B: PROPERTY TABLES, REFRIGERATION CYCLES AND HX 1) Boiling of pure substances: water and steam tables 2) Refrigerant tables 3) Binary mixtures.
For the CMS Pixel detector
Design of the thermosiphon Test Facilities 2nd Thermosiphon Workshop
For the CMS Pixel detector
FPix Cooling Circuit. FPix Cooling Circuit FPix Shared HD - Nominal Flow ΔPtotal = 5bar Δm = 0.5g/s mnominal = 2.6g/s ΔPtotal = 10bar Δm = 0.2g/s mnominal.
Aachen Status Report: CO2 Cooling for the CMS Tracker
Aachen Status Report: CO2 Cooling for the CMS Tracker at SLHC
Progress at the large scale CO2 system,
VELO Thermal Control System
Aachen Status Report: CO2 Cooling for the CMS Tracker
CO 2 CO2 Cooling for HEP experiments Bart Verlaat TWEPP-2008
Steam traps Applications and Recommendations
For the CMS Pixel detector
CO 2 CO2 COOLING FOR THE LHCB-VELO EXPERIMENT AT CERN Bart Verlaat
Presentation transcript:

Dimensioning of CO 2 cooling pipes in detector structures Pipe dimensioning & Flow distribution Detector Mechanics Forum Oxford, 20 June 2013 Bart Verlaat 1

Thermal chain in detectors The design of the cooling is the whole chain between heat source and heat sink 2 Heatload SiliconC-foam Pipe wall CO2 in tube Manifold CF-sheet Th. paste Glue HTC ΔPΔP Typical example for IBL

Thermal chain in detectors The design of the cooling is the whole chain between heat source and heat sink 3 Heatload SiliconC-foam Pipe wall CO2 in tube Manifold CF-sheet Th. paste Glue HTC ΔPΔP Load variations give gradients w.r.t the common sink => Outlet manifold! Typical example for IBL

Design of cooling: From source to sink So the reference should not be at a pipe wall, nor at the liquid temperature as it is generally approached. –This is similar then taking a reference in the middle of the structure. 4 Pressure drop ~20% Heat transfer ~ 19% Stave conductance ~61% Loaded stave temperature: -24.4°C (0.72 W/cm 2 ) Unloaded stave temperature: -39°C Atlas IBL example Outlet Manifold = temperature reference Inlet manifold

How to optimize the cooling as part of the whole thermal chain? The best thermal solution is not only related to small temperature gradients. –If so our detectors will be made of copper… –We have to find the balance between the important parameters Generally thermal gradients vs mass (rad. Length) How can we find the optimum cooling tube dimension? –Depends on the real criteria: Lowest mass (Radiation length)? Smallest pipe? Minimum amount of pipes? –We should not only look at the pipe but also at the structure around A smaller cooling tube is replaced by other material, when embedded. Where do we have to look at: –Pressure drop and heat transfer As part of the thermal chain –Flow distribution For the proper fluid conditions 5

6 First we need to understand what happens inside a cooling tube? Heating a flow from liquid to gas

Understanding detector evaporator tubes In a 2PACL the capillary inlet temperature is a function of the outlet saturation pressure. The detector inlet is close to saturation. –But can be liquid due to pressure drop –Usually ambient heating is enough to overcome sub cooled entry state –Detectors with high dP have to be designed to cope with liquid at the inlet FE: pre heating by electronics (CMS pixel) Pressure drop of the evaporator tube and outlet tube is part of the thermal resistance chain from heat source to sink! 7 Outlet manifold: Pressure = fixed Inlet manifold: Temperature = fixed Temperature exchange Outlet line dP Detector dP Inlet capillary dP Inlet manifold outlet manifold

Long branch thermal profile Outlet tube Inlet tube Evaporator tube Offset of evaporator temperature due to outlet pressure drop Temperature gradient inside detector due to pressure drop and heat transfer Liquid2-Phase Manifold temperature = common reference of all branches HTC dP Liquid entry into evaporator Inlet: 2mm x 4m, Detector: 2mm x 4m, Outlet: 2mm x 4m Heatload on detector: 200 Watt

Flow distribution: Inlet tube reduction 9 Figures from: DESIGN CONSIDERATIONS OF LONG LENGTH EVAPORATIVE CO2 COOLING LINES Bart Verlaat and Joao Noite, GL-209, 10th IIF/IIR Gustav Lorentzen Conference on Natural Working Fluids, Delft, The Netherlands 2012 Inlet: 2mm x 4m Stave: 2mm x 4m Outlet: 2mm x 4m Inlet: 1mm x 4m Stave: 2mm x 4m Outlet: 2mm x 4m Pumping energy is flow x dP. Adding capillaries can save pumping power (in example 1.61*3.54/2.18*3.75=0.70 => 30% saving) Pressure drop and dry-out calculated using CoBra Which flow do we need when 200 Watt to a single stave is applied?

Influence of the in and outlet- lines on thermal performance 10 Figures from: DESIGN CONSIDERATIONS OF LONG LENGTH EVAPORATIVE CO2 COOLING LINES Bart Verlaat and Joao Noite, GL-209, 10th IIF/IIR Gustav Lorentzen Conference on Natural Working Fluids, Delft, The Netherlands 2012 Inlet: 2mm x 4m Stave: 2mm x 4m Outlet: 2mm x 4m Inlet: 1mm x 4m Stave: 2mm x 4m Outlet: 2mm x 4m Inlet: 1mm x 4m Stave: 2mm x 4m Outlet: 3mm x 4m

Dealing with environmental heat pick-up Three important statements: –Expose return tube to ambient heating There is usually enough cooling power left –Connect as much as possible the inlet to the outlet Outlet boils first (lower P), so will take care of heat absorption –Avoid boiling before the inlet manifold Flow separation will feed some channels with vapor only! 11 Pre capillary heat pickup Inlet manifold outlet manifold Manifold boiling Outlet transfer line outlet manifold Outlet transfer line Capillary dP makes manifold liquid To keep this problem simple: Have the manifold right after the heat exchanging transfer line. Remaining cooling power for ambient

IBL: A detector with very long in and outlet lines The IBL detector is only 800mm long, but has about 15m long in and outlets. dT due outlet line pressure drop significantly (ca 3 º C) Ambient heat load in same order as detector load 12 Atlas IBL example Ambient heating Heat exchange Inlet Outlet IBL Ambient

Cooling tube temperature profile (HTC & ΔP) In detectors the aim of a cooling tube design is: –Low mass or small diameter –Low temperature gradient (hottest point wrt outlet reference) For efficient heat transfer: –ΔT( ΔP+HTC ) and tube diameter or mass as small as possible To quantify the optimal diameter we can look either to the mass or tube volume involved 13 ΔT( ΔP ) (Reduced diameter) ΔT( HTC ) (Reduced diameter) ΔT( HTC ) ΔT( ΔP+HTC ) (Reduced diameter) ΔT( ΔP+HTC ) Tube length Temperature Fluid temperature Tube temperature V tube *ΔT (ΔP+HTC) ) Q Volumetric heat transfer = (W/m 3 *K) M*ΔT (ΔP+HTC) ) Q Mass specific heat transfer = (W/kg*K)

Volumetric heat transfer coefficient Optimal Diameter? Overall temperature gradient Heat transfer temperature gradient Pressure drop temperature gradient Cooling tube performance example L=3m, Q=400W, T=-20°C Models used: HTC and dP, Thome 2008

Comparison of fluids Volumetric heat transfer is also a good method to compare different fluids. –How can we put as much heat into a small as possible cooling tube?? Interesting: Performance almost linear with fluid pressure. 15 Models used: HTC-Kandlikar and dP-Friedel

“Drawback” of smaller pipes In an embedded structure the smaller pipe is replaced by other material. –‘Heavy” pipe has a lower weight, but light vapor is also replaced by “something” The bottleneck in most cooling structures is the glue layer around the pipe. –Small area –Bad conductance Better to judge the whole thermal chain from a fixed volume 16 What is now an optimal pipe diameter? D=10mm

Mass related results (Same case as previous) Calculation with IBL-like properties: –T_tube=0.1 mm –T_glue=0.1 mm –k_tube=7.2 W/mk –k_foam=35 W/mk –k_glue=1.02 W/mk –d_glue=2400 kg/m3 –d_foam=198 kg/m3 –d_tube=4400; kg/m3 17

Recalculating the IBL Selected IBL tube is 1.5mm => good choice! Next to do: Make similar analyses wrt radiation length mm

CO 2 heat transfer and pressure drop modeling Nowadays good prediction models of CO 2 are available. For detector analyzes we use mainly the models of J. Thome from EPFL Lausanne (Switzerland) –Cheng L, Ribatski G, Quiben J, Thome J, 2008,”New prediction methods for CO 2 evaporation inside tubes: Part I – A two-phase flow pattern map and a flow pattern based phenomenological model for two-phase flow frictional pressure drops”, International Journal of Heat and Mass Transfer, vol 51, p –Cheng L, Ribatski G, Thome J, 2008,”New prediction methods for CO 2 evaporation inside tubes: Part II– An updated general flow boiling heat transfer model based on flow patterns”, International Journal of Heat and Mass Transfer, vol 51, p Models are flow pattern based and are reasonably well predicting the flow conditions and the related heat transfer and pressure drop. Dry-out prediction is included. The Thome models are successfully used to predict the complex thermal behavior of particle detector cooling circuits. A simulation program called CoBra is under development at Nikhef/CERN-DT to analyze full detector cooling branches. 19

Experimental heat transfer data (measured at SLAC) 20 Interesting research on heat transfer is done at SLAC in a joint effort with Nikhef. M. Oriunno (SLAC) & G. Hemmink (Nikhef)

CoBra Model (CO 2 BRAnch Model) 21 R1 x R2 x R3 x R5 x R2 y+1 R3 y+1 R4 x R4 y+1 R1 y+1 R1 X+1 R2 X+1 R3 X+! R5 X+1 R2 y R3 y R4 X+1 R4 y R1 y P x+1,H x+1,T x+1 P x,H x T x P y+1,H y+1,T y+1 P y,H y,,T y T P x+1 =dP x+1 +P x H x+1 =dH x+1 +H x dH=Q1/MF Q1 is calculated in the thermal network The thermal node network calculates the heat influx in the cooling pipe based on: Applied power Q3 on node 3 Environmental heating from fixed temperature T4 on node 4 Heat exchange with another pipe section via R5 between nodes 2 and 2 of the connected sections

CoBra example calculation CoBra is able to analyze complex thermal profiles of CO 2 in long tubes 22 5mx1.5mmID tube (4m heated), Mass flow=0.3g/s, Q=90Watt, T=-30 º C Dry- out Mist Annular Stratified Wavy Stratified Bubbly Slug Process path Dry-out Liquid Slug Annular

Cobra example: Node network for IBL 23 T environement R 4 ≈ HTC air R 2 +R 3 ≈ TFoM R 1 ≈ HTC CO2 T CO2 T environement T CO2 R 4 +R 3 ≈ Insulation+HTC air R 5 ≈ Heat exchange R 1 ≈ HTC CO2 R 2 ≈ Tube wall Q 3 ≈ Applied power T environement T CO2 R 4 +R 3 ≈ HTC air R 1 ≈ HTC CO2 R 2 ≈ Tube wall T environement T CO2 R 1 ≈ HTC CO2 R 2 ≈ Tube wall T CO2 R 1b ≈ HTC CO2 R 1a ≈ HTC CO2 R 4 +R 3 ≈ Insulation+HTC air 1. Concentric line 3. Bare tube 2. Bundled lines 4. Stave

Internal heat exchange and ambient heating 24 Figure 7: CoBra calculation example of the IBL cooling tube. The branch has a 1mm inlet (1-4), a 1.5 mm cooling tube (4- 8), a 2mm outlet (8-9) followed by a 3mm outlet (9-12). The dashed temperature profile is the actual sensor temperature taking into account the conductance of the support structure. The graph on the left has no internal heat exchange, the right graph takes internal heat exchange of the in and outlet tube into account. Figures from: DESIGN CONSIDERATIONS OF LONG LENGTH EVAPORATIVE CO2 COOLING LINES Bart Verlaat and Joao Noite, GL-209, 10th IIF/IIR Gustav Lorentzen Conference on Natural Working Fluids, Delft, The Netherlands 2012

Comparison to test results 25 Figure 8: Temperature and pressure test results of the CMS pixel upgrade cooling branch (left) and the Atlas IBL cooling branch (right). Comparison with the CoBra calculator showed that the calculator is a promising tool for predicting the temperature and pressure gradients over long length cooling branches. CMS-B-PIX Atlas-IBL Figures from: DESIGN CONSIDERATIONS OF LONG LENGTH EVAPORATIVE CO2 COOLING LINES Bart Verlaat and Joao Noite, GL-209, 10th IIF/IIR Gustav Lorentzen Conference on Natural Working Fluids, Delft, The Netherlands 2012

Cooling development philosophy Whatever the model give as a result: –Don’t trust them! the models are empirical. –Use them as a design guideline. Always verify in a test! –Not only to quantify heat transfer, but as well to filter out strange behavior 26

Strange start-up behavior in the Velo In the Velo the CO 2 does not always start boiling. It turned out that our bright idea of increasing the tube length wasn’t so brilliant after all. 27 Tube length At startup everything is liquid 1.The outlet starts to boil 2.The good boiling heat transfer is taking heat away from the inlet 3.As a result boiling at the inlet is suppressed. 4.Once boiling is achieved it will not go back to the liquid state Fluid temp. Tube wall temp. Temperature

Conclusions The common temperature boundaries of all parallel systems are: – The pressure (=saturation temperature) in the outlet manifold. –The temperature / enthalpy of the liquid in the inlet manifold. –Normally both temperatures are the same. Parallel channels need flow distribution by increasing the inlet pressure drop The in let manifold must be sub-cooled liquid. Overall performance of the thermal system includes: –Conductive path in detector structure –Heat transfer to the evaporative liquid –Pressure drop in evaporator and outlet tube. –Full thermal path must be considered in the design optimization Always verify your models with tests. 2-phase flow has sometimes strange behavior Avoid tube crosstalk, boiling in 1 channel can suppress boiling in the other 28 Things to keep in mind when designing CO 2 cooling loops: