1 CXS490 - Pre-Engineered Fire Protection Systems Kitchen Systems.

Slides:



Advertisements
Similar presentations
Fire Safety and Fire Extinguisher Use
Advertisements

Approved Commercial Cooking Systems and UL 300 Regulation
Approved Commercial Cooking Systems and UL 300 Regulation Garden Grove Fire Department Fire Prevention Bureau.
Regulations (Standards - 29 CFR) Flammable and Combustible liquids
Flammable and Combustible Liquid & Compressed Gas Handling and Storage
International Mechanical Codes Scald Protection. – Where a combination potable water-heating and space-heating system requires water for space.
Portable Extinguishers Firefighter I
Carbon Dioxide Systems 1.Carbon dioxide properties 2.Storage 3.Uses 4.Limitations 5.Types of systems 6.Local Application 7.Total Flood.
KURSUS PENGENALAN KEPADA PERKHIDMATAN MEKANIKAL DALAM BANGUNAN
Student Book © 2004 Propane Education & Research CouncilPage Placing Appliances into Initial Operation Knowing the proper techniques and.
RANGE GUARD / GAYLORD HOOD.
Texas Fire Marshals' Conference
NFPA 96 and Building Code Requirements for Commercial Kitchen Hood Systems Presentation for the Sevier County Fire Code and Building Code Officials Presented.
Fire Safety & Fire Extinguisher Use
COMPRESSED GASES. Compressed Gases Chemicals include oxygen, argon, nitrogen, helium, acetylene, hydrogen, nitrous oxide, carbon dioxide, ammonia, chlorine,
Portable Fire Extinguisher Safety Emergency Procedures.
© 2012 Copyright, Phil Ackland and Associates Understanding Commercial Kitchen System Fires Sponsored by the Calgary Fire Department May 28-29,
Enabling Wellbeing 1. Halton - Enabling Wellbeing Halton was established in 1969 Family owned company, operating in 23 countries. We are passionate about.
8/29/021 Commercial Kitchen Fire Safety. 2 Agenda Introduction Video and Discussion General Safety –Personnel –Appliances –Oils If Fire Occurs Fire Extinguishers.
Mechanical Plan Review. Review Plan Package Use Group/Occupancy Correct Code Reference/Conformance Revisions Mechanical Plans/Spec Books Structural Plans.
How would you explain this on the 3394? If Fire Erupts on YOUR Boat If Underway, stop the boat Have everyone who is not wearing a PFD put one on Position.
Evaluating Kitchen Hoods Rudy Hawkins C-1. Hood Designs and Categories - Background o Commercial Kitchen Hoods have two designs: o Exhaust Hoods o Grease.
Fire protection systems
Fire Detection and Suppression Chapter 7 Special Extinguishing Systems.
Local Application Total Flooding System: (NFPA 12) A system consisting of a supply of carbon dioxide arranged to discharge into, and fill to the proper.
Fire Prevention.
Chapter 12 Systems and Equipment for Fire Protection.
The Life Safety Surveyor Facility Tour
FIRE SAFETY TRAINING THE LOSS PREVENTION UNIT OF THE OFFICE OF RISK MANAGEMENT.
Atlantic Beach Fire Department Presents: For Business Employees and the General Public.
Spray Finishing Operations/Spray Booth March 9, 2009.
Means of Egress and Fire Protection. 2 Objectives Understand Alarms and Warning Devices Know the location of Exits and Exit Routes Understand the RACE.
HOT WORK PROCEDURES Welding and Hot Work, such as brazing or grinding present a significant opportunity for fire and injury. CCR Title 8 Sub Chapter 7,
Fire extinguisher Training. COURSE TITLE:FIRE EXTINGUISHER SAFETY AWARENESS Venue: Fire /Safety classroom – Fire training ground. Duration : 4 Hours Classroom.
Fire Safety & Fire Extinguisher Use. OBJECTIVES Understand the combustion process and different fire classes Understand fire extinguisher types, operating.
VENTING AND COMBUSTION AIR
Unit 8: Portable Fire Extinguishers & Smoke Control Management Systems
Kidde Engineered Fire Suppression System 25 bar Equipment Hardware Engineered for use with 3M™ Novec™ 1230 Fire Protection Fluid.
Business Owners and Managers and the Fire Code
Fire Detection and Suppression Chapter 1 Fire Extinguishing Agents and Portable Fire Extinguishers.
NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer.
NFPA 31 Standard for the installation of Oil- Burning Equipment
Safety Training Presentation
Air Conditioning International Mechanical Code
CHAPTER 12 Copyright © 2007 Thomson Delmar Learning 12.1 Protective Systems.
Unit 4: General Safety Practices
1 CXS490 - Pre-Engineered Fire Protection Systems Off-Road Vehicle Systems.
OSHA’s Most Frequently Cited Violations Hazard Communication 29 CFR (f)(5)(ii) states that all chemical containers must be labeled.
Fires need 3 Things To Start Oxygen (Air) Fuel (any material that will burn) Heat (sparks, matches, flames)
Unit 2: Fire Safety and Utility Controls
Spray Booths Follow safe operating instructions. Spray-finishing operations  Organic materials  Inorganic materials  Dispersed form  Deposited to.
Chapter 2.1 Introduction to Culinary Arts
Subpart F - Fire Protection & Prevention ( ) Flammables/combustibles - Approved containers Fire protection program/equipment 2A fire extinguishers.
ME444 ENGINEERING PIPING SYSTEM DESIGN
Presented by John Lewandowski and Mike Larabel Inspection, Testing, and Maintenance of Kitchen Hood Systems Michigan Fire Inspectors Society Winter Educational.
Fire Extinguishers Burlington Fire Department 215 S Church Street, Burlington, NC
Carbon Dioxide System Design
“Portable Fire Extinguishers Safety”
BASIC FIRE SAFETY.
AUTOMATIC SPRINKLERS.
NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations 2008 Edition 9/19/2018.
Flammable and Combustible Liquids
BASIC FIRE SAFETY.
Fire Safety & Fire Extinguisher Use
Fire Safety and Utility Controls
Spray Booths Follow safe operating instructions
BASIC FIRE SAFETY.
Presentation transcript:

1 CXS490 - Pre-Engineered Fire Protection Systems Kitchen Systems

(2) Cooking equipment designing to conform to Part Commercial cooking equipment provided will be designed,constructed and installed per NFPA 96 Check Applicable Edition (1) Also refers to Part 6 Ontario BC Requirements

(1) Cooking equipment provided with exhaust & Fire Protection System to NFPA (2) Existing exhaust & Fire Protection Systems may be Approved by the Chief Fire Official Maintained to NFPA 96 standards Commercial Exhaust Systems Ontario FC Requirements

(1) Instructions for operating the Fire Extinguishing System posted conspicuously in Kitchen area (2) Instructions included in the Fire Safety Plan Once installed suppression systems are to be maintained under this article Cooking area separated from rest of building 45 min or protected by fixed Fire Protection System Ontario FC Requirements

5 Hood Chapter 2 Grease removal device Chapter 3 Duct system Chapter 4 Fire System Chapter (a) The exhaust hood & filtration systems can be: -Dry -Water wash -Ion -Pollution control unit 5 NFPA 96 Requirements

6 Exhaust ducts may be: 16-gauge (no 18) carbon steel 20 or 18-gauge stainless steel Kitchen Hood capture heat, smoke and grease-laden vapours directs these into the exhaust ductwork to the building’s exterior and solidly connected to a listed & rated utility or up-blast exhaust fan. NFPA 96 Requirements

7 Ducts Seams, joints & penetrations – liquid tight or continuous welded exterior joints Clearance 457 mm (18 inches) to combustibles 152 mm (6 inches) to shaft interior 75 mm (3 inches) to limited/drywall 0 mm (0 inches) to non-combustibles Ducts & Clearance

8 Type I Grease producing cooking equipment Type II Non-grease laded; lighter weight,folded galvanized metal, or aluminum, or stainless steel Must project beyond cooking equipment 152 mm (6 inches) on both sides Hood

9 Devices in Hoods mechanical filter not allowed ≥ 457 mm (18 inches) from cooking surface ≥ 1219 mm (48 inches) to filters over fuel fired charcoal broilers Grease Removal

10 Listed Steel or equivalent rigidity Tight fitting – held in place Not less than 45º angle to horizontal Drip tray underneath filter rack to a grease cup Spark arrester prior to grease removal devices for solid fuel Grease Filters

11 Baffle Filter Impingement Modular Extractor Dry Cartridge Water Wash Hood Hot or Cold Water with a cleaning agent added Grease Removal Devices

12 Not connected to other vent or exhaust system Without dips or traps Openings provided at sides, top and changes in direction 508 mm x 508 mm (20” x 20”) opening for personnel entry or opening to allow for cleaning every 3.66 m (12 ft) (per ) Welded 16 gauge carbon steel or 18 gauge stainless steel Note: There is 5 to 10 times more grease in horizontal ducts and elbows! 12 Duct Systems

13 Access panels on the exterior of the building located at the top of the vertical riser Ducts not supported by roof or exhaust hood Horizontal ducts to slope to canopy No drip pockets Properly fastened to top of steel joists Hangers equal or heavier gauge Hoods hung separate from exhaust ducts Duct to fan – flexible connector not permitted Duct Systems

14 Fans Rated for commercial cooking vapours Up Blast or BIRM (Backward Incline Restaurant Model) Cooking equipment Fat Fryers ≥ 406 mm (16”) from surface flames of adjacent equipment ( ) Allows steel or tempered glass baffle ≥ 203 mm (8”) high to reduce clearance ( ) Fan & Cooking Equipment

15 Every six months Trained and qualified Proper operation of all actuator components Fusible links replaced annually, or more frequently Date of Fusible links on inspection report Temperature and Location on Inspection report Inspection & Service

16 Nozzles Properly aimed Capped and Clean Clear of grease and oil Manual Pulls 1.5 m or less to centre of the pull ring Nozzles& Manual Pulls

17 Fuel Shutoff Automatically activated by extinguishing system Turns off all sources of fuel or electrical appliances Manually reset or electrically through reset relay box Filters Cleaned weekly by the owner or changed by a cleaning company Nozzles& Manual Pulls

18 Operation of the extinguishing system must operate the F/A when provided or required due to occupancy type Electrical power operating extinguishing system supervised ( ) Fire Alarm Connection

19 showing date of cleaning on premises Areas not cleaned noted on the report for the AHJ Vent Cleaning Service

20 Solid fuel cooking – monthly High volume – quarterly 24 hours operation, charbroiling or wok Moderate volume – semi-annually Low volume – annually Church, day camp, seasonal or seniors centre Inspections

21 Appliances functional & maintained in order Proper nozzles & properly aimed Nozzles capped & clean Detector/Link line clear or clean of grease or carbon EMT clear of grease Check link manufacturer, rating & date stamp Hood penetrations properly sealed Gas valve accessible & not located under hazard Check cylinder assembly for corrosion & leakage Check Pull Station height & located in egress path General Inspections

22 Wet Chemical or alkali based dry chemical portable extinguisher provided to protect commercial cooking equipment ( ) Must comply with NFPA m maximum distance in the egress path Warning sign: ACTIVATE THE FIRE SUPPRESSION SYSTEM FIRST Extinguisher

23 ULC/ORD c/UL 300 Water 6 ½ min Wet Chemical cannot meet 20 minute re-flash requirement Dry Chemical Carbon Dioxide Existing may be acceptable Approved by the Chief Fire Official (CFO) Upgrade if changes to cooking equipment High efficiency better insulated 5 times more chemical required Extinguishing Media

24 Each nozzle has a flow number describes the flow capacity also determines number of cylinders required System Flows

25 1W up to perimeter of 687 mm (27”) up to diameter of 216 mm (8 ½”) at widest point Used with 5.68 to L (1.5 to 3 Gallon) systems 2W up to perimeter of 1905 mm (75”) up to diameter of 610 mm (24”) at widest point 2WH up to perimeter of 1905 mm (75”) up to diameter of 610 mm (24”) at widest point System Flows

26 Nozzle aimed into duct 51 to 108 mm into duct (2 – 8”) Locate nozzle at intersection of diagonals If duct between 1905 to 3810 mm (75 – 150”) perimeter, divide duct into two If more divide by 1905 (75”) Duct Nozzles

27 25 to 508 mm (1 - 20”) above the top of filter or 108 to 160 mm (8-12”) from the face of filter and within 51 mm (2”) of the centre-line One nozzle can protect up to 2.44 m (8’) as long as the filter width does not exceed 508 mm (20”) Filter Nozzles

28 Nozzles rating cannot exceed the longest side or the maximum area With deep fat fryers nozzle height ranges established Appliance Nozzles

29 Each cylinder has established number of flows points 1.5 gallon is six (6) flow and 3 gallon is eleven (11) flows Cylinder Flows

30 3/8” pipe Supply line Max 12.2 m (40’) Maximum rise 1.8 m (6’) Maximum elbows 9 Maximum Tees 1 Maximum Flows 5 Duct line Max 1.8 m (6’) Maximum rise 1.22 m (4’) Maximum elbows 4 Maximum Tees 1 Maximum Flows 2 Example 1.5 Gallon - 6 Flow Points

31 Plenum line Max 1.22 m (4’) Maximum rise 0.61 m (2’) Maximum elbows 4 Maximum Tees 1 Maximum Flows 2 Appliance line Max 3.05 m (10’) Maximum rise 0.61 m (2’) Maximum elbows 6 Maximum Tees 3 Maximum Flows 3 Example 1.5 Gallon - 6 Flow Points

32 Diagram - Flows