NFPA 96 and Building Code Requirements for Commercial Kitchen Hood Systems Presentation for the Sevier County Fire Code and Building Code Officials Presented.

Slides:



Advertisements
Similar presentations
Approved Commercial Cooking Systems and UL 300 Regulation
Advertisements

Approved Commercial Cooking Systems and UL 300 Regulation Garden Grove Fire Department Fire Prevention Bureau.
UNIVERSITY of NORTHERN COLORADO HOT WORK PROGRAM.
WAYNE DALTON OF SYRACUSE PRESENTS:
International Building Code
Regulations (Standards - 29 CFR) Flammable and Combustible liquids
Initiating Devices Manual Fire Alarm Boxes Ionization Smoke Detectors
Fired And Unfired Pressure Vessels
International Mechanical Codes Scald Protection. – Where a combination potable water-heating and space-heating system requires water for space.
FIRE DOOR INSPECTIONS NFPA 80 STANDARDS THIS STANDARD REGULATES THE INSTALLATION AND MAINTENANCE OF ASSEMBLIES AND DEVICES USED TO PROTECT OPENINGS IN.
Chapter 8: Duct Design and Sealing To be used with the Guide to Building Energy Efficient Homes in Kentucky.
“Do not take anyone’s advice as to how this building should be assembled.”
Saving Lives and Property Through Fire and Smoke Containment ©2004 IFC Flexible Fire Resistive Duct Enclosures.
Enabling Wellbeing 1. Halton - Enabling Wellbeing Halton was established in 1969 Family owned company, operating in 23 countries. We are passionate about.
1 CXS490 - Pre-Engineered Fire Protection Systems Kitchen Systems.
Mechanical Plan Review. Review Plan Package Use Group/Occupancy Correct Code Reference/Conformance Revisions Mechanical Plans/Spec Books Structural Plans.
Evaluating Kitchen Hoods Rudy Hawkins C-1. Hood Designs and Categories - Background o Commercial Kitchen Hoods have two designs: o Exhaust Hoods o Grease.
Fire protection systems
Code changes to 2009 Michigan Mechanical Code
Engineering Controls and Laboratory Design Session 4 Laboratory Safety Training.
PERMITS & INSPECTIONS DEPARTMENT 2003 INTERNATIONAL RESIDENTIAL CODE IRC.
© Siemens Industry, Inc Confidential / Drive Your Business Forward Ignite the Power of New Products and Partnerships Siemens Fire Partner Summit.
Fire Detection and Suppression Chapter 7 Special Extinguishing Systems.
N.F.P.A. 13R Justin Bohlmann FIR-204.
SAFETY TALK - SLIDE 1 OF 14 Elkhart Products Corporation 08/00 WELCOME ELKHART PRODUCTS CORPORATION “TOOLBOX SAFETY TALK” Welding, Cutting, & Burning.
Welding, Cutting, & Burning. GENERAL HAZARDS General hazards of welding include: –Impact –Penetration –Harmful dust –Smoke –Fumes –Heat –Light radiation.
The Life Safety Surveyor Facility Tour
2007-CBC - UL Damper Requirements
Spray Finishing Operations/Spray Booth March 9, 2009.
HOT WORK PROCEDURES Welding and Hot Work, such as brazing or grinding present a significant opportunity for fire and injury. CCR Title 8 Sub Chapter 7,
2012 International Fire Code Adopted as the minimum fire safety standard by the State of Wyoming City of Sheridan must adopt the minimum standard to retain.
Chapter 4: Air Leakage Control: Materials and Techniques
Child Care Fire Safety Program North Carolina Fire Prevention Code 2000 International Fire Code with NC amendments. North Carolina Building Code Council.
VENTING AND COMBUSTION AIR
Industrial Acoustic Sound Enclosures FanAir Company designs and builds Acoustic Sound Enclosures Engineered to each specific application to control noise.
Unit 8: Portable Fire Extinguishers & Smoke Control Management Systems
Business Owners and Managers and the Fire Code
Stafford County Public Schools Safety Program
PERFORMANCE & CODE ANALYSIS TIMBer Inc. ·Brooke Fedder · Marie Rottschaeffer· Izzie Molinuevo· Tena Pettit·
AIR QUANTITY REQUIRED TO TRANSFER HEAT IN A FORCED AIR SYSTEM In all four mechanical systems considered, the transfer of heat, either by taking it out.
NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer.
HVACR311 – Electrical for Refrigeration International Mechanical Code Relating to Refrigeration.
NFPA 31 Standard for the installation of Oil- Burning Equipment
International Fire Door Inspector Association Presents New Annual Fire Door Inspections NFPA 80 – 2007, 2010, 2013 Standard for Fire Doors and Other Opening.
Air Conditioning International Mechanical Code
Fire Safety By Alicia Civile and Alexandra Fernandez.
1 HVACR318 – Refrigeration II International Mechanical Code Relating to Refrigeration.
Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Firestopping – Filling the Gaps Makes a Difference Poole Fire Protection Brian Griffin & Jack Poole, PE 2007 DOE Contractor Fire Protection Workshop Argonne.
2 IMPACT - THE FIRE PERMIT = Hot Work Permit 3 Welcome ! This course is linked to the use of IMPACT, so it is assumed that: You know how to use IMPACT.
Chapter 5 ID 234 Building Codes Fire Resistant Materials and Assemblies.
Fire-Resistant Materials & Assemblies Part 2 Chapter 5.
Spray Booths Follow safe operating instructions. Spray-finishing operations  Organic materials  Inorganic materials  Dispersed form  Deposited to.
Maine State Fire Marshals Office1 Laws and Codes Relating to Existing Apartment occupancies in the State of Maine Mark Stevens CFI-II, CFPS, CFPE Inspections.
Work Area Method Level 3 Alterations – Chapter 9 prescribes requirements. 50% of Building Area Rule.
Chimney Fires Lieutenant LeGrotte Sugar Land Fire Department.
Goals of a Fire Prevention Program Fire Prevention Strategy Housekeeping Issues Flammable and Combustible Liquids Electrical Fire Hazards Compartmentalization.
Hot /Cold Aisle Containment  Traditional Data Center/Telco designs are changing significantly!
Presented by John Lewandowski and Mike Larabel Inspection, Testing, and Maintenance of Kitchen Hood Systems Michigan Fire Inspectors Society Winter Educational.
Zone 4 R-38 Ceilings U-0.35 Windows, Doors R-13 Walls R-19 Floors R-10 Foundations.
Day 2 Part 1 Technician’s Guide & Workbook for Home Evaluation and Performance Improvement.
Exercise #2 (part 2) Based on what you read in Chapter 4, determine if the corridors and exit doors meet the requirements for egress width, according to.
Flammable Liquids Directorate of Training and Education
Cross Connection Survey Training
Fire Alarm Systems for Emergency Operations of Elevators
NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations 2008 Edition 9/19/2018.
Spray Booths Follow safe operating instructions
National Fire Protection Association Update
Presentation transcript:

NFPA 96 and Building Code Requirements for Commercial Kitchen Hood Systems Presentation for the Sevier County Fire Code and Building Code Officials Presented by Roger Griffith, PE Griffith Engineering, Jefferson City, TN April 21, 2004

Course Outline Problem Areas Code Changes General Requirements Hoods Exhaust Ducts Fans Fire Suppression System Code Changes NFPA 96 International Mechanical Code (IMC)

GENERAL REQUIREMENTS Where are commercial hoods required? NFPA 96: “Cooking equipment used in processes producing smoke and grease-laden vapors shall be equipped with… NFPA 96 – A-1-1 “…intended to include residential cooking equipment where used for purposes other than residential family use…” SMC gives exceptions for domestic equipment installed in dwelling units and ovens do not heat food above 2120F.

Clearances 18 inches to combustible material 3 inches to limited-combustible material 0 inches to noncombustible material

Exceptions When the hood is listed for lesser clearances If the combustible material is protected as follows: 28 gage sheet metal spaced out 1 inch on noncombustible spacers – 9 inch clearance to combustible material 22 gage sheet metal on 1 inch mineral wool bats or ceramic fiber blanket reinforced with wire mesh or equivalent spaced out 1 inch on noncombustible spacers – 3 inch clearance to combustible material Reduced clearance to limited-combustible materials to zero clearance where protected by noncombustible materials or materials listed for the purpose of reducing clearance, and acceptable to the AHJ.

9 inch clearance reduction

3 inch clearance reduction

Clearances

Clearances

Duct Clearances Protection methods for ducts to reduce clearances shall be applied to the combustible or limited-combustible construction, not to the duct itself. Exception: Field applied grease duct enclosures and factory-built grease duct enclosures

Field Applied Protection

Duct Enclosures Field applied grease duct enclosure: A listed system evaluated for reduced clearances and as an alternative to a duct with its fire-rated enclosure. Factory-built grease duct enclosure: A listed factory–built grease duct enclosure system evaluated for reduced clearances to combustibles and as an alternative to a duct with its fire-rated enclosure.

EXHAUST HOODS Type 1: Hoods designed for grease exhaust applications Type 2: Hoods designed for heat and steam removal and other nongrease applications. (NFPA 96 does not cover) NFPA 96: 2-1, 1998 Edition

Exhaust Hoods Hoods shall be constructed of 18 gage steel or 20 gage stainless. All seams, joints, and penetrations of the hood enclosure that direct and capture grease-laden vapors and exhaust gases shall have a liquidtight continuous weld external weld.

Hood Integrity

Exhaust Hood Hoods must be sized and configured to provide for the capture and removal of grease-laden vapors. Size: Configuration: Backshelf/Proximity Hoods Short-Circuit Hoods Face Discharge Makeup Hoods Exhaust Only Hoods w/Supply Plenums NFPA 96: 2-2, 1998 Edition

Short Circuit Hoods Hood performance is principally dependent upon net exhaust. Net exhaust = Total exhaust – internal makeup Large airflows are required – high first cost & operating cost.

Backshelf Hood

Face Discharge Makeup Hood Originally designed for non-air-conditioned kitchens Makeup air becomes load to kitchen HVAC

Exhaust Only Hood Cross Section

Exhaust Only Hood w/Supply Plenum

Hood w/Supply Plenums

Fire Dampers at Hoods Fire dampers are installed in supply air connections where they penetrate the hood. Fire dampers are not installed in exhaust ducts. Fire dampers are not required in supply plenums that are isolated from the continuously welded shell.

Filters and Baffles They are required! They must be 18 inches from cooking surface. (Hoods above char-broilers must be 4 ft above the cooking surface). Filters must be installed at an angle of not less than 45 degrees Filters must be easily accessible and removable for cleaning. NFPA 96: Ch.3, 1998 Edition

EXHAUST DUCTS Ducts can not pass through fire walls or fire partitions. Ducts cannot have dips or traps. Clearances must be maintained. Ducts must be 16 gage steel or 18 gage stainless. Seams and joints shall have liquid tight external welds.

Openings in Exhaust Ducts Location At changes of direction For damper cleaning and inspection At both sides of inline fans Construction On horizontal ducts – 20”x20”; if size is not possible, provide openings large enough for cleaning every 12 feet. Access openings shall be of the same material and thickness as the duct. Access panels shall have a gasket or sealant that is rated for 15000F and shall be grease tight. Enclosure openings are required to reach access panels. They shall be protected by approved self-closing fire doors. NFPA 96: 4-3, 1998 Edition

Exhaust Ducts – Exterior Fasteners cannot penetrate duct walls. Ducts must be painted or be constructed of stainless steel.

Exhaust Ducts – Interior Enclosures must be provided for buildings more than one story, and when penetrating a rated floor /ceiling assembly. Enclosure shall be sealed around the duct at the bottom. Exception: Field applied or factory applied grease duct enclosures. NFPA 96: 4-7, 1998 Edition

Clearances at Enclosures 18” to combustible construction 6” to noncombustible or limited-combustible construction Clearances may be reduced with field applied or factory applied grease duct enclosures. Multiple ducts are not permitted in a single enclosure (SMC only requires 6” clearance)

Rooftop Terminations Maintain 10 feet clearance to adjacent buildings, property lines, and air intakes, or locate exhaust 3 feet above air intakes. Ductwork must extend 18 “ above roof.

Fans Fans must be listed for commercial cooking equipment. Rooftop Fans Rooftop fans must be hinged. Exhaust outlet must be 40 inches above roof. Termination must have a grease trap. Safe access must be provided to the fan for inspection and cleaning

Fans Wall Termination Fans Wall must be noncombustible Maintain a minimum of 10 feet clearance from outlet to adjacent buildings, property lines, grade level, combustible construction, electrical equipment, air intakes or operable windows. Air intakes or operable windows above exhaust shall be 10 feet plus 0.25 feet for each 1 degree from horizontal.

Airflow Air flow has traditionally been 1500 ft/min minimum. This is changing with the newer codes. Air volumes should be of sufficient level to capture and remove grease-laden cooking vapors. Makeup air shall prevent negative pressures from exceeding 0.02” wc in the cooking area.

Fire Suppression Systems Automatic fire extinguishing systems must be in accordance with NFPA 12 - CO2 NFPA 13 – Wet NFPA 17 – Dry Chemical NFPA 17A – Wet Chemical

Ansul System

Pyrochem System

Fire Suppression Systems Exhaust fans must continue to operate after the extinguishing system has been activated. Fans do not have to be started upon activation of the extinguishing system. Makeup air supplied internally to the hood must be shut off when fire suppression system activates. All sources of fuel and electric power that produce heat to all equipment requiring protection by that system shall automatically shut off upon activation of any extinguishing system.

Fire Suppression Systems A means of manual activation must be provided in the path of egress. (SMC requires it to be from 10-20 feet of hood.) An audible alarm or visible indicator shall be provided. If fire alarm system is installed in building, it shall be activated. If electric power is required to operate the fire suppression system, it shall have a backup power supply or all sources of fuel shall automatically shut off when the system is inoperable. Portable fire extinguishers

Fire Suppression System Inspection and Servicing Systems are required to be inspected every 6 months by properly trained and qualified persons. All devices, actuators, detectors, and components shall be checked for proper operation. Fusible links and automatic sprinkler heads shall be replaced at least annually, or more frequently. If required, certificates of inspection and maintenance shall be forwarded to the AHJ.

Cleaning and Inspection The entire system shall be inspected by properly trained and certified personnel. Quarterly – high volume operations (24 hour, charbroiling) Semi-annually – moderate volume Annually – low-volume (churches) During inspection if the system is found to be contaminated with grease, the entire system shall be cleaned by properly trained and certified personnel.

Cleaning and Inspection Hoods, ducts, fans, etc. shall be cleaned as needed to prevent them from becoming heavily contaminated with grease.

Code Updates NFPA 96 International Mechanical Code

Revisions to NFPA 96 Minimum Air Velocity through a grease duct 1,500 ft/min (1998 edition) 1,200 ft/min (2001 edition) 500 ft/min (Errata 96-01-01 to 2001 edition in January 2002 -1,500 ft/min has been in the codes since the 1930s (may have come from velocity of air in coal-burning furnaces) -Number was reduced because of ASHRAE Research Project 1033-RP Advantages of lower fan speeds: -lower grease accumulation, less duct cleaning -easier to retrofit -reduced noise -energy savings (less makeup air)

NFPA 96 – 2001 Protection shall be provided on the wall down to the floor or to noncombustible material. Horizontal duct support systems shall be designed for weight of duct plus 800 lbs. at any point. Penetrations to ducts and hoods shall be listed.

NFPA 96 – 2001 A minimum of 5 feet horizontal clearance from fan to combustible material.

NFPA 2004 under review Chapter 15, Down Draft Appliance Ventilation Systems A new section requiring a 20” x 20” opening for personal entry for duct cleaning A requirement for factory-built duct enclosures and duct-wrapped grease duct systems to be listed in accordance with UL 2221, “Tests of Fire Resistive Duct Enclosure Assemblies.”

International Mechanical Code Performance Test Net Exhaust 2003 Code Capture and Containment Test

Capture and Containment Test Adjust and verify all exhaust and makeup airflows. Operate equipment at cooking conditions Verify capture and containment with smoke puffers Verify pressurization, and adjust if necessary Building positive to outdoors, kitchen negative to dining

Capture and Containment Test