Understanding Masterpact NT & NW

Slides:



Advertisements
Similar presentations
Understanding Micrologic
Advertisements

Molded Case Circuit Breakers for the OEM Market
1 Series V4T 1/4 DIN Temperature Controllers. 2 3 Watlows Next Generation Styling Series 97 Matching 1/16 DIN Limit Controller Series F4S and F4D Ramping.
L.T Circuit Breakers.
Prescient II Extinguishing Control Panels
Automation and Drives SIRIUS SC Solidstate Switching DevicesA&D CD CC PM4, Jan. 21, Gliederungspunkt 10 Gliederungspunkt 1 Gliederungspunkt 2 Gliederungspunkt.
Seminar on Circuit Breaker
SWITCHGEAR BIG GRAY BOXES SWITCHBOARD
Fraction Revision.
How fractions, decimals and percentages work together.
SITOP power Automation and Drives SITOP modular The First Modular Power Supply SITOP - a step ahead.
Trystar Generator Docking Stations & Portable Power Cable
“KB” - “KM” SERIES LIMIT SWITCHES
Automatic Transfer System ATyS
CL100D series DSP controlled Uninterruptible power supplies.

Smart heat for comfort and safety 1 Self-regulating system to maintain water flow in gutters and downpipes.
Siemens listened to your needs and is proud to introduce the... Sentron Mining Duty Circuit Breaker Family s.
Industrial Controls: Surion
Electrical Installation
Gdpack 40.5kV Technical Data Sheet MV-LV Prefabricated Substation
SITOP power facets A&D SE PS SITOP power Automation and Drives SITOP power flexi The power pack handles it all - from 3 to 52V SITOP power.
Movitrac LTP A General purpose frequency inverter.
Inspection & Preventive maintenance of breakers
We thought it was a GOOD IDEA, so we did it! We were the first to have quick make-quick break operators on bolted pressure contact switches.
MIFII DIGITAL FEEDER PROTECTION A Cost Effective Protection Solution for Overcurrent Protection at Any Voltage Level GE Multilin
M iniature circuit breakers to UL 489
HYDRAULICS & PNEUMATICS
© Copyright year ABB. All rights reserved /1/2015 VBF OUTDOOR VACUUM CIRCUIT BREAKER 36kV PRODUCT INFORMATION.
Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Insert Photo Here OneGear™ 7.2kV Motor Control Center.
©2011, The McGraw-Hill Companies, Inc. Chapter 4.
ACADs (08-006) Covered Keywords Switchgear, motor control, ground, circuit breaker. Description Supporting Material
MAIN ELECTRICAL SURVEY ITEMS, GENERATORS AND GOVERNORS,, CIRCUIT BREAKERS, SWITCHBOARDS AND FITTINGS (Adapted from:D.T. Hall:Practical Marine Electrical.
Graphic Symbol Location 1. DIN Terminal X52 The machine is powered by electricity using copper cable with 5 wires (3 phase wires + neutral wire +
Schutzvermerk / Copyright-Vermerk SION Vacuum Circuit-Breaker For Standard Applications Siemens Medium Voltage Sector Energy, Business Unit Medium Voltage.
FIPTMV Medium Voltage Technology
December, 2010 Vmax – Indoor vacuum circuit-breakers for Primary Distribution Product presentation 1VCP – Rev. D, en – Presentation –
Slide 1 / 35 P&T - GPS - Training PhB - 01_TECH_TeSys_U_controller_ en 06/2004 Presentation of the range Composition of the controller  Control base 
VHA PANEL WITH HPA12 CIRCUIT BREAKER
SF6 load-break switch-disconnector
Miniature Circuit Breakers (MCB) Multi 9
Sales Training Outline 2006 Klaus Tum Product Manager NEW Circuit Breakers 35 Royal Road Flemington, NJ
MV SF6 circuit-breakers for secondary distribution
Multi-function apparatus for secondary distribution
Masterpact LV power air circuit breakers and switch disconnectors
Electro-Pneumatics Module 1
Confidential / Property of Danfoss Drives A/S DKDD-SMC 1 Drives Division Danfoss presents - VLT ® 2800 Series.
Vadodara institute of engineering,kotambi NAME:NAFISKHANPATHAN(13ELEE181) BARIYA VIPUL(13ELEE182) PATEL AMIT(13ELEE180) BRANCH:EE-2 PPT OF EEE.
MKT May 2012 C850: Fast sliding gate operator. MKT May 2012 Summary  Why a fast slider operator?  USPs  Applications  Details  Technical specifications.
Main contacts closed – RED Colour with ON
5SL4 10 kA / 5SL6 6 kA miniature circuit breakers
SYNERGY INSTITUTE OF ENGINEERING AND TECHNOLOGY
1 Comparison of 100-B and 100-D Contactors B Contactors.
Sub Station.
3AH5 Vacuum Circuit-Breaker For Standard Applications
DESCRIPTION AND GUIDE TO OPERATIONS
PRESENTATION ON SUMMER TRAINING PROGRAM
Circuit Breakers & Reclosers
Overview of PowerCube Units and ANSI frames
MV vacuum circuit-breakers for secondary distribution
3AH5 Vacuum Circuit-Breaker For Standard Applications
Direct Replacement Retrofitting Solution
SION Vacuum Circuit-Breaker For Standard Applications
ELECTRICAL POWER-II Electrical engineering sixth semester
Direct Replacement Retrofitting Solution
3AH5 Vacuum Circuit-Breaker For Standard Applications
CIRCUIT BREAKERS E. Chikuni. Circuit Breakers Mechanical Switches capable of making and breaking currents under normal circuit conditions and for a specified.
Its strengths, your benefits
Its strengths, your benefits
Presentation transcript:

Understanding Masterpact NT & NW 1

Auxiliaries and accessories Drawout installation Fixed Installation NW breaker frame Micrologic socket Auxiliaries and accessories Drawout installation Fixed Installation Range and performances 2

Contents NW breaker frame Case Moving contact Current transformers Power supply Fixed contact Assembly Arc chamber Opening of contacts Return to contents

Case Supports the opening /closing mechanism stored energy mechanism (OCO sequence ) Insulated organic polymer material Fire proof No halogen

Moving contact Complete assembly fingers, braids, terminal no internal bolted joint High electromechanical and thermal withstand blow on Specific limiter contact assembly L1 performance Direct link to the OCO mechanism Isolated compartments

Current transformers Combined technology air core for measurement (Rogowsky) measurement precision 1% linearity from 40A to 400kA self powered iron core for trip unit power Integral connector automatically connected One CT per pole Mounted on bottom side of moving contact

Micrologic trip unit power supply Circuit breaker Micrologic Communication module COM Module ASIC Microprocesseur Additionals functions (measurement, analyses...) Basic protection Optical coupling Air CT Isolation Power supply Trip unit power supply Iron CT Optional external 24V DC power supply for : programmable contact power supply, when breaker is open : Powers display, Identification, adjustments through “Com” module BUS power supply Standard Internal voltage sensor or optional external voltage sensor for µP power supply and measurement

Fixed Contact Breaking the arc arcing contact protects main contacts against wear high number of electrical operation increased life expectation Top terminal no internal joint

Assembly Reliability reduced number of components simple concept compact modular Three cases (3x3P & 3x4P) NT06 - 16 NW 08 - 40 NW 40b - 63

Arc chamber Increased arc impedance favors extinguishing properties patented metallic filter high porosity energy and gas absorption results in de-ionization of external gas Reduced external projections Reduced enclosure pressure Safety clearance above arc chamber NW : not required NT : D/O no, Fixed reduced Removable for contact inspection NT NW

Opening of contacts Commutation principle Contact pads protected from the electric arc for better performance Return to contents

Contents Micrologic socket Mitop trip solenoid Making current release (DINF) NW Interface Trip alarm contact Remote reset 2 contacts module Communication module Return to contents

Mitop trip solenoid Transforms the trip command into a mechanical operation to open the breaker Activate the alarm contact (SDE) NW

Making current release (DINF) Self protection of the breaker when closing on very high fault current Standard on all NT and NW breakers NW

NW Interface NW Accessory fixture Trip alarm contact SDE 1 communication module Auto trip controller : Missing trip unit security feature identical on NT NW

Alarm trip contact SDE Trip signalisation on electrical fault (Mitop command) Standard changeover contact 10A 240V on all NT and NW breakers Optional : second alarm trip contact SDE 2 standard or low level NT NW

Remote reset NT NW Remote reset of a tripped breaker automatic reset of the mechanical indicator 2 voltages : 110 / 130 V AC 200 / 240 V AC Exclusive with the second SDE NT NW

2 contacts module M2C programmable contacts : to energize bell or visual alarms to shed and reconnect non priority circuits … 2 closing contacts 10 A 240V AC Monitored by Micrologic P et H M6C : 6 programmable contacts in external DIN case NT NW

Communication module NT Independent modules Breaker module data transmission threshold adjustment breaker status breaker monitoring breaker identification wave form capture readings of histories & logs Chassis module transmission of « connected, test, disconnected » positions NT Return to contents

Contents Auxiliaries and accessories Electrical operating mechanism Voltage releases Auxiliaries connection block support « OF » auxiliary switches « Ready to close » contact Locking accessories and BPFE Control unit Operation counter Front cover Return to contents

Electrical operating mechanism MCH Charges and automatically recharges the stored-energy spring upon breaker closing AC 50 / 60 Hz 100V to 480V CA 7 references DC 24V to 250V 4 references Charging time : 4 s maxi Easy installation : 1 screw Local and remote signalisation of « spring charged » mechanical indicator «charged» Changeover contact 10A 240V NT NW

Voltage releases Closing (XF) & opening (MX) coils AC 50/ 60 Hz from 12V to 525V 8 references Com compatible 12 to 480V DC from 24V to 250 V 4 references Security opening coils MN and MNR from 24 to 525V 7 references 5 references NT NW

NW Auxiliaries connection block support Allows the fixation of auxiliary connectors MN or MX2 MX1 XF PF MCH Supports the « OF » changeover switch block NW

OF auxiliary switches NT NW NW standard : block of 4 OF contacts optional :2 additional blocks changeover contact 10A 480V low level compatible simplified mounting : 2 screws rotative contacts directly operated by mechanism NT standard :4 OF contacts identical to Compact NS changeover switch 6A 480V optional : low level contact 5A 480V clip on type NT NW

Ready to close contact PF Changeover contact 10A 240V Indicates : the breaker is open the stored energy mechanism is charged the mechanism is correctly reset the breaker opening push button is not locked no opening order is present NT

Installation of Micrologic socket Left side The socket supports communication module Micrologic control unit NW

« open » position breaker locking NW key locking :1 or 2 locks padlocking : up to 3 padlocks electrical closing pushbutton (BPFE) available on support NT key locking :1lock Locks Ronis, Profalux, Castel NT NW

Micrologic control units 4 protection levels LI, LSI, LSIG, LSIV Combined with 3 measurement levels A : current P : A + voltage + power + energy H : P + energy quality management (harmonics) Available functions monitoring and protection measure network monitoring maintenance help

Micrologic control units Common to all NT and NW breakers CT rating / performance socket breaker rating breaking capacity (N1, H1, H2, H3, L1) Circuit breaker is maintained in open position when control unit is missing Interchangeable on site NT NW

secondary wiring support control unit and « com » module NW Communication ZSI External neutral Earth leakage protection (vigi) Control unit external 24V voltage supply External voltage (phases and neutral) Programmable contacts M2C or M6C NT identical except external voltage exclusive with M2C/M6C NT NW

Operation counter Sums the number of operating cycles (closing /opening) maintenance help Easy installation Visible on the front panel NW

Front cover Front cover installed provides double insulation IP 20 : finger safe Attractive design NT NW Return to contents

Contents Drawout installation Drawout accessories Chassis Auxiliaries terminals Extracting the rail Racking sequence Primary connectors Return to contents

Masterpact NT Lateral side panels Supports breaker on rails Carrying handles Easy installation with 4 screws NT

Drawout connectors Connection between beaker and chassis Connectors Vertically oriented for optimal heat dissipation NT NW Return to contents

Chassis Back mold Clusters Shutters Positions Secondary terminals Breaker installation

Back mold NW Support interface primary clusters customer bus connection point Location of the shutters NW

Chassis assembly Arc chute cover installed as standard 2 sizes of chassis 800 A - 4000 A 4000 A - 6300 A 2 variants 3P 4P NT NW

Clusters One fits all ! Vertical orientation for better heat dissipation 10 fingers on each cluster across the entire range Clip on type Number of clusters depends on breaker frame size NT NW

Shutters actuator NW Reversible upper and lower Quick installation Controlled by rear of breaker NW

Safety shutter installation Safety shutters « up » and « down » identical but independent Shutter locking NW in front of the chassis on the primary stabs NT on the primary stabs only NT NW

Chassis position contacts Connected - test - disconnected NW 3 changeover contacts 10A 240V for each position activated by actuators Possible to replace the test and disconnected actuator by the connected actuator to get 9 CE contacts NT 3 CE, 2 CD, 1 CT Combined «connected/closed » contacts (EF) NT NW

Auxiliaries terminals 2 wires from 0,75 to 2,5mm² Predefined position Simple identification Quick connection Easy installation NT NW

Auxiliaries cover Protection of auxiliary wires Easy identification by tampoprinting Quick mounting with 2 screws NT NW Return to contents

Extracting the rails and installing the breaker Interlock must be defeated before removing breaker Provides guide for breaker Breaker slides in manually to disconnected position NT NW Return to contents

Racking sequence with crank handle Safety Automatically opens breaker before connecting or disconnecting mechanical stop in all positions Push button for releasing each mechanical stop NT NW Return to contents

Primary connectors Connector options Rear connectors Mixed connectors Front connectors Return to contents

NW connector options NW Rear connectors NW 08- 32 & NW40b- 50 Al (800 - 2000) Cu (2500 - 5000) vertical or horizontal NW 40 & NW 63 specific rear connectors Front connectors Al (800 - 1600) Cu (2000 - 3200) thickness : 20 mm for all connectors identical top and bottom connector NW

NT connector options NT Rear connectors NT 06 - 16 copper 15 mm identical for fixed and drawout Front connectors long connector on top short connector on bottom side Options for front or rear connectors Spreaders pole pitch 95 mm edgewise terminal extension additional connectors ( eg: for cripmled lugs) NT

Primary connection Vertical / horizontal rear Connectors matched to breaker size NT 06 - 16 NW 08 - 32 NW 40b - 63 pole pitch :70, 115, 230 mm Specific rear connectors for NW40 Pole pitch : 150 mm horizontal 115 mm vertical identical for fixed and drawout NT NW

Primary connection mixed Without modification of the breaker depth, the primary connectors may be rotated Mixed connectors Coupling torque on the breaker 16mN busbars to primaries 50mN NT NW

Front connection NW NT Draw out breaker top side : long connectors bottom side : short connectors spreaders option pole pitch : 95 mm NW Front connection limited to 3200 A identical top and bottom connectors NW Return to contents

Fixed installation Support bracket Vertical or horizontal mounting up to 4000A Secondary terminals 2 wires from 0,75 to 2,5mm² position predefined simplified identification quick connection simple installation Rotatable primary connectors same as draw out breaker NT NW

Fixed installation Front connection and accessories Identical top and bottom connectors thickness 12 mm Accessories Spreaders pole pitch 95 mm edgewise terminal extension additional connectors ( eg: for cripmled lugs) thickness 12 mm for all accessories adaptable on fixed or draw out NW top side: long connectors bottom side: short ones Return to contents

Contents Range and performances General characteristics NT 3/4P dimensions NW 3P dimensions NW 4P dimensions NT & NW performances IcU / Icw endurances Micrologic range Return to contents

General characteristics Insulation voltage : 1000V Impulse withstand voltage : 12kV rated voltage : 690V Specific versions Switch 1000V AC DC 400Hz - 16Hz 2/3 Transfer switches Manual, remote controlled Automatic by rods : 2 NT & 2NW by cables : 2NT, 1NT+1NW 2NW, 3NW

Masterpact NT 06 - 16 3P / 4P Overall dimensions height and depth fixed Weight fixed : 13 / 18 Kg draw out : 30 / 40 Kg Neutral Pole On left by default protection : 1/2, full, off F: 259 D: 322 3P F: 210 D: 288 4P F: 245 D: 358 F: 290 D: 277

Masterpact NW 08-40 & 40b-63 3P Overall dimensions Height and depth fixed double poles construction for Masterpact NW 40b-63 Weight fixed : NW 08 - 40: 60 Kg NW 40b - 63 : 120 Kg draw out : NW 08 - 40: 90 Kg NW 40b - 63 : 225 Kg pole pitch : 115 mm / 230 mm F: 352 D: 439 F: 422 D: 441 F: 297 D: 394 F: 352 D: 479 F: 297 D: 394 F: 774 D: 786

Masterpact NW 08-40 & 40b-63 4P Neutral pole on left as default protection : 1/2, full, off Overall dimensions Height and depth fixed double poles construction for Masterpact NW 40b-63 weight fixed NW 08 - 40: 80 Kg NW 40b - 63 : 160 Kg draw out : NW 08 - 40: 120 Kg NW 40b - 63 : 300 Kg F: 352 D: 439 F: 297 D: 394 F: 544 D: 556 F: 352 D: 479 F: 297 D: 394 F: 997 D: 1016

Masterpact NT Performances 220V to 440V Icw (0,5 s) L1 H1

Masterpact NW Performances 220V to 440V Icw (1s) L1 H3 H2 H1 N1

Performances NT & NW endurance Mechanical endurance : Electrical endurance : With maintenance Without maintenance Nbre de cycles (x1000) Without maintenance Nbre de cycle (x1000)

Current protection type Micrologic range Micrologic 2. 0 A Measurement type version Current protection type Current protection type 2 : Distribution L, I 5 : Selective L, S, I 6: Selective and ground fault L, S, I, G 7 : Selective and earth leakage L, S, I, V A P H 2.0 A 5.0 A 6.0 A 7.0 A 5.0 P 6.0 P 7.0 P 5.0 H 6.0 H 7.0 H Return to contents

Things will never be the same