Presentation is loading. Please wait.

Presentation is loading. Please wait.

5SL4 10 kA / 5SL6 6 kA miniature circuit breakers

Similar presentations


Presentation on theme: "5SL4 10 kA / 5SL6 6 kA miniature circuit breakers"— Presentation transcript:

1 5SL4 10 kA / 5SL6 6 kA miniature circuit breakers

2 Features 2 Swiching capacity, characteristics and voltages 10 Technical features 11 Tripping characertistics 12 Dimension - symbols 14 Bus mounting 15 Additional components 16 Selection and order number overview 17

3 Features Easy-to-read, colored switch position indicator integrated in the handle Actuators in gray Optimum reach-round touch protection Removal from the busbar network requires no tools Consistent busbar concept throughout the Siemens miniature circuit breaker range 5SL4 MCB series

4 Features 5SL6 MCB series 5SL4 MCB series Switching capacity of 6000 A
Easy and quick mounting of auxiliary switches and fault signal contacts Switching capacity of A Easy and quick mounting of auxiliary switches and fault signal contacts, AA, UA, RC unit, AFDD

5 5SL4 10 kA / 5SL6 6 kA miniature circuit breakers
Ergonomic handle Ergonomic handle and housing contours for user-friendly switching Comfortable manual releasing of the miniature circuit breaker from the busbar without tools

6 5SL4 10 kA / 5SL6 6 kA miniature circuit breakers
Optimum terminal version Rectangular terminal version for accommodating pin busbars with conductors from 0.75 to 35 mm² for easier insertion of conductors Optimum reach-round touch protection

7 5SL4 10 kA / 5SL6 6 kA miniature circuit breakers
Consistent busbar concept Consistent busbar concept throughout the Siemens miniature circuit breaker range Easily accessible and safe line connection and a larger wiring space

8 5SL4 10 kA / 5SL6 6 kA miniature circuit breakers
Removal requires no tools Replacement of a device from the busbar-mounted assembly requires no tools

9 5SL4 10 kA / 5SL6 6 kA miniature circuit breakers
Mounting of additional components 5SL miniature circuit breakers are suitable for the easy and quick mounting of auxiliary switches and fault signal contacts 5SL4: 5ST301… auxiliary switches (AS) 5ST302… fault signal contacts (FC) 5ST303… shunt trips (ST) 5ST304… undervoltage releases (UR) 5SM60… AFD Unit 5ST36.., 5ST37.. busbars are mountable.

10 Switching capacity, characteristics and voltages
5SL6 miniature circuit breakers for a switching capacity of 6000 A (IEC EN ) 5SL4 miniature circuit breakers for a switching capacity of A Tripping characteristics: B, C and D 1P, 230/400 V 1P+N, 230 V 2P, 400 V 3P, 400 V 3P+N, 400 V 4P, 400 V 5SL6 MCB series 5SL4 MCB series

11 Technical features 5SL6 MCB series 5SL4 MCB series Technical features
Standards: EN Rated voltage: 230/400 V AC Sealable handle Degree of protection: IP 40 Mounting position: any Ambient temperature: -25ºC … +55ºC Climate-resistant: according to IEC Pollution degree: 2 Rectangular terminal version for accommodating pin busbars together with conductors from 0.75 to 35 mm² 1 to 4-pole version Touch protection Rated current: 0.3 A – 63 A 5SL6 MCB series 5SL4 MCB series

12 Tripping characteristics type "B" and type "C"
Tripping characteristic type "B" Tripping characteristic type "C" Miniature circuit breakers with tripping characteristic "B" are designed for universal use in socket outlet circuits and lighting circuits Verification of personal safety according to DIN VDE is not required. Miniature circuit breakers with tripping characteristic C are preferred in lamp circuits and motor circuits with high starting currents

13 Tripping characteristic type "D"
For circuits with equipments wich generates strong impulse like transformers or magnetic values

14 Dimensions – symbols Dimensions Symbols 1P 1P+N 2P 3P 3P+N 4P

15 Bus mounting Bus mounting
Bus mounting with standard busbars of 1-, 2- and 3-pole type in finished lengths and sold by the meter for customized cutting-to-length. Also in the standard range are busbars for bus mounting when auxiliary switches or similar are fitted.

16 Additional components
Handle locking device Adapted handle locking device suitable for 5SL, 5SY, 5SJ and 5SP For locks with a diameter from 3 mm to 6 mm Padlock for 5ST3 801 and 5ST3806 handle locking device

17 Selection and order number overview
Examples 5SL4110-6 MCB 230/400 V; 10 kA 1-pole; B10 5SL4116-6 MCB 230/400 V; 10 kA 1-pole, B16 5SL4120-6 MCB 230/400 V; 10 kA 1-pole; B20 Structure of the order number system Example: 5SL4316-7 Characteristic Number of amps Number of poles Series and type of miniature circuit breaker Miniature circuit breakers from 0.3 A to 63 A with "B, C, D" characteristic


Download ppt "5SL4 10 kA / 5SL6 6 kA miniature circuit breakers"

Similar presentations