TESTING GROUNDING SYSTEMS

Slides:



Advertisements
Similar presentations
Bonding and Grounding What? Why? How?
Advertisements

Introducing Electricity and Electrical Safety
Introducing Electricity and Electrical Safety
The Electrical GuruTM Paul W. Abernathy,CME
Electrical Safety Program. How Electricity Works Operating an electric switch is like turning on a water faucet. Behind the faucet or switch there must.
OSHA Office of Training and Education - Revised by TEEX 12/05/07
Electrical Safety.
Electrical Safety Basic Electrical Safety Rafael Coll, Environment Safety and Health Section Health& Safety Group Ext Pager: (630)
This presentation is for illustrative and general educational purposes only and is not intended to substitute for the official MSHA Investigation Report.
CHEM 521 Safety Presentation. Hazard Symbols You Must Know.
GROUND FIELD RESISTANCE TESTING
By: Aseem Aggarwal. Causes of Electrocution Fatalities Contact with Overhead Power lines Contact with Live Circuits Poorly Maintained Extension Cords.
OSHA Office of Training and Education
Electrical Safety and Grounding Essentials Copyright © Texas Education Agency, All rights reserved.
Proper Use of Extension Cords Proper Use and Electrical Hazard Awareness for Extension Cord Users Module 2.
ELECTRICAL SAFETY Safety Training for the Non-Qualified.
Technician License Course Chapter 9 Lesson Module 20: Electrical Safety.
Technician License Course Chapter 9 Lesson Module 20: Electrical Safety.
Chapter : 7 : Mains Electricity
OSHA Office of Training and Education
 Recognize the scope and structure of the OSHA standards.  Identify the common electrical hazards in long term care settings.  Discuss electrical safety.
Occupational Safety and Health Course for Healthcare Professionals.
Circuit Protection Electrical circuits require protection to prevent fire or electrocution in the event of a fault. There are two main types of circuit.
Union College EHS Training 1 Electrical. 2 Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical.
Hazard - Inadequate Wiring
Bonding, Grounding and the NEC  Presented by The National Association of Certified Home Inspectors
The Home Inspection Book: A Guide for Professionals By Marcia Darvin Spada Copyright, Thomson/South-Western, 2003, Revised, 2006.
BUILDING TRADE SAFETY ELECTRICAL SAFETY.
Safety Training For The Non-Qualified
ELECTRICAL SAFETY OSHA 29 CFR 1910 SUBPART S
Area of Study 2: Electricity
Electricity at Work.
Electrical Safety.
Electrical Safety INSTRUCTOR’S NOTES:
Electrical Safety Training
Electrical This presentation is designed to assist trainers conducting OSHA 10-hour General Industry outreach training for workers. Since workers are.
Electrical Safety INSTRUCTOR’S NOTES:
1 Electrical Safety. 2 Electrical Hazards & OSHA 29 CFR (b)(1) requires: “Electrical equipment shall be free from recognized hazards that are.
Electrical Safety INSTRUCTOR’S NOTES:
Electrical Power Systems
Grounding, bonding, and ground fault currents
Ferris State University & Michigan Department of Career Development 1 Electrical Safety.
Electrical Safety in Construction. Objectives In this course, we will discuss the following: Common electrical hazards Standards relating to those hazards.
Basic Electrical Safety
Safety Rules, Practices and Devices Electric Shock – Nerve and muscle (including breathing and heart beat) functions work off of electric pluses (electron.
SAFETYSAFETY. Overview ●Introduction to Safety ●Potential Electronic Mishaps ●Safe Work Practices.
Proper Use of Extension Cords
Electrical Safety and Electrical Safe Work Practices EHS Course #525 Reference EHS Electrical Safety Procedure
1 HVACR317 – Core for Refrigeration Safety and Hazard Prevention.
GROUND FIELD RESISTANCE TESTING COMPLYING WITH MSHA REGULATIONS.
PORTABLE & TRANSPORTABLE ELECTRICAL EQUIPMENT. Legal Requirement and References Abu Dhabi RSB Electrical Regulations - makes reference to the need to.
Electrical Safety, Subpart K
The two types of electricity used in mining are: “AC” or alternating current and “DC” or direct current.
HOUSE WIRING Final Review. Electricity Electricity = flow of electrons Conductor= electricity passes thru easily - Metal, water, person Insulator = restricts.
Principles of Electricity Volt The measurement of electrical pressure.
BASIC ELECTRICAL SAFETY. INTRODUCTION PURPOSE: To provide employees with safe work practices & procedures to prevent an electrical accident or injury.
Electrical Safety.
UNIT-5. ELECTRICAL SAFETY, WIRING & INTRODUCTION TO POWER SYSTEM
Circuit Protection Unit 9.
Basic Electrical Safety
Personal Protective Equipment
Electrical Safety in the Home
EET 323 – Electrical System Design Lecture 9: Grounding
This presentation is for illustrative and general educational purposes only and is not intended to substitute for the official MSHA Investigation Report.
Basic Electrical Safety
Basic Electrical Safety
A. Touching both terminals with the hands can cause electrical shock
Electrical components and systems
Presentation transcript:

TESTING GROUNDING SYSTEMS Originally Developed by: RONALD J. RENOWDEN - CMSP Denver Field Office Supervisor, MNM MSHA Rocky Mountain District Denver, Colorado Enhanced by: Roy W. Milam Electrical Engineer/Instructor National Mine Health and Safety Academy Beckley, West Virginia

TESTING GROUNDING SYSTEMS As required by: 30 CFR §56/57.12028

56/57.12028 the REG. “Continuity and resistance of grounding systems shall be tested immediately after installation, repair, and modification; and annually thereafter. A record of the resistance measured during the most recent test shall be made available on request by the Secretary or his duly authorized representative.”

WHY DO WE TEST ? Ensure that continuity & resistance tests are conducted on a specific schedule (at least annually) Alert mine operators if there is a problem in the grounding system Problem may not allow the circuit protective devices to quickly operate when faults occur

WHY DO WE TEST? With exception of fixed installations - Numerous fatalities and injuries have occurred due to HIGH resistance or LACK of continuity in equipment grounding systems Proper testing and maintenance of grounding systems can prevent electrical accidents This all sounds so good that we made it the policy regarding 12028.

56/57.12028 the POLICY The intent of this standard is to ensure that continuity and resistance tests of grounding systems are conducted on a specific schedule. These tests will alert the mine operator if a problem exists in the grounding system which may not allow the circuit protective devices to quickly operate when faults occur. With the exception of fixed installations, numerous fatalities and injuries have occurred due to high resistance or lack of continuity in equipment grounding systems. These accidents could have been prevented by proper testing and maintenance of grounding systems.

P O L I C Y Grounding systems typically include the following: 1. equipment grounding conductors - the conductors used to connect the metal frames or enclosures of electrical equipment to the grounding electrode conductor; 2. grounding electrode conductors - the conductors connecting the grounding electrode to the equipment grounding conductor; and 3. grounding electrodes - usually driven rods connected to each other by suitable means, buried metal, or other effective methods located at the source, to provide a low resistance earth connection. P O L I C Y

P O L I C Y Operators shall conduct the following tests: 1. equipment grounding conductors - continuity and resistance must be tested immediately after installation, repair, or modification, and annually if conductors are subjected to vibration, flexing or corrosive environments; 2. grounding electrode conductors - continuity and resistance must be tested immediately after installation, repair, or modification, and annually if conductors are subjected to vibration, flexing or corrosive environments; and 3. grounding electrodes - resistance must be tested immediately after installation, repair, or modification, and annually thereafter. P O L I C Y

56/57.12028 the POLICY Conductors in fixed installations, such as rigid conduit, armored cable, raceways, cable trays, etc., that are not subjected to vibration, flexing or corrosive environments may be examined annually by visual observation to check for damage in lieu of the annual resistance test. When operators elect to conduct this visual examination as a method of compliance with 30 CFR56/57.12028, MSHA will require that a record be maintained of the most recent annual visual examination.

56/57.12028 the POLICY Grounding conductors in trailing cables, power cables, and cords that supply power to tools and portable or mobile equipment must be tested as prescribed in the regulation. This requirement does not apply to double insulated tools or circuits protected by ground-fault-circuit interrupters that trip at 5 milli-amperes or less.

56/57.12028 the POLICY Testing of equipment grounding conductors and grounding electrode conductors is not required if a fail-safe ground wire monitor is used to continuously monitor the grounding circuit and which will cause the circuit protective devices to operate when the grounding conductor continuity is broken.

That’s all the policy! But what does it all mean ? A record of the most recent resistance tests conducted must be kept and made available to the Secretary or his authorized representative upon request. When a record of testing is required by the standard, MSHA intends that the test results be recorded in resistance value in ohms. That’s all the policy! But what does it all mean ?

TYPICAL GROUNDING SYSTEM has three parts EQUIPMENT GROUNDING CONDUCTORS (the most important part!!!) Grounding Electrode Conductors Grounding Electrodes

EQUIPMENT GROUNDING CONDUCTOR The conductors used to connect the metal frames or enclosures of electrical equipment to the grounding electrode conductor Life Wire; Life Line Most important electrical safety item in the electrical system People protector

GROUNDING BUS maybe in MCC Equipment Grounding Conductors GROUNDING BUS maybe in MCC Motor 1 Motor 4 Motor 2 Motor 3

GROUNDING ELECTRODE CONDUCTOR Conductor that connects the grounding electrode and the transformer to the equipment grounding conductor TRANSFORMER Main Ground Bus maybe in the MCC Earth Grounding Electrode

GROUNDING ELECTRODES Usually driven rods connected to each other by suitable means, buried metal plates, or any other effective methods located at the power source to provide a low resistance earth connection. What is actually in contact with Earth. Grid Rod

EQUIPMENT GROUNDING CONDUCTORS Test for Continuity and Resistance Immediately after - INSTALLATION, REPAIR, OR MODIFICATION, AND ANNUALLY, IF conductors are subjected to VIBRATION FLEXING CORROSIVE ENVIRONMENTS

GROUNDING ELECTRODE CONDUCTOR Test for Continuity and Resistance Immediately after - INSTALLATION, REPAIR, OR MODIFICATION, AND ANNUALLY, IF conductors are subjected to VIBRATION FLEXING CORROSIVE ENVIRONMENTS

GROUNDING ELECTRODES Testing Test for Resistance (Earth) Immediately after - INSTALLATION, REPAIR, OR MODIFICATION, AND ANNUALLY thereafter.

Are there EXCEPTIONS ? YES !!! In lieu of doing annual resistance tests, the Grounds may be examined annually by visual observation to check for damage….. BUT ONLY IF: The conductors are in fixed locations such as; RIGID CONDUIT ARMORED CABLE RACEWAYS CABLE TRAYS, ETC (there’s more)

MORE EXCEPTIONS These FIXED LOCATIONS Vibration FLEXING CORROSIVES MUST NOT be SUBJECTED TO: Vibration FLEXING CORROSIVES

HOW MUCH IS TOO MUCH ? FLEXING VIBRATION CORROSIVES

HOW MUCH IS TOO MUCH ? The inspector makes the final determination concerning areas acceptable to visual examinations

IF VISUAL EXAMS ARE CONDUCTED MSHA policy requires that a WRITTEN RECORD be maintained of the most recent ANNUAL VISUAL EXAMINATION, can be electronic

EQUIPMENT GROUNDING CONDUCTORS IN: Trailing cables Power cables Cords supplying power to tools Cords and cables supplying power to portable or mobile equipment MUST BE TESTED AS PRESCRIBED IN THE REGULATION

When Is Testing NOT Required? IF a fail-safe ground wire monitor is used. The monitor will cause the circuit protective device to open when the grounding conductor continuity is broken. It continuously monitors the continuity of the grounding conductor. Double insulated tools are used. There is no grounding conductor to test. If the circuit used incorporates a GFCI that trips at 5 milli-amps or LESS. There are 110v and 220v devices now available.

RECORDS RESISTANCE VALUES IN OHMS Most recent tests Must be available for review by MSHA upon request No specific format required Be legible Visual exam records

A little ADVICE ? Should have electrical knowledge Know how to test and use the instrument/PPE Know what kind of electrical system Check circuit protective device vs. Ohms test Check with power off Proper size ground wire Never let metal framework or earth be the primary grounding conductor Never use peg grounding

NATIONAL ELECTRICAL CODE Section 250-51-EFFECTIVE GROUNDING PATH: The path to ground from circuits, equipment, and metal enclosures for conductors shall: Be permanent and electrically continuous Have capacity to conduct safely any fault current likely to be imposed on it, and Have sufficient low impedance to limit the voltage to ground and to facilitate the operation of the circuit protective devices. The earth SHALL NOT be used as the sole equipment grounding conductor

OK, now that the operator has tested his grounding circuit and recorded the results, what do we do with them? In other words……

How do you know if the ground wire resistance is okay? Can apply good old OHM’S LAW: E = IR E = VOLTS I = AMPS (current) R = RESISTANCE (ohms) E I = R E I R

BUT …..FIRST ! Remember OHM’S LAW ! ( E = IR ) Circuits are protected by fuses/breakers against SHORT CIRCUITS AND GROUND FAULTS IF GF occurs, we want the fuse/breaker to clear ASAP! Question? Where does the current go when a ground fault occurs? GROUNDING CONDUCTOR carries the fault current back to the SOURCE (current does not return to earth, but sometimes travels thru it). FAULT CURRENT takes path of LEAST resistance?

CONTINUED IF ground wire is missing or high resistance, current will flow in dangerous places to return to the source. TOUCH AND STEP POTENTIALS MAY EXIST ON THE FRAMES OF EQUIPMENT AND ON THE EARTH HAZARDOUS!!!!! : SHOCK, BURNS, ELECTROCUTION……..DEATH

EXAMPLE: The operator’s record of resistance testing (in OHMS) shows the following: Crusher motor = 1 ohm Screen Deck = .5 ohm Stacker main motor = 1.5 ohm Conveyor 1 = 1 ohm

Need: Circuit/System VOLTAGE: Example:What’s Next ? Need: Circuit/System VOLTAGE: Motors supplied with 3 phase, 460 volt AC Grounded WYE Service; Ø-Ø=460v; Ø-grd=265v Need: Fuse/Circuit Breaker Size (for each) 100hp, 125amps, 3-fuses @ 300amps each (crusher motor) 40hp, 52amps, 3-fuses @ 100amps each (screen) 25hp, 34amps, 70 amp breaker (stacker) 10hp, 14amps, 30 amp breaker (conveyor 1)

GROUNDED WYE Grounded WYE Service; 460 V, 3-PHASE ØA-ØB=460v; ØA-grd=265V ØA-ØC=460v; ØB-grd=265V ØB-ØC=460v; ØC-grd=265V O A B A O B C O C Ground Ground

How good is the equipment grounding? CONVEYOR 1: 1ohm, Ø-grd=265v. How much FC will flow if GF at motor frame? To find current (ohms law) I= E/R. 265v I = =265 amp FC; On 30 amp 1ohm breaker 265a.(FC)/30a(bkr) = 8.83...What’s this mean? Breaker will TRIP almost instantaneous level ASAP GOOD GROUNDING!

LET’S CHECK ANOTHER ! SCREEN: .5 ohms, Ø-grd=265v 265v I = =530 amp FC; On 100 amp .5ohm fuses 530a.(FC)/100a.(fu) = 5.30...What’s this mean? Fuse will not TRIP near instantaneous level (ASAP) GOOD GROUNDING ? Questionable! Review trip curve chart for fuse to find trip time…. ADVICE: Check connections; loose, dirty, wire size? CORRECT/ REPAIR! Screens- flexing and vibration!

LET’S CHECK ANOTHER ! CRUSHER: 1 ohm, Ø-grd=265v 265v I = =265 amp FC; 300 amp fuses 1ohm 265a.(FC)/300a.(fu) = .88 ...What’s this mean? Fuse will not BLOW (must see at least 125% to begin) DANGEROUS GROUNDING UNACCEPTABLE! ADVICE: Check connections; loose, dirty, wire size? CORRECT & REPAIR! Crushers - flexing and vibration

Let’s make a small change!!! CRUSHER: 1 ohm, Ø-grd=265v, but this time we’re going to use a 100 Amp, Magnetic Trip Circuit Breaker with a trip range of 150-480 amps, set on LOW, as protection. 265v I = =265 amp FC; CB set 150 Amps 1ohm 265a.(FC)/150a.(Inst.) = 1.77 ...What’s this mean? Breaker will TRIP instantaneously. GOOD GROUNDING!

Corner Grounded Delta Corner Grounded Delta Service; 460 V, 3-PHASE ØA-ØB=460v; ØA-grd=0V ØA-ØC=460v; ØB-grd=460V ØB-ØC=460v; ØC-grd=460V O A B O B C O C A Ground

Corner Grounded Delta CONVEYOR 1: 1ohm, Ø-grd=480v. How much FC will flow if GF at motor frame? To find current (ohms law) I= E/R. 480v I = =480 amp FC; On 30 amp breaker 1ohm 480a.(FC)/30a(bkr) = 16.0...What’s this mean? Breaker will TRIP at instantaneous level ASAP GOOD GROUNDING !

Corner Grounded Delta I = .5ohm =960 amp FC; On 100 amp fuses SCREEN: .5 ohms, Ø-grd=480v 480v I = .5ohm =960 amp FC; On 100 amp fuses 960a.(FC)/100a.(fu) = 9.60...What’s this mean? Fuse will TRIP near instantaneous level (ASAP) GOOD GROUNDING !

Corner Grounded Delta CRUSHER: 1 ohm, Ø-grd=480v 480v I = =480 amp FC; 300 amp fuses 1ohm 480a.(FC)/300a.(fu) = 1.6 ...What’s this mean? Fuse will start heating up. (must see at least 125% to begin) Will blow on very long delay. DANGEROUS GROUNDING UNACCEPTABLE! ADVICE: Check connections; loose, dirty, wire size? CORRECT & REPAIR! Crushers - flexing and vibration

FLOATING or UNGROUNDED SYSTEMS BE AWARE! HAZARDOUS- IF NOT MONITORED FOR GROUNDS AND MAINTAINED ELECTRICAL SHOCK THERMAL ARC FLASH BURNS ELECTROCUTION FIRES

Now let’s look at some of the test instruments that can be used to test the grounding system

Instruments used to test the grounding electrode

This is a Biddle Earth Tester that is battery powered This is a Biddle Earth Tester that is battery powered. It uses 6 “C” cells. It is used to test the grounding electrode resistance.

This a type of Biddle Earth Tester that is battery powered This a type of Biddle Earth Tester that is battery powered. It is powered by 4 “C” cells. It is used to test the grounding electrode resistance. Measuring the resistance of the equipment grounding conductor for this piece of equipment.

This is a Biddle Earth Tester that is used to test the resistance of the grounding electrode. It is powered by the use of the hand crank on the side of the device.

This is the Field Kit that is used with an Earth Tester to measure the resistance of the grounding electrode. It contains 2 metal stakes, and 3 conductors of various lengths.

Set-Up for Testing Grounding Electrode Resistance C1 P1 G P2 C2 Earth Test Rods Grounding Electrode

This person is driving a test rod to be used while testing the grounding electrode resistance.

This is the method used when testing the grounding electrode resistance with a Biddle Earth Tester.

The results obtained during the testing of the grounding electrode resistance are plotted on a graph. The actual resistance of the electrode is the flat part of the graph.

Another method of testing the resistance of the grounding electrode is using a voltage source, such as a vehicle battery, a voltmeter and an ammeter. We do not recommend this method as it can be extremely dangerous.

This is one possible set-up for testing the grounding electrode resistance.

This is the method used when testing the grounding electrode resistance with a Biddle Earth Tester.

Use OHM’S LAW to calculate the resistance values your tests found. R=E/I

The results obtained during the testing of the grounding electrode resistance are plotted on a graph. The actual resistance of the electrode is the flat part of the graph.

This is the ECOS Pow-R-Mate Tester This is the ECOS Pow-R-Mate Tester. It is used to test the resistance and impedance of the grounding electrode. It is both battery powered and plug-and-cord connected.

This is a Biddle Insulation Tester that is used to test the insulation value of conductors, motors, transformers, and cables. It is powered by the hand crank on the side of the device. This device should not be used to test the grounding electrode nor the equipment grounding conductors.

Instruments used to test the grounding electrode conductor and the equipment grounding conductors

This is a Fluke Graphics Multi-Meter which can be used to measure the resistance of the equipment grounding conductors.

This is a Fluke Multi-Meter which can be used to measure the resistance of the equipment grounding conductors.

This is a Simpson Multi-Meter which can be used to measure the resistance of the equipment grounding conductors. It is reading an open conductor now.

This is a Simpson Multi-Meter, with test leads attached, which can be used to measure the resistance of the equipment grounding conductors. It is reading an open conductor now.

This is a Simpson Multi-Meter, with test leads attached, which can be used to measure the resistance of the equipment grounding conductors. It is reading Zero ohms resistance as the test leads are contacting each other. The meter is being zeroed.