Control System Analysis and Design by the Frequency Response Method

Slides:



Advertisements
Similar presentations
Stability Margins Professor Walter W. Olson
Advertisements

Bode Diagram (1) Hany Ferdinando Dept. of Electrical Engineering Petra Christian University.
Fundamentals of Electric Circuits Chapter 14 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Frequency response When a linear system is subjected to a sinusoidal input, its steady state response is also a sustained sinusoidal wave, with the same.
Chapter 10: Frequency Response Techniques 1 ©2000, John Wiley & Sons, Inc. Nise/Control Systems Engineering, 3/e Chapter 10 Frequency Response Techniques.
Frequency Response Techniques
Bode Magnitude Plots Constructed Bode Actual Bode
Loop Shaping Professor Walter W. Olson
CHE 185 – PROCESS CONTROL AND DYNAMICS
Frequency Response Methods and Stability
Transient & Steady State Response Analysis
Lecture 9: Compensator Design in Frequency Domain.
Dr. / Mohamed Ahmed Ebrahim Mohamed Automatic Control By Dr. / Mohamed Ahmed Ebrahim Mohamed Web site:
Chapter 5 Frequency-Domain Analysis
سیستمهای کنترل خطی پاییز 1389 بسم ا... الرحمن الرحيم دکتر حسين بلندي - دکتر سید مجید اسما عیل زاده.
Automatic Control Theory-
Automatic Control Theory School of Automation NWPU Teaching Group of Automatic Control Theory.
Chapter 8 Frequency-Response Analysis
Chapter 9 Frequency Response and Transfer Function
Automatic Control Theory School of Automation NWPU Teaching Group of Automatic Control Theory.
Chapter 6: Frequency Domain Anaysis
Frequency Response OBJECTIVE - Bode and Nyquist plots for control analysis - Determination of transfer function - Gain and Phase margins - Stability in.
F REQUENCY -D OMAIN A NALYSIS AND STABILITY DETERMINATION.
Frequency Response Analysis Section 6. E&CE 380 Copyright © 1998 by William J. Wilson. All rights reserved G(s)G(s)G(s)G(s) r(t) = A sin(  t) c(t) =
Chapter 10 Frequency Response Techniques Frequency Response Techniques.
INC 341PT & BP INC341 Frequency Response Method Lecture 11.
Week 9 Frequency Response And Bode Plots. Frequency Response The frequency response of a circuit describes the behavior of the transfer function, G(s),
Chapter 6: Frequency Domain Anaysis
Lecture 9 Feedback Control Systems President UniversityErwin SitompulFCS 9/1 Dr.-Ing. Erwin Sitompul President University
Lecture 21: Intro to Frequency Response 1.Review of time response techniques 2.Intro to the concept of frequency response 3.Intro to Bode plots and their.
7.1 Root Locus (RL) Principle We introduce the RL through an example. Consider servo motor system shown bellow The closed loop transfer function is motor.
MESB374 System Modeling and Analysis Chapter 11 Frequency Domain Design - Bode.
Control Systems Lect.3 Steady State Error Basil Hamed.
Feedback Control System THE ROOT-LOCUS DESIGN METHOD Dr.-Ing. Erwin Sitompul Chapter 5
Network Analysis and Synthesis
6. Nyquist Diagram, Bode Diagram, Gain Margin, Phase Margin,
Design via Root Locus (Textbook Ch.9).
DNT Control Principle Frequency Response Techniques DNT Control Principle.
Frequency-Domain Analysis and stability determination
Frequency-Domain of Control Systems
Chapter 9 Design via Root Locus <<<4.1>>>
Chapter 6 Feedback Circuits
Chapter 9 Design via Root Locus <<<4.1>>>
Frequency Resp. method Given:
7.1 Root Locus (RL) Principle
Root-locus Technique for Control Design
Root-Locus Analysis (1)
Fundamentals of Electric Circuits Chapter 14
Digital Control Systems (DCS)
Root Loci Analysis (3): Root Locus Approach to Control System Design
Feedback Control Systems (FCS)
Frequency Response Techniques
Frequency Resp. method Given: G(s)
Hanani binti Abdul Wahab 24 September 2008
Compensators.
Feedback Control Systems (FCS)
Frequency Response Techniques
UNIVERSITI MALAYSIA PERLIS SCHOOL OF ELECTRICAL SYSTEM ENGINEERING
Frequency Response Method
دکتر حسين بلندي- دکتر سید مجید اسما عیل زاده
Frequency Domain specifications.
7-5 Relative Stability.
Root-Locus Analysis (2)
7-4 Control System Design by Frequency Response Approach
Chapter 4. Time Response I may not have gone where I intended to go, but I think I have ended up where I needed to be. Pusan National University Intelligent.
Frequency Response OBJECTIVE
Frequency Response Techniques
IntroductionLecture 1: Basic Ideas & Terminology
Time Response, Stability, and
The Frequency-Response Design Method
Presentation transcript:

Control System Analysis and Design by the Frequency Response Method Chapter 7 Control System Analysis and Design by the Frequency Response Method

7-1 Introduction 1. The concept of frequency response G(s) R(s) Y(s)

Frequency response: The frequency response of a system is defined as the steady-state response of the system to a sinusoidal input signal. For a stable LTI system, the resulting output signal, as well as signals throughout the system, is also sinusoidal in the steady-state; it differs from the input waveform only in amplitude and phase angle.

2. Obtaining steady-state outputs to sinusoidal inputs For a given stable LTI system with a sinusoidal input, the steady state output can be completely characterized by its transfer function with s being replaced by j. That is, if the system transfer function is G(s), then from the steady-state response we have

To prove this conclusion, consider the following controlled plant: G(s) R(s) Y(s)

G(s) R(s) Y(s) Transient response Steady-state response If the system is stable, then the transient response

The steady state response Note that Hence,

Write where Similarly, Therefore,

Now, the steady-state response can be written as with and

based on which, we obtain the following important results: Amplitude ratio of the output sinusoid to the input sinusoid Phase shift of the output sinusoid with respect to the input sinusoid

Noting that It follows that the frequency response characteristics of a stable LTI system to a sinusoidal input can be obtained directly from which is the complex ratio of output sinusoid to input sinusoid. Remark: Though we have deduced the frequency response under the assumption that G(s) is stable, it can be extended to the case that G(s) is unstable.

Example 1. The controlled plant is R(s) Y(s) Let r(t)=Xsint. Find its frequency response yss(t). Solution: By definition of frequency response, yss(t) can be completely characterized by G(j), that is, with

Example 2. The controlled plant is Hence, where <0. Example 2. The controlled plant is R(s) Y(s) Let r(t)=Xsint and suppose T1>T2. Find its frequency response yss(t).

Solution: By definition, Since in this example,

Since by assumption, T1>T2, it follows that >0. Definition: A positive phase angle is called phase lead and a negative phase angle is called phase lag. By this definition, the fist example is a phase lag system, while the second one is a phase lead system. Therefore, the lead compensator corresponds to a phase lead network while lag compensator, a phase lag network.

3. Why is frequency response important? Since for an LTI system, its frequency response can be fully characterized by G(j), or by our later analysis will show that by using the so called Bode diagram and Nyquist plot, one is able to Determine how the system responds at different frequencies; Find stability properties of the system in closed-loop control; Design compensating controllers.

7-2 Bode Diagrams or Logarithmic Plots Concept of Bode diagram A Bode diagram consists of two graphs: One is a plot of the logarithm of the magnitude of a sinusoidal transfer function; the other is a plot of phase angle; both are plotted against the frequency on a logarithmic scale. C R

where the base of the logarithm is 10, the unit is decibel (dB) and the horizontal axis is logarithmic scale lg. Bode Phase angle: with the horizontal axis being also lg.

Example. Given a first-order system Plot its Bode diagram. Solution: Write and

Hence, both Bode magnitude and phase angle diagrams are shown below:

Example. An open-loop transfer function is given below: Plot its Bode diagram. Solution: Write and

Bode diagram 10 20 30 40 50 2 4 6 1 8 60

From the aforementioned examples, it is clear that one of the main advantages of Bode diagram is that multiplication of magnitude can be converted into addition, which may make our analysis much simpler.

2. Bode diagrams for basic factors of G(j)H(j) The basic factors that very frequently occur in an arbitrary transfer function G(j)H(j) are

1 10 100 1000 20lgK (dB)  

Example. Open-loop transfer functions are Plot their Bode diagrams. The bode magnitude plot is the sum of 20lg(10) and -20lg.

Bode magnitude: Phase angle: Asymptotic curves for Bode magnitude:

The frequency 1/T is called corner (break) frequency, at which Vividly describes the asymptotic curve The maximum error in the magnitude curve caused by the use of asymptotes occurs at 1/T is approximately equal to 3 dB since

First-order derivative factorG(s)=Ts+1: whose Bode magnitude and phase angle curves, due to the property that Ts+1 is the reciprocal factor of 1/(Ts+1), need only be changed in sign. Corner frequency: 1/T

Example. Open-loop transfer functions are Plot, for T1>T2 and T1<T2 cases, Bode diagrams.

The magnitude of G(j) is The phase angle of G(j) is

From we have 1  r G(j) Resonant frequency: Resonant peak value: Mr G(j) Resonant frequency: When \omega is greater than or equals to 0.707, there is no resonant peak occurs and abs(G(j\omega)) decreases monotonically with maximum value=1=abs(G(j0)). Resonant peak value:

For 0 < 0.707, 1  0=r G(j) and from which it can be seen that for > 0.707, there is no resonant peak and the magnitude G(j) decreases monotonically as the frequency  increases (20lgG(j)<0 dB, for all values of  > 0. Recall that, for 0.707<< 1, the step response is oscillatory, but the oscillations are well damped and are hardly perceptible).

Asymptotic curves for Bode magnitude: When <<n, the Bode magnitude becomes When >>n , the Bode magnitude becomes Therefore, the corner frequency =n.

-40dB/dec

Note that at n, the phase angle is 900 regardless of  since If zita is very small the resonant peak cannot be neglectable.

Comment on the resonant peak value Mr For 0 < 0.707, For  >0.707,

Since it follows that Zeta=0 corresponds to simple harmonic motion. This means that if the undamped system is excited at its natural frequency, the magnitude of G(j) becomes infinite.

Example. The Bode asymptotic magnitude curve of a second-order system is shown below. Determine its transfer function and resonant peak value. Solution: The transfer function is of the form: o 30 L()/dB 630 33dB 40dB/dec Therefore,

3. General procedure for plotting Bode diagrams 1). Write G(s)H(s) in the following normalized form (for instance): from which the basic factors that compose the transfer function can be obtained. 2). Identify the corner frequencies associated with these basic factors (for instance): 1/1, 1/2, 1/T1, 1/T2, n, and so on.

3). Draw the separate asymptotic magnitude curves for each of the factors: [-20] Brown curve

Correspondingly, draw the separate phase angle curves for each of the factors: 00 450 900

4). Draw the composite curves by algebraically adding the individual curves.

Example. The controlled plant is Draw its asymptotic Bode diagram. Solution: Note that the system consists of Constant gain K =10 (20lg10=20 dB) An integral factor A first-order factor with corner frequency 2rad/s

[-20] [-40]

-20dB/dec -40dB/dec

Example. The controlled plant is Draw its asymptotic Bode diagram. A constant gain K=5 (20lgK=14 dB) An integral factor 1/s A first-order factor with corner frequency 2rad/s A first-order derivative factor with corner frequency 10rad/s A pair of complex poles with corner frequency 50rad/s

40dB

Example. The controlled plant is Draw its asymptotic Bode diagram. Note that we must rewrite the above transfer function in a normalized form.

4. Minimum phase and nonminimum phase transfer functions Definition: A transfer function is called a minimum phase transfer function if all its zeros and poles lie in the left-half s-plane, whereas those having poles and zeros in the right-half plane are called nonminimum phase transfer functions.

Example. We investigate the range of the phase angles for the following two plants over the entire frequency range from zero to infinity. By definition, G1(s) is a minimum phase transfer function, while G2(s) is a nonminimum phase one.

In case of T>T1, G1(s) and G2(s) have same Bode magnitude, but their phase angles are different: lg G2(j) -1800

In case of T<T1, G1(s) and G2(s) have same Bode magnitude, but their phase angles are different:

In general, we have following conclusion: For a minimum phase system, the transfer function can be uniquely determined from the magnitude curve alone, while for nonminimum system, this is not the case. For systems with the same magnitude characteristics, the range in phase angle of the minimum-phase transfer function is minimum among all such systems, while the range in phase angle of any nonminimum-phase transfer function is greater than this minimum.

Determine its transfer function and static position error constant Kp. Example. The Bode magnitude plot of a minimum phase system is shown below: 14 3 10 Determine its transfer function and static position error constant Kp.

Solution: The minimum phase assumption implies that the magnitude plot alone suffices to determine its transfer function. The system consists of three factors: gain K, and two first-order factors with corner frequencies 3 rad/s and 10rad/s, respectively. Therefore, the transfer function is The static position error constant is

Determine its transfer function and prove that Example. The Bode magnitude plot for Type 1 minimum phase system is shown below: [-20db/dec] [-40db/dec] lg L() 20lgKv =1 2 3 1 Determine its transfer function and prove that

Example. The Bode magnitude plot for type 2 minimum phase system is shown below: [-40db/dec] [-20db/dec] lg L() 20lgKa =1 2= [-60db/dec] Prove that

Example. The asymptotical Bode magnitude plot of a minimum phase system is shown below. Determine its transfer function. Solution: The minimum phase assumption implies that the transfer function is of the form:

The slope of the leftmost curve is 20dB/dec The slope of the leftmost curve is 20dB/dec. Therefore, the system has an integral factor. When =1, the y-axis is 15dB, at which the gain is 20lgK=15, K=5.6 When 27, the slope changes from 20dB/dec to 40dB/dec, which shows that =2 is the corner frequency of a first-order system. =7 is the corner frequency of a first-order derivative factor. Therefore, the transfer function is

7-3 Polar Plots 1. The concept of Nyquist curve The Nyquist curve of G(j) is a plot of the magnitude of G(j) versus the phase angle of G(j) on the polar coordinates as  is varied from zero to infinity. Write or

Let Then, as  varies from 0 to +, the terminal of the vector function traces out a curve j 1 O which is called Nyquist curve, also polar plot.

2. Nyquist plots for basic factors of G(j)H(j)

Consider the following network: Plot its Nyquist curve.

A semicircle Notice: To draw the Nyquist curve, one should choose some typical points, for instance, =0, =1/T and =.

Example. Plot the Nyquist curve of the following transfer function: Since The low-frequency portion of the curve is

The high-frequency portion is and is tangent to the negative real axis.

First-order derivative factor:

=0 = Resonant peak r

The low-frequency portion of the curve is and the high-frequency portion is

3. General shapes of polar plots We consider the polar plots of general form of transfer function (n>m): =0, Type 0 systems: The low-frequency portion of the plot is

The high-frequency portion of the plot is Example. Consider the following transfer function Sketch its Nyquist plot.

Solution: The low-frequency portion of the plot is The high-frequency portion of the plot is

and is tangent to the negative real axis. Similarly, we can discuss the Nyquist plot for

Example. Consider the following transfer function: Sketch its Nyquist plot. If T1, T2> and >T3,

 =1, Type 1 systems: The low frequency portion of the plot is The high frequency portion of the plot is

Example. Consider the following transfer function: Sketch its Nyquist plots for two cases: <T1, T2 and >T1, T2.  =2, Type 2 systems:

One disadvantage of Nyquist plot is that it does not show clearly the contributions of

Example: Let the controlled transfer function be given as Sketch its Nyquist curve. Solution: The system consists of four factors: Gain K and two integral factors and a first-order factor. The low-frequency portion of the plot is and the high-frequency portion of the plot is

The sketch of the Nyquist plot is Example: Let the controlled transfer function be given as Sketch its Nyquist plots for two cases: <T and >T.

Example: Let the controlled transfer function be given as Sketch its Nyquist curve.

Example: Let the controlled transfer function be given as Sketch its Nyquist curve.

Example: Let the controlled transfer function be given as Sketch its Nyquist curve. Solution: The system is nonminimum phase. The low-frequency portion of the plot is and the high-frequency portion of the plot is