POWER FACTOR CORRECTION WISEMAN NENE EIT – ELECTRICAL ESTON SUGAR MILL
POWER FACTOR CORRECTION AS A MEANS OF COST SAVINGS
CONTENT INTRODUCTION OBJECTIVES NATURE OF ELECTRICAL POWER/LOAD POWER FACTOR THEORY
ADVANTAGES OF IMPROVED POWER FACTOR DISADVANTAGES OF LOW POWER FACTOR METHODS OF IMPROVING POWER FACTOR OVERVIEW OF THE SYSTEM SYSTEM BREAKDOWN
POWER AND COSTS SAVINGS PROJECT COSTS COSTS RECOVERY PERIOD SAFETY AND MAINTENANCE OF THE SYSTEM CONCLUSION
INTRODUCTION COSTS SAVINGS IS ONE OF THE MEASURE DRIVERS IN INDUSTRY FOR BUSINESS SUSTAINABILITY POWER FACTOR CORRECTION IS ONE OF THE MEANS THAT CAN BE USED TO REDUCE COSTS
NATURE OF ELECTRICAL LOAD Resistive - I and V peaks are simultaneous The angle between the two is zero Inductive - I lags V The angle between the two is negative Capacitive – I leads V The angle between the two is positive
OBJECTIVES TO INVESTIGATE MEANS OF COST REDUCTION FROM THE ELECTRICAL PERSPECTIVE – (POWER FACTOR CORRECTION)
POWER FACTOR THEORY PF = ACTIVE POWER / APPARENT POWER = P / S = kW / kVA ACTIVE POWER (P) = kW APPARENT POWER (S) = kVA
POWER TRIANGLE
SYSTEM BEFORE PFC PF = 0.68 Lagging
DESIRED MINIMUM SYSTEM TRIANGLE PF = 0.8 Lagging
NEW SYSTEM POWER TRIANGLE PF = 0.92 Lagging
ADVANTAGES OF IMPROVED PF REDUCED APPARENT POWER PRODUCED IMPROVED PLANT EFFICIENCY ADDITIONAL LOADS CAN BE ADDED TO THE SYSTEM REDUCED OVERLOADING OF CABLES, TRANSFORMERS, SWITCHGEAR, ETC. IMPROVED NETWORK VOLTAGE IMPROVED STARTING TORQUE OF MOTORS
DISADVANTAGES OF LOW PF INCREASES ELECTRICITY COSTS CAUSES OVERLOADING OF GENERATORS, TRANSFORMERS AND DISTRIBUTION SYSTEM GREATER VOLTAGE DROPS AND POWER LOSSES LOW EFFICIENCY AND UNNECESSARY WEAR AND TEAR TO INDUSTRIAL ELECTRICAL EQUIPMENT REDUCES LOAD HANDLING OF THE PLANTS’ ELECTRICAL SYSTEM
METHODS OF IMPROVING POWER FACTOR SYNCHRONOUS MOTORS STATIC VAR COMPENSATORS STATIC CAPACITORS
METHODS OF IMPROVING POWER FACTOR SYNCHRONOUS MOTORS Has long service life Can withstand higher short circuit currents High maintenance and installation costs STATIC VAR COMPENSATORS Fast response system System is very expensive
STATIC CAPACITORS Simple and easy to install Cannot be repaired
CONNECTION TO THE NETWORK Basic connection diagram for static capacitors
SYSTEM CONFIGURATION 4 x 48kVAr + 3 x 50 kVAr = 342 kVAr FRONT – END SECTION 4 x 48kVAr + 3 x 50 kVAr = 342 kVAr BACK – END SECTION = 6 x 62.5 kVAr = 375 kVAr
SYSTEM OPERATION Manual Mode Uses a selector switch to select a stage Automatic – using Epcos BR6000 PFC Controller Uses a selector switch to automatically select a stage
POWER AND COSTS SAVINGS Electrical saving in terms of the power consumed P = 151.44 kW P = 429.08 kW @ 0.68 PF , S = 631 kVA And at: @ 0.92 PF, S = 466.39 kVA STOTAL = SOLD – SNEW = 164.61 kVA I = S/√3 x 525 = 181.02A P = √3 V I Cos θ = 151.44 kW
RAND VALUE SAVING (ACTUAL) Assuming 24 hours/day for 30 days @ 0.4019/kWh and saving 151.44 kWh, National grid Power Energy Charge Saving = 151.44 x 24 x 30 x 0.4019 = R 43,821.89/month
POWER SAVINGS (BACK-END) P = 903.4 kW @ 0.61 PF, SOLD = 1.48 MVA @ 0.8 PF, SNEW = 1.13 MVA STOTAL= SOLD – SNEW = 350 kVA I = S/√3 x 525 = 384.9 A P = √3 V I Cos θ = 280 kW
SAVINGS ( RAND-VALUE, BACK-END) Assuming 24 hours/day for 30 days @ 0.4019/kWh and saving 280 kW hourly: Energy Charge Saving = 280 x 24 x 30 x 0.4019 = R 81,023.04/month
OVERALL POWER / COST SAVINGS For 2010 season Eskom used during crushing=331.3 hrs, [06-07-10 to 04-10-10] Electrical Power saved; P FRONT-END = 151.44 kW P BACK-END = 280 kW Total Power Saved (2010 season) = 151.44 kW + 280 kW = 431.44 kW = 431.44 kW x 331.3hrs = 142.936 MWh = 142936kWh x R0.4019 /kWh = R 57,446.00
BUDGET & COSTS RECOVERY PERIOD Approximately R45 000. Source: Electrical Department Budget Recoverable: Within 1 Month on National Grid
FINAL SYSTEM PICTURES The following pictures shows the installation locations and the results obtained from the front-end section
CONTROLLER Controller - Epcos BR6000
CONTROL Auto and Manual Control
CAPACITOR BANKS
CONTROL PANELS
MAIN PANELS
DISPLAYS With all banks OFF
WITH 6 BANKS ON .
PF ALL BANKS ON PF = 0.92 Lagging
BACK-END SECTION
SAFETY No unauthorized person should switch the system ON/OFF. Before opening the capacitor banks panels, make sure the main isolator is off and wait for at least 5minutes for the capacitors to discharge
CONCLUSION As seen on the pictures in the previous slides, the new system was successful. The power factor was corrected from 0.68 lagging to 0.92 lagging in the front-end and from 0.61 to 0.8 lagging in the back-end section
CONCLUSION cont. The costs and power savings were significant at 142.936 MWh during the 4 months period recorded during the 2010 season
ACKNOWLEDGEMENTS ESTON ENGINEERING TEAM
THANK YOU!!! ???