AEP’s Ground Grid Resistance Measurement Procedure

Slides:



Advertisements
Similar presentations
Mitigation of AC Induced Voltage On Buried Metallic Pipelines
Advertisements

Earth Ground Resistance The Basics
GROUND We walk on it, play on it, and live on it, but what is it in reality when it comes to communications systems, and how do we obtain a “TRUE” and.
GROUND FIELD RESISTANCE TESTING
Stray Current Investigations A Method of Troubleshooting Stray Current on Underground Residential Distribution (URD) Loops Stacey Mighty Malcolm Distribution.
EE4503 Electrical Systems Design
Protection against Lightning Overvoltages Overvoltages due to lightning strokes can be avoided or minimized in practice by (d) shielding the overhead lines.
AC Mitigation Overview
MUHAMMADALI MC SDE(KAM) KANNUR EARTHING. O BJECTIVES OF EARTHING  To reduce the cross talk and noise  To afford reliable path for circuits involved.
A BC D Electric field near the surface of a conductor.
Grounding of Airfield Lighting Joseph Vigilante, PE Penn State/FAA Hershey Conference 2009.
Earthing / Grounding Issues
Dynamic Presentation of Key Concepts Module 2 – Part 3 Meters Filename: DPKC_Mod02_Part03.ppt.
Electrical Earthing D.K.Pathirana. Applications of earthing Protect human against lightning and earth fault condition Protect the premises against lightning.
1 Slavko Vujević*, Petar Sarajčev* and Jakov Petrović** *University of Split, Faculty of Electrical Engineering, Mechanical Engineering and Naval Architecture,
Transmission Lines …….. Conductor Material
ECE 424 – Introduction to VLSI Design
© Shannon W. Helzer. All Rights Reserved. Unit 13/Chapter 18 Electric Currents 0.0.
Static Electricity Electrical Charge: Is a concentration of electricity.
This photo shows the overall lab and electrolytic tank.
IEEE Wind Farm Collector System Grounding for Personal Safety Summary of Topics.
Basic Electrical Circuit 1
Current & Circuits February ‘08
ECE 476 Power System Analysis Lecture 7: Transmission Line Parameters Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois.
Gandhinagar Institute of Technology
EKT 451 CHAPTER 5 DC & AC Bridge..
Lecture 6 Development of Transmission Line Models Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Basics of Ground Rod Testing
Thursday March 31, PHYS Dr. Andrew Brandt PHYS 1444 – Section 02 Lecture #16 Thursday Mar 31, 2011 Dr. Andrew Brandt HW7 Ch 27 is due Fri.
Design of a readout system for RPCs Olu Amoda2 The LODEN Group The group is an association of Fermilab scientists who teamed up to build a cosmic ray.
L1-1 ELECTROMAGNETICS AND APPLICATIONS Lecture 8 TEM Transmission Lines Luca Daniel.
GROUND FIELD RESISTANCE TESTING COMPLYING WITH MSHA REGULATIONS.
© 2007 Ideal Industries 1 of 12 Basics Clamp-on Ground Resistance Tester.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign.
Atlanta IAS Presentation November 2015 Presentation by: Hilton Mills Hood-Patterson & Dewar 850 Center Way, Norcross GA
1 DET4TC2 Measurement of Earth electrode resistance and soil resistivity……….
CHAPTER 5 DC AND AC BRIDGES.

GROUNDING SYSTEM OF HV/MV SUBSTATIONS FORMED THROUGH CABLE LINES WITH INSULATED METAL SHEATH.
Electric Fields and Circuits Ch’s 33,34,35 Created by: St. John.
The MicroBooNE Cryostat Wall as EMI Shield We estimate the noise charge induced on a TPC wire. We start with Marvin Johnson’s analysis of the transfer.
UNIT-5. ELECTRICAL SAFETY, WIRING & INTRODUCTION TO POWER SYSTEM
MI 3290 Earth Analyser Earth testers
Novel Simulation Method to Quantify Induced Voltage & Current between Parallel or Partially Parallel Proximity AC Transmission Circuits Xuan Wu, David.
WEBENCH® Coil Designer
AEP’s Ground Grid Resistance Measurement Procedure
PRACTICAL METHOD FOR ANALYSIS OF GROUNDING SYSTEM OF HV/MV SUBSTATIONS LOCATED IN URBAN AND SUBURBAN AREAS.
PRACTICAL METHOD FOR ANALYSIS OF GROUND FAULT CURRENT DISTRIBUTION ON GROUNDING SYSTEM OF LARGE HV SUBSTATIONS I. Among outgoing lines there is no any.
Evaluation Techniques
ELECTRIC SHOCK AND EARTHING
EARTHING.
Chapter 5: Earthing and Bonding
21/09/2018 Electricity.
Direct-Current Bridge.
Installation And Estimation of Service Connection
Govt. Polytechnic,Manesar
Environmental and Exploration Geophysics I
Electric Circuits Fundamentals
Grounding System Design and Testing for Critical Facilities
Lattice (bounce) diagram
Topographic Survey Introduction „ Mapping surveys are made
Topographic Survey Introduction „ Mapping surveys are made
Measurements of Inductance & Capacitance
Protecting Your Shack From Lightning (as best you can)
Applied Electromagnetic Waves
Appalachian Underground Corrosion Short Course
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
Grounding Myths.
Presentation transcript:

AEP’s Ground Grid Resistance Measurement Procedure

Overview Ground grid resistance (GGR) and GIC flow Available approaches for obtaining GGR value Calculating Effective GGR A recommended procedure for obtaining GGR value

Ground Grid Resistance and GIC Flow 1. Typical Substation ground grid 4/0 cu buried at 18” 10-20’ grid welded Ground Rods every 20’ typical Low R Meets the requirement of IEEE80 standard

2. Basic GIC flow

Change in GIC values vs Substation GGR under different Thevenin ratio 3. The significance of GGR value on GIC calculation GIC Thevenin Ratio= GGR GGR+Station′s Thevenin impedance Change in GIC values vs Substation GGR under different Thevenin ratio

R Obtaining GGR Value 1. Direct approach Fall of potential (FOP) Resistance Distance

Most popular method for measuring sub station ground grid impedance Fixed test frequency range from 20 hertz to 418 hertz (50Hz and 60 Hz are omitted) To achieve 95% accuracy, it requires 6.5 times the grids maximum diagonal distance. Due to the impact of other interconnected ground sources, FOP should be performed only with new installation or the substation should be de-energized

Clamp on meter

Theoretically it is able to measure the combination of substation ground grid and shield wire resistance The signal of clamp on meter is too weak to obtain an accurate measurement

Computer based grounding multi-meter

Follows fundamental principles of the FOP method There are 1 current injection probe and 6 voltage probes Require less space for probe placement and does not need de-energize the substation. AEP’s field test has experienced inaccurate results. The vendor claimed they have improved the technique but requested additional funding. So AEP has stopped pursuing this approach

Value form experience Last resort Based on experience, the value GGR range can be between 0.1 and 2 ohm. Our experience showed these default values can differ from actual values by up to 600%

Step 1: Soil Resistivity 2. Indirect approach Step 1: Soil Resistivity Step 2: Calculate GGR Wenner Method IEEE 80 USGS Survey CDEGS Simulation

Soil Resistivity 𝜌 𝜌= 𝑅𝐴 𝐿 𝜌 = the resistivity of 1 cubic meter or 1 cubic centimeter soil. The unit of 𝜌 is ohm-m or ohm-cm

Geological Survey UNITED STATES DEPARTMENT OF AGRICULTURE Rural Electrification Administration REA BULLETIN 1751F-802

Step 1: Soil Resistivity Wenner Method a = Distance between the electrodes b = electrode depth R = Reading in instrument If a >20b the soil resistivity is calculated as: 𝜌= 4𝜋𝑎𝑅 1+ 2𝑎 𝑎 2 +4 𝑏 2 − 𝑎 𝑎 2 + 𝑏 2 𝜌=2𝜋𝐴𝑅

Measurement can be taken outside of the energized station yard Can obtain site-specific, multi-layer values For reliable results, the test line must be longer than the diagonal length of the station yard.

Step 2: Calculating GGR IEEE 80 (IEEE Guide for Safety in AC Substation Grounding) A minimum value of the substation grounding system resistance in uniform soil can be estimated by means of the formula of a circular metal plate at zero depth Where: 𝑅 𝑔 Substation ground grid resistance 𝜌 Soil Resistivity in ohm-meter A Area occupied by the ground grid in 𝑚 2 𝑅 𝑔 = 𝜌 4 𝜋 𝐴 (1)

Current Distribution, Electromagnetic Fields, Grounding and Soil Structure Analysis (CDEGS) Software Soil resistivity analysis and soil structure interpretation Arbitrary soil structures; any frequency & transients

Comparison of USGS survey data and CDGES simulation results Station Name Uniform Soil Layer Resistivity From USGS Survey (ohm*m) CDGES - Wenner Method (ohm*m) GGR Calculated by IEEE 80 method (ohms) GGR From CDGES (ohms) 1 250 266.3481 1.812989 0.8 2 500 207.9795 2.145076 2.1438 3 41.43066 0.367745 724.17 4 74.35284 0.320555 0.59 5 202.9892 1.805878 4.11 6 934.514 5.662666 9.2347 7 66.67 84.61926 0.082047 0.3114 8 15.34106 0.10846 0.70856 9 1004.323 5.921809 4.0409 10 56.98275 0.142078 0.14 11 125 49.92627 0.056835 0.1086207

Comparison of different methods with per station cost Soil Resistivity Measurement Needed? Station Ground Grid Model Required? Requires De-Energized Station? Cost ($/Station) Accuracy Effective GGR Direct measurement (Direct Approach) Fall of Potential No Yes $5,000 High Clamp On $1,600 Low Computer based grounding multi-meter $17,000 Unconfirmed GGR Measurement for Effective GGR Calculation (Indirect Approach) Wenner method $4000 Survey $0 IEEE 80 CDEGS $1600

Calculating Effective GGR 1. GIC flow with shield wire It is standard AEP practice to connect station ground grids, either directly (with dedicated copper wires) or indirectly (through supporting steel structures) to the shield wires for lightning protection on high voltage transmission lines, which themselves are grounded at every transmission structure. The shield wire grounding has provided an additional path for GIC propagation

Shield wire

2. Calculating Effective GGR Effective GGR is the parallel of substation GGR and resistance of all overhead shield wires connecting to the substation ground grid. Where: 𝐺𝐺𝑅 𝑆 Substation ground grid resistance 𝑅 𝑠𝑤−𝑋 Equivalent grounding resistance of Xth shield wire 𝐺𝐺𝑅 𝐸 = 1 1 𝑅 𝐺𝐺𝑅 + 1 𝑅 𝑠𝑤−1 + 1 𝑅 𝑠𝑤−2 +… 1 𝑅 𝑠𝑤−𝑋 (2)

Shield wire is grounded through a conductor installed at each tower Shield wire is grounded through a conductor installed at each tower. It can be assumed as a series of Γ equivalent models shown below: Where: 𝑅 𝐿 nth segment shield wire resistance 𝑅 𝐺 nth segment shield wire grounding resistance

When there is only one Γ segment When there are two Γ segments 𝑅 1 = 𝑅 𝐿 + 𝑅 𝐺 𝑅 2 = 𝑅 𝐿 + 𝑅 𝐺 ∥ 𝑅 𝐿 + 𝑅 𝐺 = 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝐺 + 𝑅 𝐿 + 𝑅 𝐺 = 𝑅 𝐿 + 𝑅 𝐺 𝑅 1 𝑅 𝐺 + 𝑅 1

When there are three Γ segments: 𝑅 3 = 𝑅 𝐿 + 𝑅 𝐺 ∥ 𝑅 𝐿 + 𝑅 𝐺 ∥ 𝑅 𝐿 + 𝑅 𝐺 = 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝐺 + 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝐺 + 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝐺 + 𝑅 𝐿 + 𝑅 𝐺 = 𝑅 𝐿 + 𝑅 𝐺 𝑅 2 𝑅 𝐺 + 𝑅 2

When there are n Γ segments: 𝑅 𝑛 = 𝑅 𝐿 + 𝑅 𝐺 ∥ 𝑅 𝑛−1 = 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝑛−1 𝑅 𝐺 + 𝑅 𝑛−1 lim 𝑛→∞ ( 𝑅 𝑛 ) = lim 𝑛→∞ ( 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝑛−1 𝑅 𝐺 + 𝑅 𝑛−1 ) = 𝑅 𝐿 + 𝑅 𝐺 𝑅 𝑛 𝑅 𝐺 + 𝑅 𝑛 = 𝑅 𝑛 (3) Solving above equation gives: 𝑅 𝑛1 = 𝑅 𝐿 + 𝑅 𝐿 2 +4 𝑅 𝑔 𝑅 𝐿 2 𝑅 𝑛2 = 𝑅 𝐿 − 𝑅 𝐿 2 +4 𝑅 𝑔 𝑅 𝐿 2 𝑅 𝑛2 is less than 0 which can be excluded. Therefore the Xth shield wire equivalent grounding resistance is calculated by 𝑅 𝑛1 . After calculating all shield wire equivalent ground resistance 𝑅 𝑠𝑤−𝑋 , the effective GGR is calculated by (2)

Identify Substation List Procedure for Obtaining GGR and Effective GGR values AEP’s recommendation Identify Substation List NO GGR exist YES Soil Resistivity Wenner method Calculate Effective GGR Estimate GGR CDEGS GIC Calculation

Questions?