HCB 3-Chap 19B: All-Air_Multizone_Reddy1 Chapter 19B: ALL-AIR SYSTEMS FOR MULTIPLE SPACES Agami Reddy (July 2016) 1)CAV terminal reheat 2)CAV multizone.

Slides:



Advertisements
Similar presentations
Chapter 3. HVAC Delivery Systems
Advertisements

BUILDING AIR CONDITIONING
Heating, Ventilating, and Air-Conditioning
Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
Commercial Mechanical Requirements
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning
Foundations of Real Estate Management TM BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building.
The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.
Components of HVAC System
Heating and Air Conditioning I
Lecture 14a: Introduction to Secondary Systems
HVAC Equipment Supplement. AIR-HANDLING UNIT (AHU) AHU DAMPERS COORDINATED FOR AIR- SIDE ECONOMIZER OPERATION.
Chilled Beam Presentation
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY. “Air conditioning is the control of the humidity of air by either increasing or decreasing its moisture content.
1 Meeting ASHRAE Fundamentals, Standard 55 & 62.1 with Chilled Beams Displacement Ventilation.
HVAC Systems Overview HVAC Overview - # 1 Tom Lawrence
Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement.
Objectives Finish with Multizone Systems
AIR CONDITIONING SYSTEMS 1. All Air Systems An all-Air System is defined as a system providing complete sensible and latent cooling capacity in the cold.
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
Air Conditioning Systems
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
Lecture 16: Zone Air Paths and Air Distribution Units
Conditioning of Moist Air
Important variables Water: Air: Conversion:
Announcements Midterm Project Prepare groups of 3 to 4 students You can submit the list at the end of next class Midterm Exam 03/09/10 - In class Exam:
Lecture Objectives: Finish with HVAC Systems Discuss Final Project.
Lecture Objectives: Specify Exam Time Finish with HVAC systems –HW3 Introduce Projects 1 & 2 –eQUEST –other options.
Improved Precision Leading to Improved Energy Efficiency Edward Decker AE 790 – Intelligent Buildings June 6, 2006.
STUDY ON HVAC SYSTEM STUDY ON HVAC SYSTEM
Objectives Analyze processes in AHU and buildings.
Lecture Objectives: Clarify issues related to eQUEST –for midterm project Learn more about various HVAC - economizer - heat recovery Discuss about the.
Introduction to Energy Management. Week/Lesson 7 HVAC System Types.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
Lecture Objectives: Discuss the exam problems Answer question about HW 3 and Final Project Assignments Building-System-Plant connection –HVAC Systems.
Objectives Propose residential system related final project –Compare VAV systems with DOAS systems.
A New (Rational) Way To Condition Air (and Save Energy) AEE, Philadelphia February 18 th 2016 Andrew Mongar, President, AirGreen LLC.
EXAMINATION 3 REVIEW FORMAT & AREAS COVERED DISTRIBUTION SYSTEMS DELIVERY DEVICES UNITARY SYSTEMS HEAT PUMPS SPACE REQUIREMENTS & DESIGN CONSIDERATIONS.
HCB 3-Chap 19A: All-Air Systems_Single Zone 1 Chapter 19A: ALL-AIR SYSTEMS: SINGLE ZONE AND SINGLE DUCT Agami Reddy (July 2016) 1)Introduction and common.
Maria’s Restaurant Chapter 2 Section 9
Lecture Objectives: Discuss HW3 parts d) & e) Learn about HVAC systems
Maria’s Restaurant Chapter 1 Section 4
Objectives Finish analysis of most common HVAC Systems
Technology in Architecture
HVAC Basics Arkan Arzesh HVAC – Heating, Ventilation, Air-conditioning.
Lecture Objectives: Answer questions related to HW 4
Lecture Objectives: Finish with HVAC systems
Lecture Objectives: Discuss HW3 parts d) & e) Learn about HVAC systems
Munters DOAS, Chilled Beams and VRV
Chilled Beam Performance:
Chapter 11: DESCRIPTION OF HVAC SYSTEMS
Objectives Continue with advance HVAC systems
HCB 3-Chap 19A: All-Air Systems_Single Zone
Chapter 19B: ALL-AIR SYSTEMS FOR MULTIPLE SPACES
VAV DESIGN FOR IMPROVED INDOOR AIR QUALITY
Chapter 13B: PSYCHROMETRIC MOIST AIR PROCESSES
Frenger “Radiant” chilled beam performance at 1 Shelly St - Sydney
Lecture Objectives: Discuss HW4 parts
Mandatory Design Requirements
FBE03: Building Construction & Science
Follow-ups from Classes 8 and 9
Announcements Exam 1 Next Class (Thursday, March 14th):
Objective Revie the Cooling Cycle Learn about air distribution systems
Refrigeration & Air conditioning
Maria’s Restaurant Chapter 2 Section 9
Chapter 3B: INDOOR AIR QUALITY
Chapter 11: DESCRIPTION OF HVAC SYSTEMS
Chapter 6B: INFILTRATION CALCULATION
Presentation transcript:

HCB 3-Chap 19B: All-Air_Multizone_Reddy1 Chapter 19B: ALL-AIR SYSTEMS FOR MULTIPLE SPACES Agami Reddy (July 2016) 1)CAV terminal reheat 2)CAV multizone and dual-duct 3)VAV terminal reheat 4)Example of sizing an all-air system 5)Part-load performance of all 3 systems- solved example 6)Fan powered VAV systems: primary and secondary air flows 7)Measures to improve energy efficiency - Fan control - Outdoor air economizer - Heat recovery devices - Deck reset 8) Advantages of all-air systems

HCB 3-Chap 19B: All-Air_Multizone_Reddy2 HVAC Systems for Multiple Spaces Different zones have different sensible and latent loads and need different supply air conditions – Terminal reheat – Multi-zone system – Dual Duct System – VAV System Constant CFM, varying DBT and W Varying CFM with Fixed or varying DBT and W Wasteful in energy Saves both thermal energy as well as fan electricity

HCB 3-Chap 19B: All-Air_Multizone_Reddy3 CAV Terminal Reheat Systems CFM to each zone kept fixed, supply temps. varied with load Reheat at individual zones can be hydronic or electric Needed in summer for cooling and humidity control Needed in winter since some zones may still need cooling

HCB 3-Chap 19B: All-Air_Multizone_Reddy4 CAV Multi-Zone Units Pro: Simple and low initial cost Con: High operating cost, lack of flexibility and humidity control is not good

HCB 3-Chap 19B: All-Air_Multizone_Reddy5 Multi-zone Central Air System

HCB 3-Chap 19B: All-Air_Multizone_Reddy6 CAV Multi-Zone Dual-Duct Systems Pro: Flexibility (compared to multi-zone system) Con: High operating cost and poor humidity control

HCB 3-Chap 19B: All-Air_Multizone_Reddy7 Single duct VAV secondary system sizing (Design or peak conditions) Example 19.8

HCB 3-Chap 19B: All-Air_Multizone_Reddy8

9

10

HCB 3-Chap 19B: All-Air_Multizone_Reddy11

HCB 3-Chap 19B: All-Air_Multizone_Reddy12

HCB 3-Chap 19B: All-Air_Multizone_Reddy13

HCB 3-Chap 19B: All-Air_Multizone_Reddy14

HCB 3-Chap 19B: All-Air_Multizone_Reddy15

HCB 3-Chap 19B: All-Air_Multizone_Reddy16 Example Part Load Conditions (a) Single duct VAV system

HCB 3-Chap 19B: All-Air_Multizone_Reddy17

HCB 3-Chap 19B: All-Air_Multizone_Reddy18

HCB 3-Chap 19B: All-Air_Multizone_Reddy19 (b) Single duct CAV system

HCB 3-Chap 19B: All-Air_Multizone_Reddy20

HCB 3-Chap 19B: All-Air_Multizone_Reddy21 -VAV system outperforms the other two systems, and is very close to the ideal loads. It is the best choice since it requires the least cooling energy, a smaller heating energy and lower fan electricity use. -If we define efficiency in terms of the ideal loads, then for the VAV system it is (27.6/29) = 0.95, while that for the single duct CAV = [(27.6 Tons x 12,000 Btu/h- ton) / (37.7 Tons x 12,000 Btu/h-ton+ 93,947)= The two CAV systems are similar thermodynamically, and the differences in energy use determined are partly due to the manner we selected the hot deck temperature, the way we adjusted for the supply fan being upstream, and also due to slightly different resulting humidity levels in the space which affect the latent loads. 0.71

HCB 3-Chap 19B: All-Air_Multizone_Reddy22 Fan-Powered VAV Terminal Boxes The basic VAV system with single supply fan evolved into fan-powered VAV boxes with one fan at each box (fan power about 1/3 rd to ½ HP) with terminal reheat. The reason was that low supply flows (down to say 0.4 cfm/ft^2) compromised IAQ (poorer mixing, more stagnant air spaces, poorer filtration) Thus, fan-powered VAV maintain higher air circulation thru room at low thermal loads while retaining some of the advantages of VAV systems Primary air flow Secondary air flows Plenum return needed

HCB 3-Chap 19B: All-Air_Multizone_Reddy23 Fan powered VAV boxes allow plenum air (called secondary air) to be drawn in, thereby increasing supply air flow rate to room Fig Induction VAV system Plenum

HCB 3-Chap 19B: All-Air_Multizone_Reddy24 Fan-Powered VAV Terminal Boxes The secondary air flow is adjusted so that the total supply air flow is kept at the design flow Especially used in Perimeter zone In colder climates, terminal heat has to be supplemented by baseboard heaters Three types of designs evolved which allowed higher room supply flow rates without adversely impacting thermal and fan energy: - Induction type - Series fan powered box (consumes slightly more energy) -Parallel fan powered box (consumes less energy) (good equip manufacturer web site to check is TITUS) Nowadays VAV terminal fans have ECM (electronically commutated motors) which are very efficient and consume little energy

HCB 3-Chap 19B: All-Air_Multizone_Reddy25 The two types of fan powered VAV boxes Fan located within primary airstream and runs continuously when zone is occupied Fan located outside primary airstream- this allows intermittent fan operation -Series: fan runs continuously -Parallel: fan intermittent Fig

HCB 3-Chap 19B: All-Air_Multizone_Reddy26 FIGURE Two zone space conditioned by a series fan powered VAV system Series Fan Powered VAV

HCB 3-Chap 19B: All-Air_Multizone_Reddy27 Flow Characteristics Series fan powered Parallel fan powered Almost constant air flow to space- can be used for both perimeter and interior spaces Intermittent fan operation- Primary air modulated in response to cooling demand primary air used for perimeter zones with auxiliary hot water or electric heat

HCB 3-Chap 19B: All-Air_Multizone_Reddy28 All-Air Systems: Energy Efficiency Measures 1)Use VAV instead of CAV 2)Energy efficient operation: fan control 3)Economizer operation and benefits 4)Heat recovery devices 5)Via deck temp reset ( The temperature set points of the heating and cooling coils are changed with changes in outdoor DBT (on which the building loads depend)

Fan Control- Three different commonly used methods of controlling fan speed in VAV systems- the VSD is most energy efficient but most costly HCB 3-Chap 19B: All-Air_Multizone_Reddy29

HCB 3-Chap 19B: All-Air_Multizone_Reddy30 Outdoor Air Economizer operation Basic concept: Increase the outdoor air flow intake under certain outdoor air conditions so that “free cooling” brought in can reduce active cooling -Two types of economizers: - sensible - enthalpy In any case, the outdoor air flow has to be modulated properly, otherwise the benefit of reduced energy is lost FIGURE Enthalpy and temperature economizer operating ranges. The constant- enthalpy line represents the room enthalpy criterion.

HCB 3-Chap 19B: All-Air_Multizone_Reddy31 About 65 F FIGURE Outside airflow characteristic for fixed-volume system with economizer.

HCB 3-Chap 19B: All-Air_Multizone_Reddy32 Outdoor DBT when outdoor mass flow reaches its minimum value: - Return air temperature from a zone is 25° C (77° F) -At least 25 percent outdoor air is required at all times to meet ventilation requirements, -design cooling system air supply temperature is to be 13° C At which outdoor temperature will outdoor inlet damper be at its minimum setting? Example 19.11: Building process—The economizer

HCB 3-Chap 19B: All-Air_Multizone_Reddy33 Heat Recovery Devices from Exhaust Air Plate-type heat exchanger

HCB 3-Chap 19B: All-Air_Multizone_Reddy34 FIGURE Sketch of the HVAC system with energy recovery unit for Example Example 19.12: Energy benefit of exhaust air energy recovery Assume a building with 100% outdoor air. The exhaust air temperature is always kept constant at 75 o F year-round. The building supply temperature is assumed to be 55 o F and 100% saturated during summer and 90 o F during winter operation. The ventilation and exhaust air streams are both equal to 10,000 cfm. (a) Determine the capacity of the cooling and heating coils without energy recovery under the following peak or design outdoor air conditions: -winter: 40 o F and 40% RH -summer: 98 o F and 40% RH (b) Determine the capacity of the cooling and heating coils when an energy recovery unit of effectiveness of 0.6 is included.

HCB 3-Chap 19B: All-Air_Multizone_Reddy35

HCB 3-Chap 19B: All-Air_Multizone_Reddy36

HCB 3-Chap 19B: All-Air_Multizone_Reddy37 Table 19.4 Advantages/Disadvantages of All-Air Systems AdvantagesDisadvantages Best choice for close control of zone temperature and humidity May limit the extent to which energy use can be reduced in low or zero energy buildings Major equipment is centrally located allowing for nonintrusive maintenance Duct space requirements add to building height Providing heating and cooling in different zones simultaneously is easily achieved Air balancing is difficult Can handle space churn to some extent May be more expensive than other secondary systems in first cost and operating cost Seasonal changeover is easily achieved by HVAC controls Noise in fan operation may be a problem in certain types of spaces Well suited for air-side economizer, heat recovery and large outside air requirements May not be satisfactory for perimeter spaces in cold locations No drain pipe or power wiring in occupied areas Difficult to correct indoor conditions in individual rooms if improperly designed initially Less property damage if air ducts leak May lead to shoddy construction since air leakage from ducts causes no visible damage and so may be overlooked

HCB 3-Chap 19B: All-Air_Multizone_Reddy38 Outcomes Knowledge of the different types and working principles of CAV multizone systems Be able to be analyze problems involving CAV and VAV multizone systems under peak design conditions and under part load operation Knowledge of the different types, operating principles and features of fan-powered VAV systems Familiarity with differed ways by which energy efficiency can be enhanced in all-air systems Be able to analyze the energy benefits of outside air economizer cycles, and heat recovery devices Understanding the advantages and disadvantages of all-air systems