Design of starters for AC motors C.K. PITHAWALA COLLAGE OF ENGINEERING & TECHNOLOGY Group no - 3 Name Enrolment no Chaudhari Darshan M.130090109007 Chaudhari.

Slides:



Advertisements
Similar presentations
Chapter 13 AC Motors. Chapter 13 AC Motors Objectives Discuss the operation of an induction motor. Identify and explain the operation of various three-phase.
Advertisements

Three-Phase AC machines
Motors & Motor Starters
Single Phase Induction
Induction Motor Review
Contactor, Relays and Overloads
Components & Symbols Used in Electrical Circuits
Lesson 15: Dc Motor Control Components and Diagrams
Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams
SECTION 4 ELECTRIC MOTORS UNIT 19 MOTOR CONTROLS.
Section 4: Electric Motors
E2 Motors and Motor Starting
Vigyan Ashram, Pabal. Starter is a device which connects with motor in series to decrease the current at starting time and increase current after starting.
AC MOTOR INDUCTION MOTOR.
Lecture 17Electro Mechanical System1 Locked-rotor torque  To produce a starting torque in a single-phase motor, we must somehow create a revolving field.
Department of Electrical and Computer Engineering
Motor ELECTRICAL ENERGY Mechanical Energy.
INTRODUCTION.
Motor Start Theory ME00107A.
PRESENTATION ON INDUCTION MOTOR
Induction Motors Prepared By : PRAGNESH, MEET, SAGAR, SAAVAN, KANISH
Induction Motors.
Three-Phase AC machines
STARTING OF 3PH INDUCTION MOTOR
Electric Machine Introduction
Magnetic field due to an electric current
INDUCTION MOTOR.
Self Switching Power Supply. Introduction Self Switching Power Supply  Embedded system requires a regulated power supply.
Squirrel cage induction motor; (b) conductors in rotor; (c) photograph of squirrel cage induction motor; (d) views of Smokin’ Buckey motor: rotor, stator,
INTRODUCTION Like any electric motor, a 3-phase induction motor has a stator and a rotor. The stator carries a 3-phase winding (called stator winding)
Prepared by:- Chandan pathak ( ) Utpal rathod( ) Hitendra vyas( )
AC Machines. BOOSTER Basic Function:- -Sometimes when we use electrical power we need different voltage level to main supply. It is provided by Booster.
1 Teaching Innovation - Entrepreneurial - Global The Centre for Technology enabled Teaching & Learning, N Y S S, India DTEL DTEL (Department for Technology.
Elements of Electrical Design HASMUKH GOSWAMI COLLEGE OF ENGINEERING
ACTIVE LEARNING ASSIGNMENT TOPIC NAME :- DC MOTOR STARTERS ELEMENTS OF ELECTRICAL DESIGN ( ) AY Course co-ordinator:- SAMIR B PATEL PREPARED.
Shri Navsari Paschim Vibhag Koli Samal Kalyankari Trust Sanchalit MAHATMA GANDHI INSTITUTE OF TECHNICAL EDUCATION & RESEARCH CENTER NAVSARI NPE Campus,
Presentation of ELECTRIC MACHINES Title: Single Phase Motors By: Rahul Khanna{ }EC3 rd Sem Guided By: Prof. Ravi Patel.
Synchronous Motors Introduction An alternator may operate as a motor by connecting its armature winding to a 3-phase supply. It is then called a synchronous.
Three-Phase AC machines
Push Button Station and Relay
En. No. : En. No. : Div. : 3 rd EC Sub. : EM topic : Starter.
Chapter 13 – AC Motors AC motors convert AC electrical energy to Mechanical energy.
THREE-PHASE INDUCTION MOTOR
Industrial Star Delta Starter For a 3-Phase Induction Motor
Unit – IV Starting and Speed control of Three phase Induction motor
Single Phase Induction
DC Generators.
Electric Machine Induction Motor
Three-Phase AC machines
AC Motors AC motors convert AC electrical energy to Mechanical energy.
Principle of Operation
Electric Machine Introduction
Three-Phase AC machines
AC and DC motors.
Three Phase Induction Motors
PRESENTED BY:AMOD SHAKYA. Power Circuit –connectoin with motor using contactor Control Circuit-using switch make a holding circuit.
ACTIVE LEARING ASSIGNMENT
INDUCTION MOTOR.
Three-Phase AC machines
Presentation of ELECTRIC MACHINES Title: Single Phase Motors By: Rahul Khanna{ }EC3 rd Sem Guided By: Prof. Ravi Patel.
Induction Motor (Asynchronous Motor)
Why is starter necessary for a three-phase induction motor?
Principle of Operation
Chapter 36 Single – Phase Motors. Chapter 36 Single – Phase Motors.
Topic 3: Connecting and Starting Three Phase Induction Motors
Induction Motors (Lecture 1&2)
By Ashvani Shukla Manager(C&I) BGR ENERGY
Presentation transcript:

Design of starters for AC motors C.K. PITHAWALA COLLAGE OF ENGINEERING & TECHNOLOGY Group no - 3 Name Enrolment no Chaudhari Darshan M Chaudhari Hardik D Chavda Mayur N Joshi Ankur S Pathak Dhaval K Guided By: Prof. Chetan K. Lad Prof. Hetal Patel

 Function Of Starter  The device which is used to start the 3-phase induction motor is called a starter.  Necessity Of Starter  Function of starter is to limit the starting high current to a safe value.  The magnitude of E2 depends upon the flux linking with the rotor conductors and its relative speed. The strength of the rotor flux depends upon the applied voltage. At the instant of applying rated voltage to the stator winding, rotor is stationery and as such the ship is unity. So if full rated voltage is given to the stator winding, then the magnitude of the emf induced in the rotor conductors will be high, because the relative speed between the rotor conductors and stator revolving flux is very high i.e. equal to the synchronous speed of the stator flux. Further the rotor conductors are short circuited and thus have low impedance.  Hence, the current drawn by the stator winding or motor is very large, approximately 5 to 7 times the full load current.

 Direct- on- line starter (D.O.L. starter)  Manual primary resistance starter  Primary resistance automatic starter  Automatic auto transformer starter  Manual star – delta starter  Automatic star – delta starter  Manual rotor resistance starter  Automatic rotor resistance starter

Fig (1) : DOL starter L1, L2, L3 Lines M Main contacts MA Auxiliary or maintaining contact S1 START PUSH button S2 OFF PUSH button OLC Overload relay coil OL Overload relay contact C Magnetic coil or operating coil

 A starter which connects a motor directly across the line is called a Direct- O3-Line starter, i.e. in this method, the motor is connected by means of a starter across the full supply voltage.  Fig. (1) shows a wiring diagram of a push button type Direct-On-Line starter, which is commonly used.  It is very simple, inexpensive, easy to install and maintain.  It consists of a ‘START’ and ‘OFF’ push buttons, Electromagnetic contactor and overload relay.  Switching by this starter is directly from line without any provision to control the starting current i.e. there is no device to reduce the starting current in this starter.

 Operation  When the START push button ‘S1’ is pressed, the circuit is completed from L1 through S2, S1, C (operating coil) and normally closed contacts (O.L.) of the overload relay to L2.  i.e. L1 – S2 – S1 – C - O.L. – L2  Thus, the coil C is energized, and it closes contacts M and connects the motor across the line.  An Auxiliary or Maintaining contact MA is used to keep the holding or operating coil energized after the finger’s removed from the ‘’START’ push button S1.  When the ‘OFF’ push button ‘S2’ is pressed, the supply through the contactor coil C is disconnected.Since the coil C is de-energised, the main contacts M are opened.  The supply to the motor is disconnected and the motor stops. Fig (2) Control Circuit

 In this starter, there is no current limiting device to limit the starting high current, only protection against under voltage and overload is provided.  Under Voltage Protection  When the supply voltage is below a certain value or in the event of failure of  power supply, the coil C is de-energized, therefore motor will be disconnected'  from the main supply.  Overload Protection  The motor is protected against overload by a thermal overload relay which open circuits. The control circuit when over load occurs.  In case of an overload on the motor, overload relay coils are energised. The normally closed contacts DOL Is opened and the contactor coil C is de-energized the motor from the supply.  In this method of starting. The rate of temperature rise is high and motor may get damaged if the starting period is large, which may be due to excessive load or excessive voltage drop in the supply lines.  So small size squirrel cage inductor. Motors up to 5 kW may be this method.

Fig(1) : Manual Primary resistance starter

 In this method of starting of 3- phase induction motor, primary resistances are connected in all the three phase of the stator winding, as a result the applied voltage across the stator winding at the instant of starting is reduced to a fraction K of the rated voltage of the motor.  Therefore the initial high starting current will also reduce by the same fraction.  The purpose of primary or starting resistors is to drop some voltage and hence reduce the voltage applied across the motor terminals.  The torque developed by the motor is directly proportional to the square of applied voltage, so if the voltage applied across the motor terminals is reduced by fraction K, but the starting torque is reduced by a fraction of that obtainable with direct switching.  The drawbacks of this method of starting is reduced starting torque and large power consumption and heating of resistors.  Hence this method of starting is used for small motors only.

L1, L2, L3 Lines S1,S2 Start contents SA Auxiliary or maintaining contact Cs Magnetic coil or operating coil for start contacts Cr Magnetic coil for running contacts TRc Time delay relay coil TR Time delay contact R1, R2, R3 Running contacts R1, r2, r3 primary resistors OLC Overload relay coil OL Overload relay contact PB1 START push button PB2 STOP push button Fig (1) : Primary diagram of a primary resistance automatic starter

 Operation  When the ‘START’ push button PB1 is pressed, the circuit is completed from L1 through PB2, PB1, coil Cs and normally closed contacts (OL) of the overload relays to line L2.  i.e. L1 - PB2 – PB1 - Cs – OL – L2  Thus, the coil Cs ( operating coil for start contacts) is energized and it closes all starting contacts S1, S2, S3 and SA.  The auxiliary or maintaining contact SA is used to keep the operating coil Cs energized after the finger id removed from this START push button PB1.  The primary resistors r1, r2, and r3 in series with line will reduce the starting current drawn from the line.  Also, at the same time, the coil TRc of a time delay relay connected across a and b is energized and set the time mechanism.  After a definite time delay, contact TR close and circuit is completed through operating coil CR.  Pressing the ‘STOP’ push button de-energizes all contactors and thus the supply to the motor Is disconnected and the motor stops.

 This coil CR becomes energized, close the run contacts.  The primary resistors now bypassed, thus connected the motor across the line.  Pressing the ‘STOP’ push button de – energizes all contactors and thus the supply to the motor is disconnected and the motor stops.

Fig (1) : Manual auto transformer starter

 In this method, 3-phase auto transformer with fixed tappings is used to obtain reduced voltage for starting the 3-phase induction motors. Normally 50% to 60% tappings can be used to obtain a safe value of starting current.  Thus, 50% to 60% of the rated voltage is applied at starting and the auto transformer is cut out of the motor circuit, when the motor has picked up the speed about 70% to 80% of the normal speed.  Hence, during normal running condition, the voltage across the stator winding is of rated value. Fig (1) shows the schematic diagram of. Manual auto transformer starter.  One problem that occurs with a primary resistor starter is that all the voltage that is dropped through the resistors is turned into heat. The amount of heat may become very large and cause problem, Auto transformer starter is able to provide  The same type of voltage reduction without building up large amount of heat. Further in this method of starting, the voltage is reduced by transformation and not by dropping voltage in the resistors and hence the current and power drawn from the supply are also reduced in comparison to primary resistance starter.  This starter also provides the large amount of torque per ampere of line current. This method are use in both star and delta connected motors.

L1, L2, L3 Lines S1,S2 Start contents SA Auxiliary or maintaining contact Cs Operating coil for Start contacts R1, R2, R3 Running contacts Cr Magnetic coil or operating coil for start contacts ST start contacts Cst Operating coil for start contacts TR Pneumatic timer T.O. Time opening Contact T.C. Time closing contact OLC Overload relay coil OL Overload relay contact PB1 START push button PB2 STOP push button Fig (1) : Automatic auto transformer starter

 Operation  When the ‘START’ push button PB1 is pressed, the circuit is completed from L1 through OFF push button PB2, PB1, operating coil Cs and normally closed contacts (OL) of the overload relays to line L2.  i.e. L1 – PB2 – PB1 – Cs - OL – L2  Thus, the coil Cs ( operating coil for start contacts) is energized and it closes all the starting contacts S1, S2, S3 and SA.  Further, on staring pressing the ‘START’ push button PB1,at the same time, one alternative path is completed as follows:  L1 - PB2 – PB1 – T.O. - CsT – OL – L2  Hence, start coil CST et energized, which closes start contacts ‘ST’. Control Circuit

 The star contacts connected the three coil ends of the auto transformer together to from the start point and auto transformer connected in series with the motor.  Thus the voltage is reduced.  After a per – determined time, the pneumatic timing relay opens the star contactors and simultaneously closes time closing switch T.C.  At the same time operating coil CR get energized by following path:  L1 – PB2 - Auxi. Contact SA – T.C. – ST – CR – OL - L2  All the run contacts (r1, r2 and r3) are than closed placing the motor directly across the line and motor runs with full supply voltage.  Pressing the OFF push button PB2 or in case of an overload on the motor de –energized all contactors and therefore disconnect the motor from the supply line.

Fig (1) : Manual Star – Delta Starter

L1, L2, L3 Lines S Start contents Cs Operating coil for Start contacts D Delta contacts Cd Operating coil for Delta contacts M Line contacts C M operating coil for contacts M TR Pneumatic timer TO Time opening Contact TC Time closing contact OLC Overload relay coil OL Overload relay contact PB1 START push button PB2 STOP push button Fig (1) : Wiring diagram and control circuit of automatic star-delta starter

 The operating coil CM get energized by following path:  ‘ L1 – PB2 – PB1 – CM – OL – OL – OL – L2’  At the same time, the operating coil Cs get energized by following path :  ‘ L1 – PB2 – PB1 – TO –D –CS – OL – OL – OL – L2’  The operating coil CD is energized by following path  'L1 - PB2 –MA – TC – S – CD – OL – OL – OL - L2'  Pressing the OFF PUSH button, de-energizes all contactors and disconnects the motor from the line.

3 – Phase Ac Supply Fig (1) : Manual rotor resistance starter

 This method of starting Is only used for slip ring induction motors because in case of squirrel cage induction motors, rotor has copper bars, which are short circuited at both ends.  Hence it is not possible to add any external resistance in the rotor circuit.  In case of slip ring induction motors, rotor has 3-phase star connected winding whose terminals are connected to three respective slip rings.  In rotor resistance starter the three terminals of the rotor winding are connected to a variable external resistances through slip rings. Full supply voltage is applied across the stator. Resistances are fully in the circuit at starting, so that the starting current is reduced.  The External variable resistance connected in each phase of the rotor circuit not only reduces the current at starting but increases the starting torque also due to improvement in power factor.  The rotor circuit resistance is gradually cut out, as the motor speeds up and during normal running condition, the rotor circuit resistance is completely cut out and the sliprings are short circuited.

Fig (1) : Manual rotor resistance starter

Fig. (2) Control circuit  L1, L2, L3 Lines  S Starting contacts  Cs Operating coil or Magnetic coil for starting contacts  R Running contacts  CR Operating coil for running contacts  CTR Time delay relay coil  TR Time delay relay contact  SA Auxiliary starting contact  OLC Overload relay coil  OL Overload relay contact  PB1 START push button  PB2 OFF push button

 Operation  Fig (1) shows the wiring diagram of an automatic rotor resistance starter which is commonly used for starting slip ring induction motors and Fig (2) shows its control circuit. This starter consists of start and run contactors, time delay relay, overload relays, START and OFF push buttons.  When the START push button PB, is pressed, the circuit is completed from line L1 through OFF push button PB2, PB1 operating coil Cs and normally closed contacts of overload relays of L2.  Therefore, the operating coil Cs is energized, closing the starting contacts S and auxiliary contact SA and the motor starts with external starting resistances in rotor circuit which will limit the starting current and improve the starting torque.  At the same time, the coil CTR of a time delay relay is also energized and set the timing mechanism.

 After a predetermined time, contact TR will close and the operating coil for running contacts CR will energized through following path :  ‘L1 – pb2 –SA –TR –CR – OL – OL – OL – L2’  Thus, coil CR is energized and causes running contacts R to close and short circuit the starting resistances. Thus external starting resistances get short circuited during running condition and motor runs with full rated speed.