5SL4 10 kA / 5SL6 6 kA miniature circuit breakers
Features 2 Swiching capacity, characteristics and voltages 10 Technical features 11 Tripping characertistics 12 Dimension - symbols 14 Bus mounting 15 Additional components 16 Selection and order number overview 17
Features Easy-to-read, colored switch position indicator integrated in the handle Actuators in gray Optimum reach-round touch protection Removal from the busbar network requires no tools Consistent busbar concept throughout the Siemens miniature circuit breaker range 5SL4 MCB series
Features 5SL6 MCB series 5SL4 MCB series Switching capacity of 6000 A Easy and quick mounting of auxiliary switches and fault signal contacts Switching capacity of 10000 A Easy and quick mounting of auxiliary switches and fault signal contacts, AA, UA, RC unit, AFDD
5SL4 10 kA / 5SL6 6 kA miniature circuit breakers Ergonomic handle Ergonomic handle and housing contours for user-friendly switching Comfortable manual releasing of the miniature circuit breaker from the busbar without tools
5SL4 10 kA / 5SL6 6 kA miniature circuit breakers Optimum terminal version Rectangular terminal version for accommodating pin busbars with conductors from 0.75 to 35 mm² for easier insertion of conductors Optimum reach-round touch protection
5SL4 10 kA / 5SL6 6 kA miniature circuit breakers Consistent busbar concept Consistent busbar concept throughout the Siemens miniature circuit breaker range Easily accessible and safe line connection and a larger wiring space
5SL4 10 kA / 5SL6 6 kA miniature circuit breakers Removal requires no tools Replacement of a device from the busbar-mounted assembly requires no tools
5SL4 10 kA / 5SL6 6 kA miniature circuit breakers Mounting of additional components 5SL miniature circuit breakers are suitable for the easy and quick mounting of auxiliary switches and fault signal contacts 5SL4: 5ST301… auxiliary switches (AS) 5ST302… fault signal contacts (FC) 5ST303… shunt trips (ST) 5ST304… undervoltage releases (UR) 5SM60… AFD Unit 5ST36.., 5ST37.. busbars are mountable.
Switching capacity, characteristics and voltages 5SL6 miniature circuit breakers for a switching capacity of 6000 A (IEC EN 60898-1) 5SL4 miniature circuit breakers for a switching capacity of 10 000A Tripping characteristics: B, C and D 1P, 230/400 V 1P+N, 230 V 2P, 400 V 3P, 400 V 3P+N, 400 V 4P, 400 V 5SL6 MCB series 5SL4 MCB series
Technical features 5SL6 MCB series 5SL4 MCB series Technical features Standards: EN60898-1 Rated voltage: 230/400 V AC Sealable handle Degree of protection: IP 40 Mounting position: any Ambient temperature: -25ºC … +55ºC Climate-resistant: according to IEC 60068-2-30 Pollution degree: 2 Rectangular terminal version for accommodating pin busbars together with conductors from 0.75 to 35 mm² 1 to 4-pole version Touch protection Rated current: 0.3 A – 63 A 5SL6 MCB series 5SL4 MCB series
Tripping characteristics type "B" and type "C" Tripping characteristic type "B" Tripping characteristic type "C" Miniature circuit breakers with tripping characteristic "B" are designed for universal use in socket outlet circuits and lighting circuits Verification of personal safety according to DIN VDE 0100-410 is not required. Miniature circuit breakers with tripping characteristic C are preferred in lamp circuits and motor circuits with high starting currents
Tripping characteristic type "D" For circuits with equipments wich generates strong impulse like transformers or magnetic values
Dimensions – symbols Dimensions Symbols 1P 1P+N 2P 3P 3P+N 4P
Bus mounting Bus mounting Bus mounting with standard busbars of 1-, 2- and 3-pole type in finished lengths and sold by the meter for customized cutting-to-length. Also in the standard range are busbars for bus mounting when auxiliary switches or similar are fitted.
Additional components Handle locking device Adapted handle locking device suitable for 5SL, 5SY, 5SJ and 5SP For locks with a diameter from 3 mm to 6 mm Padlock for 5ST3 801 and 5ST3806 handle locking device
Selection and order number overview Examples 5SL4110-6 MCB 230/400 V; 10 kA 1-pole; B10 5SL4116-6 MCB 230/400 V; 10 kA 1-pole, B16 5SL4120-6 MCB 230/400 V; 10 kA 1-pole; B20 Structure of the order number system Example: 5SL4316-7 Characteristic Number of amps Number of poles Series and type of miniature circuit breaker Miniature circuit breakers from 0.3 A to 63 A with "B, C, D" characteristic