Presentation is loading. Please wait.

Presentation is loading. Please wait.

TRANSIENT STABILITY ENHANCEMENT OF A HYBRID POWER SYSTEM

Similar presentations


Presentation on theme: "TRANSIENT STABILITY ENHANCEMENT OF A HYBRID POWER SYSTEM"— Presentation transcript:

1 TRANSIENT STABILITY ENHANCEMENT OF A HYBRID POWER SYSTEM
D.P. KOTHARI, RAMNARAYAN PATEL and T.S. BHATTI Centre for Energy Studies, Indian Institute of Technology, New Delhi (India) INTRODUCTION ILLUSTRATIVE SYSTEM EXAMPLE SIMULATION OF POWER SYSTEM AND CONTROL SCHEMES RESULTS AND DISCUSSIONS CONCLUSION

2 INTRODUCTION The Swing Equation: Generation side control:
fast valving sudden decrease in turbine mechanical power input Load side control: braking resistor increased generator power output due to artificial load

3 ILLUSTRATIVE SYSTEM EXAMPLE

4 SIMULATION OF POWER SYSTEM AND CONTROL SCHEMES
Brake insertion: immediately after fault clearing Brake removal criterion: i = 0  Fig.2: Valve stroke characteristic curve

5 SIMULATION RESULTS Fig. 3: Rotor angle swing (gen. # 3) with different control schemes, for fault at P1 and F.C.T.=0.28 sec. Fig. 4: Rotor angle swing (gen. # 1) with different control schemes, for fault at P1 and F.C.T.=0.28 sec.

6 SIMULATION RESULTS Fig. 5: Terminal voltage variation (gen. # 1) with different control schemes, for fault at P1 and F.C.T.=0.28 sec. Fig. 6: Rotor angle swing (gen. # 3) with different control schemes, for fault at P2 and F.C.T.=0.26 sec.

7 SIMULATION RESULTS Fig. 7: Rotor angle swing (gen. # 1) with different control schemes, for fault at P2 and F.C.T.=0.26 sec. Fig. 8: Rotor angle swing (gen. # 3) with different control schemes, for fault at P3 and F.C.T.=0.17 sec.

8 SIMULATION RESULTS Fig. 9: Terminal voltage variation (gen. # 3) with different control schemes, for fault at P3 and F.C.T.=0.17 sec.

9 CONCLUSIONS Transient stability performance of a typical 3-generator, 9-bus hybrid power system, with one small hydro and two steam units, has been carried out A coordinated fast valving and braking resistor control is proposed. Control laws for the operation of fast valving and braking resistor, are fairly simple and need very less computation and measurement. Simulation results show that the coordinated control substantially improves the fault clearing time. The improved generator terminal voltage profile and damping of the rotor angle swings were also observed. The coordinated control from both load and generation sides reduces the stress on the part of an individual control.


Download ppt "TRANSIENT STABILITY ENHANCEMENT OF A HYBRID POWER SYSTEM"

Similar presentations


Ads by Google