3 SELF DIAGNOSIS MDS Outdoor Unit Compressor Protection
High & low pressure switch / Sensor Overload protection input from compressor Monitoring Point (Temperature Sensor) Compressor Discharge Compressor Suction Ambient Temperature Coil Inlet Coil Coil Outlet Compressor

4 7 segment display on outdoor PCB
SELF DIAGNOSIS 7 segment display on outdoor PCB

5 7 Segment Display on outdoor PCB
SELF DIAGNOSIS 7 Segment Display on outdoor PCB Indicator Code

6 SELF DIAGNOSIS LED of outdoor PCB ERROR Code

7 SELF DIAGNOSIS MDS Indoor Unit Temperature Sensor Coil Inlet Coil
Coil Outlet Return air

8 LCD Indicator of controller
SELF DIAGNOSIS LCD Indicator of controller ERROR Code

9 SELF DIAGNOSIS ERROR Code LED Indicator of Receiver
Indication light twinkle related to malfunction code :

10 TROUBLESHOOTING Frequent Malfunction for Commissioning – Communication Error Symptom: For A series Outdoor, the 7 segment display C- For B series Outdoor, the 7 segment display EC78 For Wired Handset, the LCD panel display FC For LED Display, the Heat LED will be blinking Potential Caused A: The communication chip MAX485 of outdoor unit is damaged (Possibility is low. The Communication is tested before ship out) Solution: To replace the MAX485 chip Potential Caused B: The communication wires A/B get crossed each other or not connected (Most common caused) Solution: Check on all wiring. Ensure proper tighten and the polarity is consistent.

11 TROUBLESHOOTING Frequent Malfunction for Commissioning – Communication Error (cont’) Potential Caused C: Shielding wire is connected to ground terminal (not grounded). (Long wiring and running the communication wire together with power supply wire will cause this to happen) Solution: Ensure the shielding wire is only grounded at the outdoor unit. Do not run the communication wire with the power supply wire together. Potential Caused D: Address of indoor are wrongly set (Caution, the indoor address must be start at ‘0000’ and follow. Do no jump the number.) Solution: Make sure the address start from ‘0000, did not skip any address and no repetition.

12 TROUBLESHOOTING Frequent Malfunction for Commissioning – Specific Indoor Communication Error Symptom: For A series Outdoor, the 7 segment display CX (X – Indoor Unit Number) For B series Outdoor, the 7 segment display ECXX (XX – Indoor Unit Number) For Wired Handset, the LCD panel display FC For LED Display, the Heat LED will be blinking Example: For A series Outdoor, the 7 segment display C3 (Indoor Unit Number 4 not communicating) For B series Outdoor, the 7 segment display EC03

13 TROUBLESHOOTING Frequent Malfunction for Commissioning – Specific Indoor Communication Error (cont’) Potential Caused A: Indoor Unit PCB has no power supply. (Possible the power supply to the indoor had been turned off) Solution: Check the power supply of the indoor power. Potential Caused B: Indoor Unit address error. (Possible the indoor address is not set or duplication) Solution: Check the indoor model address.

14 TROUBLESHOOTING Frequent Malfunction for Commissioning – Specific Indoor Communication Error (cont’) Potential Caused C: Indoor Unit PCB malfunction. (Possibility is low. PCB communication is tested before ship out.) Solution: Replace with another PCB and check the communication Potential Caused D: Wrong quantity of indoor set. (Possible the quantity of indoor unit set in the outdoor PCB is not tally with the actual indoor quantity) Solution: Check the quantity of indoor unit setting at the outdoor PCB.