Objectives More HVAC systems - Sorption (absorption) chillers

Similar presentations


Presentation on theme: "Objectives More HVAC systems - Sorption (absorption) chillers"— Presentation transcript:

1 Objectives More HVAC systems - Sorption (absorption) chillers
- Economizers (Psychrometrics) and control - Desiccant systems (Psychrometrics)

2 Absorption Cycle Strong vacuum Refrigerant: water Absorber: lithium bromide Replace compressor

3

4 Absorption Cycle Water is typical refrigerant
Strong vacuum - ~0.116 psi or MPa Boiling point of water? Differences from vapor compression No compressor Chemical (e.g. LiBr - hygroscopic) Absorbs water vapor turns it into a liquid Regenerated by removing water Requires heat

5 Absorption Chillers and Cogeneration
Cooling cycle Rankine cycle 3 TH 4 2 1 Tc or boiler

6 Economizer Economizer (fresh air volume flow rate control)
Controlled device is damper - Damper for the air - Valve for the CC fresh air damper mixing recirc. air T & RH sensors

7 Economizer – cooling regime
How to control the fresh air volume flow rate? If TOA < Tset-point → Supply more fresh air than the minimum required The question is how much? Open the damper for the fresh air and compare the Troom with the Tset-point . Open till you get the Troom = Tset-point If you have 100% fresh air and your still need cooling use cooling coil. What are the priorities: - Control the dampers and then the cooling coils or - Control the valves of cooling coil and then the dampers ? Defend by SEQUENCE OF OERATION the set of operation which HVAC designer provides to the automatic control engineer % fresh air 100% Minimum for ventilation

8 Economizer – cooling regime
Example of SEQUENCE OF OERATIONS: If TOA < Tset-point open the fresh air damper the maximum position Then, if Tindoor air < Tset-point start closing the cooling coil valve If cooling coil valve is closed and T indoor air < Tset-point start closing the damper till you get T indoor air = T set-point Other variations are possible

9 Sensible and Enthalpy and Desiccant wheels

10 Desiccant wheel Figure 3 – A desiccant-based cooling system combined with regenerative heat exchanger, vapor compression cooling, and evaporative humidifier (hybrid system).