Presentation is loading. Please wait.

Presentation is loading. Please wait.

INAlA TECHNOLOGIEs Installation Training:

Similar presentations


Presentation on theme: "INAlA TECHNOLOGIEs Installation Training:"— Presentation transcript:

1 INAlA TECHNOLOGIEs Installation Training:
ECS (Equipment Communications System) ECS-L2 Commissioning Version 1.0

2 Commissioning: ECS-L Procedure
ECS-L2 Commissioning Commissioning: ECS-L Procedure

3 ECS-L2 - commissioning SAM Training ECS-L2 Communication Cable:
A “USB Printer cable” must be used between the ECS-L2 and the computer. Once Connected open the “ECS2 ECT” software. Click on USB and Login Port Settings SAM2 & Access Control = Physical port 1 – Virtual Port 301, Baud rate 9600 L&G = Physical port 2 – Virtual Port 309, Baud rate 19200 SAM1.5 = Physical port 3 – Virtual Port 310, Baud rate Rectifier = Physical port 4 – Virtual port 302, Baud rate depends on type of Rectifier. Generator = Physical port 5 – Vittual port 304, Baud rate depends on type of Generator. LED Indications LED 1 on = GSM Network found and Logged onto GPRS Setting up of the unit: Power unit on Connect using the “ECS2” ECT Set-up the communication ports for the devices you are connecting to it Set-up the Sever IP address and APN – Customer Dependent Click on “update unit” after making a change to save the configuration to the unit. Check that LED1 is on to indicate that it is logged onto GPRS and the APN – Customer Dependent. Call to commission site with representative. *Note – Check following slide for detail information of above procedure SAM Training

4 ECS-L2 – Physical Port Numbers
* The physical port that is connected to the SAM must be selected as the “Event PORT” PORT 1 - RS485 PORT 2 – Isolated RS485 PORT 3 - RS232 USB PORT – ECS2 ECT Port GND +12vdc 12VDC Power PORT 4 – RS232 PORT 5 - RS232 SAM Training

5 Software for ECS-L2 (Equipment Communication Controller-light)
Communication Controller Software (ECS2 ECT): ECT Version is viewed on the top left corner as indicated with the yellow circle EG: “ECS2 ECT V 1.4” Firmware Version is viewed on the bottom as indicated with the Red circle EG: “Build: 1.4” IP address is automatically allocated to sim card and is displayed. Enable: GPRS Modem Input APN name – Customer Dependent Input Server IP for applicable operator and UDP - Customer Dependent Set Port configuration Click on Update unit Wait for unit to complete updating SAM Training

6 Equipment Communication Controller – Port & server allocations
Virtual Port Allocations 301 SAM2 or SAM3 and Access Control 302 Rectifier A 303 Rectifier B 304 Generator 305 AVR 306 BMON 307 Fuel Cell 1 308 Fuel Cell 2 309 Energy Meter / Fire System 310 SAM 1.5 REC Vodacom Server Name Vodacom UDP Server IP UDP Server Port ZABLV CEN 299 ZABLV EAS ZABLV LIM ZABLV MPU ZABLV SGC ZABLV SGS ZABLV WES NGA Existing Server Telkom Server Name Telkom UDP Server IP UDP Server Port 2999 Operator Name APN Name Vodacom Vodameter Neotel internet Neotel Server Name Neotel UDP Server IP UDP Server Port 299 SAM Training

7 Equipment Communication Controller – Coms wiring
Communication Cable Consumables ECS (Eth/E1), ECS-L 1. 10 way Ribbon Cable 2. 10 way IDC connector for 10 way ribbon cable 3. DB9 IDC, male and female for 10 way ribbon cable ECS (Eth/GPRS), ECS (Eth/E1) & ECS-L 1. DB9, male and female, solder type 2. Milar cable used with point 1 above (Same as SAM2 Coms cross over cable) 1. RJ9 – small 4 way 2. RJ11 – large 4 way 3. RJ way 4. RJ45 – 8way 5. Cable for each above 6. CAT5 cable Possible Communication Cables needed 1. SAM1.5 2. SAM2, SAM3 & Access Control 3. Energy Meter (Landis & Gyrr) Rectifier 4. Rectifier (Battery Tech, Grintek, ASM, etc) 5. Generator (Lovato, Deep Sea, Intellilite, etc) 6. Fuel Cell (Idatech, Gencore, etc) SAM Training

8 ECS-L2 Communication wiring SAM2 & Access Control
SAM Training

9 ECS-L2 Communication wiring SAM1.5
SAM Training

10 ECS-L2 Communication wiring landis & Gyrr
SAM Training

11 ECS-L2 Communication wiring battery tech SM65
SAM Training

12 ECS-L2 Communication wiring battery tech SC200
Rear View SC200 RS232 Connection Front View SAM Training

13 ECS-L2 Communication wiring battery tech SM50
SAM Training

14 ECS-L2 Communication wiring Grintek gt500
SAM Training

15 ECS-L2 Communication wiring Deep Sea
SAM Training

16 ECS-L2 Communication wiring Lovato
SAM Training

17 Thank you


Download ppt "INAlA TECHNOLOGIEs Installation Training:"

Similar presentations


Ads by Google