1 Rich Ames :Training NetTech
_________________________________________________________

2 Security Administrator
S2 System Architecture Internet Temp Probe Door Lock Portal NetDoor Node IP Network Reader Video Recorder Analog Camera Photo ID Camera Photo ID Badge Printing Security Administrator IP Camera IP Camera (PTZ) IP Network Security Monitor NetBox Node NetBox Temp Probe Door Lock Reader Portal Alarm Remote Support Alarm Panel Door Lock Portal Reader 6 5 4 3 2 1 Elevator Gate Reader Portal Lighting

3 Network Controller, Node & Expansion Blades

4 NetDoor Node, with Access Blade

5 S2 System IP Network NetDoor Node Internet Controller Node
NetDoor Node Internet IP Network Controller Node NetDoor Node Node

6 S2 Hardware Standard (Solid State) Limitations
S2 Net Box Nodes per System 24 Card Readers per System 140 Tested/Certified Access Cards per System 60,000 Card Formats 32 Simultaneous Users 10 Alarm Input Points 500 Output Dry Contacts Temperature Probe Inputs Online event history log 50,000 records Time specifications 100 Threat Levels 8 Holidays 30 Cards per person

7 S2 Hardware Enterprise (Hard Disk) Limitations
S2 Net Box Nodes per System 256 Card Readers per System 3500 Access Cards per System 150,000 Card Formats 32 Simultaneous Users 25 Alarm Input Points 7168 * Output Dry Contacts Temperature Probe Inputs Online event history log 50,000 records Time specifications 100 Threat Levels 8 Holidays 30 Cards per person

8 Enterprise System Enterprise Controller

9 S2 Combo Board Controller LED NC to NN NC to NN Speed NN Count N Com
Connection Activity Node LED Action Co-Processor NN Com Power NN to NC Speed NN to NC Activity

10 Initmode Starting point with new NetBox Controller
Set IP Address (Controller starts on “0” subnet) Set Time (Controller) Settings Initmode (turn off?)

11 Localization Date Formats Languages 05/31/2004 31/05/2004 2004/05/31
English - Spanish Thai - Italian French - Japanese Portuguese - Chinese

12 Network Port Usage

13 Securing NetBox Data: Assumption: Interactions between the various networked components in any Network are not inherently secure. For the S2 System, each of these pathways is secured.

14 Secure by Design Minimal security vulnerabilities: Network Security
The NetBox is a “locked down” networked information appliance. S2 controls the software/firmware that is on it. The NetBox has a single purpose. It is not a general purpose computer. Minimal chance for virus attacks Network Security User Login, User Roles, Session Token SSL Encryption Authentication & Tamper Detection

15 Access Blade & NetDoor Blade
REX (Input) Buzzer (Alarm > Output) DSM (Input) Door Lock (Alarm > Output) Card Reader (Reader/Keypad) Reader 1 Reader 2 1 2 3 4 Temp Input Outputs Inputs Net Door

16 Access Control Blade 4 Inputs 4 Outputs Two card reader connectors
Readers using standard Wiegand output up to 128 bits are supported. 500 feet (152 meters) Four Supervised Inputs Door contacts and REX devices. Standard two wire inputs (supervised or unsupervised). 2000 feet (610 meters) Four Relay Outputs Strike output, door opener, buzzer. Standard 3 pin normally open or normally closed. NOTE: Inputs and Outputs not used for door hardware can be used for other functions. 4 Inputs 4 Outputs 2 Wiegand Readers

17 Alarm Inputs 8 Standard two wire inputs.
A variety of supervised and unsupervised inputs can be configured: PIR, Exit Request, Alarm button. Door Status Monitor Input blade barcode numerals begin with “01.”

18 Temperature Inputs 8 Standard two wire inputs.
S2 temperature probe. Max distance 500 ft. (1000 ft with Category 5 wire) Operating Range: º C to 100º C (-67° F to 212° F) Temperature blade barcode numerals begin with “08.” NOTE: For distances up to 500 feet (152.4 meters) use Category 3 cable. For distances over 500 feet up to 1000 feet (304.8 meters) use Category 5 cable.

19 Output Blade Output devices: Strikes, Mag locks, sounders, etc.
Eight 3-pin output relays Standard normally open or normally closed Form C Relays Suitable for controlling many strikes, but a step up relay should be used for magnetic locks. Max ratings: 30 Volts DC or AC, 2.5 Amps inductive or 5.0 Amps non-inductive Requires appropriate suppression: MOVs or diodes Output devices: Strikes, Mag locks, sounders, etc.

20 Slot/Connector Positions
Expansion Slots Slot/Connector Positions

21 The Portal Access or Egress Point Associate Inputs and Outputs Door
Gate Turnstile Associate Inputs and Outputs Readers, Keypads Locks Rex, DSM

22 Access Blade & Portal Portal Access Blade Buzzer (Alarm > Output)
REX (Input) DSM (Input) Buzzer (Alarm > Output) Door Lock (Alarm > Output) Card Reader (Reader/Keypad)

23 10 Steps to Gain Simple Access
Wire and connect a Reader and Door Lock. Define a Reader Define an Output (Lock) Define a Portal with Reader and Lock

24 Basic Access Requirements
Portal Reader Lock

25 10 Steps to Gain Simple Access
Wire and connect a Reader and Door Lock. Define a Reader Define an Output (Lock) Define a Portal with Reader and Lock Define a Card Format

26 Decoding Credentials Test and Compare to determine format
Decode content

27 Basic Access Requirements
Portal Reader Lock

28 10 Steps to Gain Simple Access
Wire and connect a Reader and Door Lock. Define a Reader Define an Output (Lock) Define a Portal with Reader and Lock Define a Card Format Define an Access Level for Readers/Groups

29 Basic Access Requirements
Portal Reader Lock Access Level Reader(s) Time Spec

30 10 Steps to Gain Simple Access
Wire and connect a Reader and Door Lock. Define a Reader Define an Output (Lock) Define a Portal with Reader and Lock Define a Card Format Define an Access Level for Readers/Groups Add a Person Assign a Card Assign an Access Level

31 Basic Access Requirements
Portal Person (Card Holder) Record Reader Lock Access Level Reader(s) Time Spec

32 10 Steps to Gain Simple Access
Wire and connect a Reader and Door Lock. Define a Reader Define an Output (Lock) Define a Portal with Reader and Lock Define a Card Format Define an Access Level for Readers/Groups Add a Person Assign a Card Assign an Access Level Present the card to the reader to unlock the Door

33 Basic Access Requirements
Portal Person (Card Holder) Record Reader Lock Access Level Reader(s) Time Spec

34 NetBox Navigation

35 Card or Keypad vs Card + PIN
Card or Keypad entry: Reader defined Reader only Keypad Format Credential format Portal Reader Only Card + PIN Reader or Reader + Keypad For Keypad Reader Keypad

36 Personal Information Optional Tabs User Defined Tab Contact
Other Contact User Defined Vehicles (Parking) User Defined Tab 20 fields available User Defined Labels for Tab and Fields. Show? Y/N Use fields for sorting and filtering reports

37 Photo ID License required (Badge)
Supports Canon PowerShot digital cameras A70, A75, A80, A85, A95, A510, A520, A620, A640, G3, G5, G6, G7, G9, Pro 1, S3 IS, S5 IS, S70, S80 and SX100 IS

38 Support Information Your Company Contact Information On “Dealer Info” Page On “About” page

39 Support Information Your Company Contact Information On Dealer Page On “About” page

40 Inputs Two Pin Relays Supervision Types
Used to monitor status or receive input Supervision Types Dual Resistor NO or NC Four States: Normal, Alarm, Short, Open Parallel Resistor NO or NC Three States: Normal, Alarm, Open/Short Series Resistor NO or NC Unsupervised NO or NC Two States: Normal, Alarm

41 Dual Resistors

42 Normally Closed Parallel Resistor

43 Normally Closed Series Resistor

44 Normally Closed Unsupervised

45 Normally Open Parallel Resistor

46 Normally Open Series Resistor

47 Normally Open Unsupervised

48 Output Relay Connectors
Normally Not Energized Normally Energized

49 Local to Node Events Output activated by Portal Status
Timed or for Length of Status.

50 The Portal Access or Egress Point Associate Inputs and Outputs Events
Door Gate Turnstile Associate Inputs and Outputs Readers, Keypads Locks Rex, DSM Events Local to Node Outputs System Wide Event Actions and Alarms

51 Momentary and Scheduled Actions
Access Portals for impromptu unlock/lock Momentary – quick unlock and relock Scheduled Portal Unlock Used to temporarily unlock for one-time activity Start time and date or Now End time and date or after X period of time Comment is a good idea – it documents unlock reason

52 Time Specs & Holidays Holidays: normal function does not apply unless specified as part of the controlling Time Spec. Define Beginning Date/Time and Ending Date/Time 3 Holiday Groups: Must be in at least one group. Holidays are not part of Access Level unless specified in the Time Spec.

53 Time Specs & Holidays Time Spec is a period of time definition
2 standard time specs (Cannot be changed) Always Never Specify Start and End Times Days of the week and Holidays that apply

54 Time Specs: Where are they used?
Access Level: Time Spec Floor Groups: Free Access Time Spec Portal Groups: Unlock Time Spec Alarm Panel: Auto Arm Time Spec Input Groups: Auto Arm Time Spec Output Groups: Auto Activate Time Spec Events – Enabled Time Spec Portals: Keypad Time Spec, Exit Reader Time Spec Exit Keypad Time Spec

55 First in Unlock, (Monitored Unlock)
Works with Portal Group Unlock Time Spec Set up in System Rules Requires a special Access Level (You should limit who can do this) Set Unlock access level (required to activate unlock time spec) Set Re-Lock access level (automatic relock at end of time spec) Set reset time: resets to locked starting position. Portal Group must have Unlock Time Spec and First In Unlock Rule Unlocks Door(s) with badge read during unlock time spec Relock at end of unlock time spec or with Relock Access Level badge read.

56 Threat Levels Pre-defined to match US Homeland Security Definition and color coding. You can add your own (snow day) You can upload your own Threat Icon Use to mass change Access ability - Quick Lock down - Must Assign Threat Level Groups to all Access Levels Activated by Event or Manually by pre-authorized person. Must reset after Threat Level has changed Manually (may require password) Input Event with change Threat Level action Make sure someone has access during Lock Down.

57 Passback and Tailgate Violations
Definitions: Passback is when a card is “passed back” to another person so both can gain access on same card. To Tailgate is to gain access without a valid card read and without forced entry. Time may be used to determine passback violation. Regions are used to determine either violation At least two regions required for passback violation. At least three regions required for Tailgate violation.

58 Regions Uncontrolled Region 1 Uncontrolled Reader A: In Uncontrolled
Reader B: In Uncontrolled Portal: Main Entrance Reader 1. Reader A Access to Region 1 Region 1 Passback? - Time only Tailgate? - No Uncontrolled Region 1 Uncontrolled

59 Regions Uncontrolled Region 1 Uncontrolled Reader A: In Uncontrolled
Reader B: In Uncontrolled Reader C: In Region 1 Reader D: In Region 1 Portal: Main Entrance Reader 1. Reader A Access to Region 1 Reader 2. Reader C Access to Uncontrolled Region 1 Passback? - Time or Region Tailgate? - No Uncontrolled Region 1 Uncontrolled

60 Passback and Tailgate Violations
Definitions: Passback is when a card is “passed back” to another person so both can gain access on same card. To Tailgate is to gain access without a valid card read and without forced entry. Time may be used to determine passback violation Regions are used to determine either violation At least two regions required for passback violation. At least three regions required for Tailgate violation. Actions to be taken (defined in Region definition) Soft - Log entry but allow access Hard - Log entry and deny access Ignore – allow access.

61 Regions Region 2 Uncontrolled Region 3 Region 1 Uncontrolled
Reader D: In Region 3 Reader E: In Region 2 Portal: Lab Back Door Reader 1. Reader E Access to Region 3 Reader 2. Reader D Access to Region 2 Region 3 Passback? - Time or Region Tailgating? - Region Uncontrolled Region 3 Region 1 Uncontrolled

62 Regions Region 2 Uncontrolled Region 3 Region 1 Uncontrolled
Reader B: In Region 1 Reader C: In Region 3 Portal: Lab Front Door Reader 1. _________________ Access to ________ Reader 2. _________________ Uncontrolled Region 3 Region 1 Uncontrolled

63 Technical and Installation Information
* For a password (must register on website): Support Phone: (508) 

64 S2 Support Central - Downloads

65 Miscellaneous Information
Photo ID URL – Storage location for Person Pictures Default on Controller /upload/pics Off-board location NAS Photo ID Layout – default layout for badges Enrollment Reader – for assigning access cards to People Default Card Format – Can change when issuing cards Hide Unpermitted Access Levels – Only allows certain User Roles to see Access Levels PIN entry timeout – System wide time allowed for PIN entry after card read. ODBC Report user password – password protection for ODBC connection direct to Network Controller for user defined reports. Log Archive Interval – Time interval between automatic archive creation of Activity Log. Temperature Scale – For Temperature input unit of measure. Unacknowledged Alarm Audio – Wave file to play once per minute during unacknowledged alarm (System Wide Action)

66 Configure Remote Nodes
Portable Node Configuration Utility Finds Nodes on network Displays Node Address, Netmask and Gateway Assign Network Controller

67 Backups (Backup is only needed when you haven’t) (Murphy’s IT corollary)
Automatic Backup daily. System holds up to 6 weeks Sunday is a full backup … all others are differential backups. Seventh week starts overwrite of oldest backup. Backup writes to CFC Optional to NAS and FTP site. Must set up NAS or FTP address and password. Will not overwrite old backups. Use “get” to off-load backup to laptop or off-site. Save, Shutdown or Reboot save to ROM is automatic (v3.0 or higher).

68 Backups to NAS or FTP sites
FTP Backup (File Transfer Protocol) web site. Network Storage (NAS=network attached storage).

69 System Upgrade Upgrade File (need i-button number, - serial number -) Backup System Upload patch file Apply Upgrade

70 Node Upgrade Activity Log
Node is back on-line Node Disconnect for Upgrade

71 IP Camera Configuration
The Install Guide has a list of IP cameras that we have tried but any IP Camera should work. System ships with a growing set of camera types. Camera Types are user configurable – see manufacturer’s documentation for pan, tilt, and zoom (PTZ) URLs etc. SHOW THIS IN THE DEMO SYSTEM! No “approved device list”, any webcam should work; system ships with a growing set of camera types Camera Types are user configurable – see manufacturer’s documentation for pan, tilt, zoom URLs etc. Definition – browser address is video feed, control address is pan, tilt, zoom. May need DNS or IP forwarding for access from outside firewall. Presets – to return to “home”; enter on camera web site Views – PIP (picture in picture), Quadview Monitoring Desktop tabs for Cameras and views

72 IP Camera Configuration
Camera Definition IP Address of Camera (No IP Address of Control (No Port If PTZ User Name Password SHOW THIS IN THE DEMO SYSTEM! No “approved device list”, any webcam should work; system ships with a growing set of camera types Camera Types are user configurable – see manufacturer’s documentation for pan, tilt, zoom URLs etc. Definition – browser address is video feed, control address is pan, tilt, zoom. May need DNS or IP forwarding for access from outside firewall. Presets – to return to “home”; enter on camera web site Views – PIP (picture in picture), Quadview Monitoring Desktop tabs for Cameras and views

73 IP Camera and NetBox Interface
S 2 o B e r d o i w V PTZ Setup s e IP Address r U I

74 Events Something that requires action Acknowledgment may be required
Door Forced Door Held Input in abnormal state Designated Alarm Input Motion Detected Invalid Entry Attempt Acknowledgment may be required

75 Events Actions triggered by Event Send an SMS (text) message
Lock a Portal * Unlock a Portal * Momentarily unlock a Portal Activate a Relay * Deactivate a Relay * Arm Input or Input Group Pulse Output or Output Group Send an Send an SMS (text) message Arm Alarm Panel Disarm Alarm Panel Move a Camera to a Preset (IP cameras must be set up before you can use them in an Event) Save the event to an Activity Log Record Video Set a Threat Level

76 Putting Events to Work Portal Status: System Wide Actions
React to Door State React to Card Read Input Action: Off-normal event Input activates Action(s)

77 Putting Events to Work Access Level Actions taken on entry
With Valid Entry Alarm Panel Actions based on Panel or Zone Arm Failure Activity in Armed Area

78 Putting Events to Work Temperature Events: Temp too High or too Low or Not Reading Node Status: Node Tamper, Timeout or Disconnect Alarm

79 Putting Events to Work Video Action: Record Video or Notify of Failed Camera Normal activates when Camera returns to normal Motion activates Recording Fail activates when camera fails or stops communicating

80 Conceptually, the DVR and NVR are treated the same
DVR or NVR S 2 B r o w s e U I V i d Setup

81 Floorplans Used to Monitor Activity or Status of
Portals – temporarily unlock Cameras – thumbnail Temperature – Graph of last hour, day, week. Link Detailed Floor Plans to General Floor Plans Setup Sequence Upload jpg files Define Floorplan Place Resources Set Place Resource type Resource select Save Floorplan

82 The Five Steps to DVR/NVR Setup
1: Complete the set up of the DVR/NVR. 2: Point the S2 NetBox to the DVR/NVR. 3: Verify live video from the NetBox interface. 4: Set up Video Motion Detection from DVR/NVR. 5: Set up Video Recording Actions from the NetBox.

83 1: Complete the set up of the NVR.
NVR Windows UI S 2 Milestone Service S 2 Milestone Generic Event Builder Video Server

84 1: Complete the set up of the NVR.
Install the software: NVR Systems software components. S2 OVIDService Handles communications between NVR and the S2 Netbox. Service should start itself. Service creates its own Event Log. Make sure you set “Overwrite events as needed” Service should add itself to the Windows Firewall (requires Windows XP SP2). S2 Generic Event Builder (Included with OVID Service) Creates correct Start, Stop and PTZ events for each camera.

85 To open the Windows Firewall applet select Settings : Control Panel : Windows Firewall

86 1: Complete the set up of the DVR.
I U r e s w o r B DVR

87 1: Complete the set up of the DVR.
Make sure you set up the cameras first, and verify that you can see live video through the DS2 interface. Be aware of browser capabilities. DM is promoting use of Java over ActiveX. JRE or 5.0 required. We are integrating their Java applet into our S2 NetBox interface.

88 2: Point the S2 NetBox to the Milestone Server
S2 Browser UI Milestone Video Server Setup

89 2: Point the S2 NetBox to the DM DVR.
S2 Browser UI Setup

90 3: Verify live video from the NetBox interface.
S2 Browser UI V DVR or NVR

91 4: Set up Video Motion Detection from NVR/DVR
2 o B e r d o i w V s Setup VMD e r U I DVR or NVR VMD Events

92 5: Set up Video Recording Actions from NetBox
Events, VI, Triggers i V Recording Events DVR or NVR VMD Events

93 Alarm Panels Identify 2 Inputs for “zone” and “armed” status from panel One Output to allow arming or disarming from NetBox Auto Arming Output to sound warning device. Warning duration Auto Arming Time Spec (armed period). When the panel should be armed. Auto Arm Inactivity Time Length of time for panel to show all zones as inactive. Arm Panel request timeout – time to wait for armed status input. 5 seconds longer than panel’s grace period. Disarm reader group – card read for disarm access level to disarm panel. Disable reader group – disabled (deny access) readers when panel is armed. Events Specify Event to occur when there is failure to arm. Event to occur when activity detected during armed period.

94 Elevator Control

95 Floors are mapped to button outputs
6 5 4 3 2 1 Elevator 1 Output 1 Output 2 Reader 1 6 5 4 3 2 1 Elevator 2 Output 3 Output 4 Reader 2 Floor 6 Floor 5

96 Elevator Access Levels
6 5 4 3 2 1 YES OK?

97 Floor Groups and Free Access Time Spec
6 5 4 3 2 1 Elevator 1 Output 1 Output 2 Reader E1 Elevator 2 Output 3 Output 4 Reader E2 Restricted Access Free Access

98 Other uses of Elevator Controls
Floor 6 Thermostat Floor 5 Thermostat Front Entrance

99 Personal Information Access Control Photo ID User Defined (optional)
Badge Access Level PIN Photo ID User Defined (optional) User Labels and fields Display all or some Contact (optional) Other Contact (optional) Vehicle (optional) Login User Roles Widget Desktop Layouts Recent Activity

100 User Roles Predefined Categories Custom User Roles
Partition Monitor – Monitor menu only Partition Administrator – Monitor plus Administration menus Partition (System) Setup – Setup plus Monitor and Administration menus Custom User Roles Threat Level Group – Affects user system access Monitor limitations Camera groups: view, go to presets, PTZ Portal Groups: view, momentary unlock. extended unlock extended lock Elevator Groups: view Event Groups: view, acknowledge, clear actions Floorplan Groups: view Report Groups: run, edit Layout Groups: run Reader Groups: view photo IDs Access Levels: assign

101 User Roles Administrator: Person Record limitations
View, Assign, Add, Edit, Delete, Lookup Add Administration Privileges Add Setup Privileges

102 History Reports History Reports Access History - General Event History
Portal Access Count by User - Custom Reports

103 Custom Report

104 System Reset and Evaluation
Reset to Factory Defaults Do Not Remove Power until after License Page Use for configuring before going to the site. Be sure to wait for single beep. Leave S2 NetBox Powered up and Plugged in Tear out Evaluation page Fill in Leave with instructor

105 Thank you for your attention!