1 Wireless Remote Controller (MR-AH01/BH01) HQ SE

2  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF schedule  Service Mode - Main/RMC address check - Communication status check Features MR-AH01 MR-BH01 Main Difference  MR-AH01 : ON/OFF schedule time Increase only  MR-BH01 : ON/OFF schedule time Increase/Decrease both For MR-BH01, real time clock is not supported ! Wireless remote controller

3 Option code setting mode (MR-AH01) 1. Remove one battery from the wireless remote controller. 2. Press + together and put the battery back to enter the option code setting mode. 3. Use the Mode button to toggle the option code page. 4. Press the Set/Cancel button to change the option code. Toggle option code page Set option code Entering option code modeSetting option code

4 Option code setting mode (MR-BH01) 1. Remove one battery from the wireless remote controller. 2. Press + together and put the battery back to enter the option code setting mode. 3. Use the Mode button to toggle the option code page 4. Press Power button to change the option code. Toggle option code page Set option code Entering option code modeSetting option code Press together

5 Option code setting mode (Neo forte R/C) 1. Remove one battery from the wireless remote controller. 2. Press Temp ▲▼ together and put the battery back to enter the option code setting mode. 3. Set option code 2 digits. And press “Mode” and set next 2 digits. 4. Press the On/Off power button to change the option code. Entering option code modeSetting option code

6 4) Then “OFF timer” is displayed. 5) Set next 2 digit. 6) After setting completion, press “On/Off” ※ Only blue colored 20 digits should be set 1) Set 2 digits using Temp ▲▼ button 2) Press “Mode”, then ◀ will move to down. Set next 2 digit 3) After setting 10 digits, press “Mode” Option code setting mode (Neo forte R/C)

7 Service mode (MR-AH01) 1. Remote one battery from the wireless remote controller. 2. Press + together and put the battery back to enter the Service Mode. NOTE : Whenever Mode, Func1 and Func2 are changed, signal wave is transmitted from the wireless remote controller. Mode Func1 Func2 Press Set/Cancel button Entering service modeSelecting service mode

8 Service mode (MR-BH01) 1. Remote one battery from the wireless remote controller. 2. Press + together and put the battery back to enter the Service Mode. NOTE : Whenever Mode, Func1 and Func2 are changed, signal wave is transmitted from the wireless remote controller. Mode Func2 Press Set/Cancel button Entering service mode Func1 Selecting service mode Press together

9 Service mode ModeFunc1Func2Description 000 COM1 communication status (Blinking display only is valid)  Operation LED Blinking – communication status of all channels  Schedule LED Blinking – Outdoor ↔ Indoor units communication status  Fan LED Blinking – Wired remote controller ↔ Indoor units communication status  Filter LED Blinking – Interface module ↔ Indoor units communication status 010 COM1 Main Address check 020 LED display test (Rotating display) Operation LED → Schedule LED → FAN LED → Filter LED → Defrost LED All On → All Off → All On → All Off ……… MAIN address Operation LED Schedule LED FAN LED Filter LED 0OFF 1 ON 2OFF ONOFF …………… 15ON

10 ModeFunc1Func2Description 10x0 MAIN address assigned by outdoor unit (if in the AUTO addressing mode) (Read as decimal value) x : MAIN address of indoor unit If matched, all LEDs are lit ON. Ex) For DVM Plus II, MAIN(1) = 1, MAIN(2) =2  MAIN address = 12 11x0 RMC Address check. (Read as HEX value) x : RMC address of indoor unit If matched, all LEDs are lit ON Ex) For DVM Plus II, RMC(1)=1, RMC(2)=2  RMC address = 1*16 + 2 = 18 For DVM Plus II, RMC(1)=2, RMC(2)=1  RMC address = 2*16 + 1 = 22 13x0 Rotary switch MAIN address check (Read as decimal value) x : MAIN address of indoor unit If matched, all LEDs are lit ON Ex) For DVM Plus II, MAIN(1) = 1, MAIN(2) =2  MAIN address = 12 NOTE : Exit the service mode by pressing any general keys in the Normal mode. NOTE : Service mode 10,11 and 13 are not allowed for COM1-only indoor units. NOTE : Applied for Cassette/Duct indoor units (not for Wall-mount indoor units) Service mode


Download ppt "Wireless Remote Controller (MR-AH01/BH01) HQ SE.  On/Off control  Air flow control  Temperature setting  Filter reset  Louver Control  Simple ON/OFF."