Presentation is loading. Please wait.

Presentation is loading. Please wait.

2015 The Healthcare Environment

Similar presentations


Presentation on theme: "2015 The Healthcare Environment"— Presentation transcript:

1 2015 The Healthcare Environment
John Maurer, SASHE, CHFM, CHSP Engineering Department The Joint Commission 1

2 2014 Challenging standards Most Cited EC & LS Issues

3 Standard 2014 Non Compliance 2013 Non Compliance EC 56% 39% EC 53% 47% IC 52% 46% LS 50% RC 49% EC 48% 45% LS LS 43% 36% LS EC 34%

4 Standard 2014 Non Compliance 2013 Non Compliance MM 35% PC 33% 27% PC 29% 18% EC 21% PC 26% 20% MM 25% 22% LD 23% 19% LD 14% EC IC 13%

5 Most Cited Standards: 2011 – 2014
2013 2012 2011 EC : Built Environment #1 #8 #7 #11 EC : Utility Systems Risks #2 #4 #10 #13 LS : Means of Egress EC : Fire Safety Systems #6 #5 LS : General Bldg Req’s #3 LS : Extinguishment #9 LS : Protection EC : HazMat & Waste #15

6 #1 EC EP 1 & 13 EP 1 Interior spaces meet the needs of the patient population and are safe and suitable to the care, treatment and services provided The organization must provide a safe environment Unsecured oxygen cylinders Outdoor safety is scored at EC EP 5

7 EC EP 13 EP 13 The organization maintains ventilation, temperature and humidity levels suitable for the care, treatment and services provided Ventilation: i.e. doors held open by air pressure; odors Temperature: Hot / Cold calls Humidity Primary concern is for areas >60%RH Mold growth is possible EP 20 Patient care areas are clean and free of offensive odors

8 EC EP 1 The Joint Commission has adopted the Facilities Guidelines Institute (FGI) Guidelines for Design & Construction of Health Care Facilities ASHRAE 170 has been attached to the Guidelines Ventilation Table 20 – 60 % requirement of relative humidity (RH) in seven affected areas of the Surgical Environment, and one in Diagnostic & Treatment NOTE CMS has allowed this through written documentation (i.e., policy): see S&C: LSC & ASC The established 60% upper range however should be maintained for issues such as mold growth See also, S&C 15-27, Potential Adverse Impact of Lower Relative Humidity (RH) in Operating Rooms (ORs)

9 #2 EC EP 15 Ventilation system is unable to provide appropriate pressure relationships, air-exchange rates and filtration efficiencies Specific areas lack negative or positive pressures in relationship to adjacent areas i.e. Endoscopy Processing Room should be negative to the egress corridor the correct number of air changes per hour Improper filtration MERV = minimum efficiency reporting value

10 Screening Tissue test: only to be used as a pre-screening tool to evaluate if further investigation needs to occur To perform the flutter test take a tissue and let it hang just off the floor near the bottom edge of a door If the tissue indicates incorrect air flow, stabilize the area by closing doors and windows, wait a few minutes and re-test If the organization presents a Testing & Balancing report the following questions should be asked when was the balancing done (seasonal issues) are any specific requirements (such as keeping a door closed) needed to achieve satisfactory results

11 Central Sterile Layout
Physically separated soiled and clean work rooms Soiled Work Room: Work surface, sink, washer/sterilizer decontaminators Soiled room is not to have direct contact with the OR Clean assembly /work room Hand washing station Sufficient workspace and equipment Self-closing door or pass through is acceptable between soiled and clean work rooms Storage provisions for humidity, temperature, and ventilation Location of storage may be within the clean assembly/ workroom in a permanently designated space Guidelines for Design & Construction of Health Care Facilities FGI edition

12 Endoscopy Processing Room
May be one room, dedicated to endoscopy equipment processing Sized as per amount of equipment processed Work flow from soiled to clean Clean should not be exposed to soiled 3ft min clearance clean from soiled at all times Droplet contamination is concern Work surface and sink Hand washing station Sufficient workspace, utilities and equipment Ventilation Negative air pressure to surrounding areas Minimum 10 ach (2 fresh, outside); direct exhaust NO requirements for temperature or humidity Guidelines for Design & Construction of Health Care Facilities FGI edition

13 Endoscopy Processing Room
Storage May be a cabinet in the endoscopy processing room Cabinet must have doors Cabinet must be at least 3ft from potential droplet contamination Consider route from processor to the cabinet Route should not cross through soiled processing area Storage may be in a separate room Inventory of Scopes Recommended practice is to include scopes in the Medical Equipment Inventory Guidelines for Design & Construction of Health Care Facilities FGI edition

14 HLD Self Contained Units (i.e. GUS)
High Level Disinfection (HLD) for semi critical devices are found in and outside the Central Sterile areas Gluteraldehyde User Stations (GUS) disinfection soak stations, or similar self contained HLD units such as those using 0.55% ortho-phthalaldehyde (OPA) The Joint Commission will focus on the processes and Personal Protective Equipment (PPE) Many of the chemical disinfectants are potentially toxic and may require adequate precautions, including face/eye shields and gloves Ventilation Requirements: None. Rooms must meet specific room requirements however Storage: in a manner that will protect from contamination or damage, such as hanging in a cabinet with doors

15 NOTE: ASHRAE voted in July 2013 to move endoscopy procedure rooms from positive to NR. FGI is planning on releasing this in the November publication of the 2014 FGI Guidelines. Therefore, if an organization had made a documented decision based on risk assessment to no longer monitor endoscopy procedure rooms as per the 2013 ASHRAE action, we would accept this. If the organization has not made a documented decision, the room should be evaluated as per the below table and construction date. No change to bronchoscopy procedure rooms.

16 Guidelines Ventilation Table: Endoscopy & Bronchoscopy
Edition Procedure Processing  (Cleaning) Pressure Direct Exhaust 2014 NR Negative (-) YES 2010 Positive (+) 2006 2001 1996/97 1992/93 1987 1979

17 Survey Process EC.02.05.01 EP 15 will generate a CLD
If the organization can repair the process that led to non-compliance the LSCS may review Following LSCS review, the LSCS may contact the Central Office to discuss the possibility of reducing the CLD to SLD, with no change to the finding Resolution should include the area affected by the equipment identified as non-compliant, not just the identified room/area i.e. ensure zone is balanced Is there an ongoing process to assess?

18 #4 LS EP 13 The hospital maintains the integrity of the means of egress Anything in the egress corridor more than 30 minutes is storage Dead end corridors may be used for storage Less than or equal to 50sqft space Carts Allowed: Crash Carts Isolation Carts Chemo Carts

19 “If the corridor looks cluttered…it probably is”
Educate Staff What is the Risk? Patient movement Staff movement Additional Staff responding to emergency patient care

20 Suites Not identified on drawings Boundaries Dimensions Exits

21 LS Drawing Information
A legend that clearly identifies features of fire safety Areas of the building that are fully sprinklered (if the building is partially sprinklered) Locations of all hazardous storage areas Locations of all rated barriers Locations of all smoke barriers Suite boundaries, including the size of the identified suites—both sleeping (max 5,000 sq ft) and non-sleeping (max 10,000 sq ft) Locations of designated smoke compartments Locations of chutes and shafts Any approved equivalencies or waivers

22 #6 EC The hospital maintains fire safety equipment and fire safety building features. Features of fire protection Inventory required to ensure all devices are tested Documentation of testing is required

23 Need for Inventory EC.02.03.05 EP 1 – 20:
Each device that is required to be tested must be documented in an inventory If x devices were tested last year, and x-1 were tested this year, which device was missed? Each device must be on the inventory to identify which device was missed Total number of devices (quantity) is not adequate Lack of an inventory (written, electronic or other) results in a finding at the EP Findings solely for lack of inventory is not scored at EC EP 25

24 EC EPs 1-20: Missing documentation: score the EP as non-compliant Also write a finding at EP 25 for documentation not being readily available to the AHJ If acceptable documentation appears, finding at EP 1 – 20 might be removed during survey EP 25 remains LD EP 4: Staff held accountable If 3 or more findings at EC EP 1 – 20

25 EC.02.03.05 During survey specific documentation is reviewed
If the documentation for a specific EP is not available a finding is written as non-compliant for that EP The documentation should be readily available If the organization clarifies after survey: Joint Commission Engineers will review and evaluate compliance LD EP 4 remains 25

26 #7 LS EP 5 – 7 & 9 Building and fire protection features are designed and maintained to minimize the effects of fire, smoke, and heat. EPs 5 – 7 Door issues EP 9 Fire Barrier Penetrations Barrier Management

27 BMP Implementation Strategy
These three activities are related to the Building Maintenance Program (BMP): Begin with compliant building features Maintain these building features Maintaining the feature Evaluate for effectiveness Inspect by schedule to determine program effectiveness Evaluate door history Adjust evaluation frequency Adjust #2 above (maintaining) to achieve program effectiveness Sample size of 10 items, one failure = 90% Consider number of observations as denominator Number of successful observations as numerator For example: 10 doors, tested quarterly (2 scheduled maintenance and 2 fire drill observations) 10 x 4 = 40 actions 2 doors fail: 40 – 2 = 38 successful actions 38 ÷ 40 = 95%

28 Barrier Management Symposium
. . .at no cost to the attendee . . .

29 Barrier Management Symposium
Program Developers: Joint Commission Firestop Contractors International Association Underwriters Laboratories Participating Organizations: American Society for Healthcare Engineering AWCI & Gypsum Institute Fire Damper Industry Fire Rated Glazing Industry National Concrete Masonry Association

30 #8 LS The hospital provides and maintains building features to protect individuals from the hazards of fire and smoke. EP2 Hazardous Areas Primarily door issues EPs 16 – 23 Smoke Barriers & Doors

31 #9 LS EP 4: Piping for the AASS is not used to support any other item EP 5: Sprinkler heads are not damaged and are free from corrosion, foreign materials, and paint EP 14: Meets all other Life Safety Code automatic extinguishing requirements related to NFPA

32 LS.02.01.35, EP 14 Missing escutcheons
Ceiling tiles misplaced in rooms Blocked access to fire extinguishers Missing signage required in NFPA Quick response sprinklers mixed with other types in patient sleeping smoke compartments

33 #10 EC EP 3 – 5 EPs 3 – 5: Personal Protective Equipment and the process to manage hazardous materials and waste handling and exposures EPs 6 – 7: Hazardous energy sources Escorts to Hot Lab based on organization policy Perspectives, July 2012 Lead aprons

34 Eye Wash Station Federal Requirements: OSHA
Score Eye Wash issues at EC EP 5 Risk assess location / application based on OSHA recommendation to reduce the risk of injury from contact with corrosive materials in areas such as Power Plant Lab Placed so that the eyewash is within 10 seconds or 55 feet from where the corrosive chemicals is used Weekly flush until clear is required Annual inspection to ensure the system is fully functional Mixing valve recommended to achieve tepid Risk assess potential exposure to determine if cold water only would be acceptable

35 #14 EC.02.05.09 EP 3 Medical Gas Systems
EP 1: Inspection Testing and Maintaining EP 2: Test when modified, installed or repaired EP 3: Obstructions and Labeling Contents of piping Areas served Accuracy

36 Medical Gas Safety Score EC.02.03.01 EP 1 …fire risk
12 ‘E’ cylinders (<300ft³) per smoke compartment (22,500ft²) may be open to the egress corridor in a rack or appropriate holders Between 300 and 3000ft³ must be stored in a room that is limited construction with doors that can be locked “In use” verses “in storage” Properly secured to a gurney is considered “in use” Properly racked is “in storage” Empty are NOT considered part of the 12 in storage Empty and full must be stored (racked) separately 36

37 Medical Gas Safety Score EC.02.06.01 EP 1 …unsafe condition
Unsecured cylinders Laying on top a gurney mattress; leaning against the wall Free standing Comingling of full and empty cylinders Transfilling liquid oxygen Transfer of any gases from one cylinder to another in patient care areas of health care facilities is prohibited. Transfilling of liquid oxygen only in an area that is: mechanically ventilated sprinklered ceramic or concrete flooring separated with at least 1 hour construction from any patient care areas 37

38 #18 LD Up 8% from 2013 The hospital effectively manages its programs, services, sites, or departments Problematic EP: EP 4: Staff are held accountable for their responsibilities Used when leadership has allowed non compliance to exist without correction Sometimes used when situation is serious but does not warrant a “decision rule”

39 #19 EC EP 6 EPs 4 – 7 Missed Generator & Automatic Transfer Switch (ATS) Tests Exercise monthly Each emergency generator must be tested with a load of at least 30% of nameplate Each ATS must be tested Missed triennial 4 hour test

40 What is your approach to ESC?
Do you have a team approach or is one person responsible? Do you do what you need to do to “make it go away” or are the issues analyzed to determine why the non compliance is present? Do you use this standard ESC response: “We have re-educated the “Fill In The Blank”?” Have you looked at patient safety events and near misses/close calls in relation to non compliance identified during your survey? Have you considered what the short term and long term impact will be if you are unsuccessful in correcting the RFIs?

41 What is your approach to ESC?
Do you develop generic ESC or are your ESC specific to the root causes of the RFIs? Does the safety culture in your organization encourage staff and medical staff to identify system and process problems so they can be addressed quickly or do you wait until something happens or a surveyor finds it? When you develop your ESC do you find a way to incorporate it into daily activities and processes or do you lay it on top of everything else staff have to do? Is the culture in your organization one that allows the importance of the ESC to fade after a few months or is patient safety and compliance embedded in your mission/vision?

42 Bottom Line! If you don’t address the issues the first time you will be continually be doing rework and patient safety and quality suffer!

43 Some things to consider…
Do you have the right people at the table to address the issues identified? Are you focusing on systems and processes and how to improve them? Have you had an issue with this requirement on previous surveys? What kind of follow up monitoring have you planned to determine whether or not the ESC has been effective over the long term? If you find that your ESC hasn’t worked how do you go about fixing that?

44 2014 The Healthcare Environment Standards Update
44

45 NPSG 06.01.01: Alarm Mgmt In Phase I (beginning January 2014)
Hospitals will be required to: (by 7/14) establish alarms as an organization priority (during 2014) identify the most important alarms to manage based on their own internal situations. Input from medical staff and clinical depts Risk to patients due to lack of response, malfunction Are specific alarms needed or contributing to noise/fatigue Potential for patient harm based on internal incident history Published best practices/guidelines

46 NPSG.06.01.01: Alarm Mgmt In Phase II (as of January 2016)
Hospitals will be expected to: develop and implement specific components of policies and procedures that address at minimum: Clinically appropriate settings When they can be disabled When parameters can be changed Who can set and who can change parameters and who can set to “off” Monitoring and response expectations Checking individual alarm signals for accurate settings, proper operation and detectability educate those in the organization about alarm system management for which they are responsible

47 Questions to Consider Have you identified clinical alarm safety as a priority? Who is on the team addressing the NPSG? How far along are you in identifying the most important alarm signals to manage? What is your biggest challenge? Remember that the entire goal must be fully implemented by January of 2016!

48 EC EP 18 For hospitals that use Joint Commission for deemed status purposes: Radiation workers are checked periodically, by use of exposure meters or badge tests, for the amount of radiation exposure

49 EC EP 19 For hospitals that use Joint Commission for deemed status purposes: The hospital has procedures for the proper routine storage and prompt disposal of trash.

50 APPLIES TO HOSPITAL & CAH PROGRAMS
Equipment Management Medical Equipment: EC , EC Utility Systems: EC , EC APPLIES TO HOSPITAL & CAH PROGRAMS

51 S&C 14-07-Hospital S&C 12-07-Hospital Superceded on 12/20/2014
A hospital may adjust its maintenance, inspection, and testing frequency and activities for facility and medical equipment from what is recommended by the manufacturer, based on a risk-based assessment by qualified personnel, unless: Other Federal or state law; or hospital Conditions of Participation (CoPs) require adherence to manufacturer’s recommendations and/or set specific requirements. For example, all imaging/radiologic equipment must be maintained per manufacturer’s recommendations; or The equipment is a medical laser device; or New equipment without a sufficient amount of maintenance history has been acquired.

52 EC Standard EC The hospital manages risks associated with its utility systems. EC EP 1 The hospital designs and installs utility systems that meet patient care and operational needs. (See also EC , EP 1)

53 EC EP 2 The hospital maintains a written inventory of all operating components of utility systems or maintains a written inventory of selected operating components of utility systems based on risks for infection, occupant needs, and systems critical to patient care (including all life-support systems). The hospital evaluates new types of utility components before initial use to determine whether they should be included in the inventory. For hospitals that use Joint Commission accreditation for deemed status purposes: The hospital maintains a written inventory of all operating components of utility systems. (See also EC , EPs 1, 3-5)

54 Utility Systems & Operating Components
Utility Systems are those systems that support the use and function of the physical environment, including electrical distribution and emergency power elevators HVAC plumbing, boiler, and steam piped medical gas system vacuum systems communication systems IT/data exchange

55 Utility Systems & Operating Components
Components on the inventory would include the equipment that is performance-related and delivers a measurable outcome. For example, the heating system may have the following components: boiler, DA tank (de-aeration tank), feed water pumps, distribution (including circulation pumps, piping, and condensate return). Support parts to the components, such as belts, filters and steam traps, might not need to be individually listed, although they would likely be part of a preventive maintenance program. Support parts of components such as pumps and motors might also be considered sub-components and may or may not be reflected on the inventory, depending on the maintenance strategies used.

56 EC EP 3 The hospital identifies high-risk operating components of utility systems on the inventory for which there is a risk of serious injury or death to a patient or staff member should the component fail. Note: High-risk utility system components include life-support equipment.

57 EC EP 4 The hospital identifies the activities and associated frequencies, in writing, for inspecting, testing and maintaining all operating components of utility systems on the inventory. These activities and associated frequencies are in accordance with manufacturers’ recommendations or with strategies of an alternative equipment maintenance (AEM) program. Note 1: The strategies of an AEM program must not reduce the safety of equipment and must be based on accepted standards of practice. An example of guidelines for physical plant equipment maintenance is the American Society for Healthcare Engineering (ASHE) book Maintenance Management for Health Care Facilities. Note 2: For guidance on maintenance and testing activities for Essential Electric Systems (Type I), see NFPA 99, 1999 edition (Section 3-4.4).

58 EC EP 5 For hospitals that use Joint Commission accreditation for deemed status purposes:  The hospital’s activities and frequencies for inspecting, testing, and maintaining the following items must be in accordance with manufacturers’ recommendations: Equipment subject to federal or state law or Medicare Conditions of Participation in which inspecting, testing, and maintaining be in accordance with the manufacturers’ recommendations, or otherwise establishes more stringent maintenance requirements New operating components with insufficient maintenance history to support the use of alternative maintenance strategies S&C Hospital Superceded A hospital may adjust its maintenance, inspection, and testing frequency and activities for facility and medical equipment from what is recommended by the manufacturer, based on a risk-based assessment by qualified personnel, unless: Other Federal or state law; or hospital Conditions of Participation (CoPs) require adherence to manufacturer’s recommendations and/or set specific requirements. For example, all imaging/radiologic equipment must be maintained per manufacturer’s recommendations; or The equipment is a medical laser device; or New equipment without a sufficient amount of maintenance history has been acquired. The organization inspects, tests & maintains New medical equipment or operating components of utility systems in accordance with manufacturers’ recommendations with insufficient maintenance history to support the use of alternative maintenance strategies. Maintenance history may be gathered from documented evidence such as Provided by the organizations contractors Available publically from nationally recognized sources Through the organizations experience over time

59 EC EP 5 Note: Maintenance history includes any of the following documented evidence: Records provided by the hospital’s contractors Information made public by nationally recognized sources Records of the hospital’s experience over time

60 EC EP 5 For hospitals that use Joint Commission accreditation for deemed status purposes:  The hospital’s activities and frequencies for inspecting, testing, and maintaining the following items must be in accordance with manufacturers’ recommendations: Equipment subject to federal or state law or Medicare Conditions of Participation in which inspecting, testing, and maintaining be in accordance with the manufacturers’ recommendations, or otherwise establishes more stringent maintenance requirements Medical laser devices Imaging and radiologic equipment (whether used for diagnostic or therapeutic purposes) New medical equipment with insufficient maintenance history to support the use of alternative maintenance strategies  S&C Hospital Superceded A hospital may adjust its maintenance, inspection, and testing frequency and activities for facility and medical equipment from what is recommended by the manufacturer, based on a risk-based assessment by qualified personnel, unless: Other Federal or state law; or hospital Conditions of Participation (CoPs) require adherence to manufacturer’s recommendations and/or set specific requirements. For example, all imaging/radiologic equipment must be maintained per manufacturer’s recommendations; or The equipment is a medical laser device; or New equipment without a sufficient amount of maintenance history has been acquired. The organization inspects, tests & maintains New medical equipment or operating components of utility systems in accordance with manufacturers’ recommendations with insufficient maintenance history to support the use of alternative maintenance strategies. Maintenance history may be gathered from documented evidence such as Provided by the organizations contractors Available publically from nationally recognized sources Through the organizations experience over time

61 EC EP 6 For hospitals that use Joint Commission accreditation for deemed status purposes: A qualified individual(s) uses written criteria to support the determination whether it is safe to permit operating components of utility systems to be maintained in an alternate manner that includes the following: How the equipment is used, including the seriousness and prevalence of harm during normal use Likely consequences of equipment failure or malfunction, including seriousness of and prevalence of harm Availability of alternative or back-up equipment in the event the equipment fails or malfunctions Incident history of identical or similar equipment Maintenance requirements of the equipment For more information on defining staff qualifications, refer to Standard HR

62 EC EP 7 For hospitals that use Joint Commission accreditation for deemed status purposes: The hospital identifies operating components of utility systems on its inventory that is included in an alternative equipment maintenance program.

63 EC EP 1 The hospital tests utility system components on the inventory before initial use and after major repairs or upgrades. The completion date of the tests is documented. (See also EC , EP 2)

64 EC EP 3 The hospital inspects, tests, and maintains the following: life-support High-risk utility system components on the inventory. These activities are documented. (See also EC , EPs 2 and 4) Note: High-risk utility system components includes life-support utility system components.

65 EC EP 4 The hospital inspects, tests, and maintains the following: Infection control utility system components on the inventory. These activities are documented. (See also EC , EPs 2 and 4)

66 EC EP 5 The hospital inspects, tests, and maintains the following: Non–life-support Non-high-risk utility system components on the inventory. These activities are documented. (See also EC , EPs 2 and 4)

67 Equipment Survey Process
Documentation is completed for High-risk, life support and non-life support devices on the inventory Accuracy of Inventory All High-risk and Life Support equipment must be on the inventory and identified Preventive maintenance frequencies must be clearly defined in writing Confirm work done as per scheduled activities Ensure appropriate work is scheduled based on maintenance strategies Evaluate equipment failure and scheduled actions

68 Survey Process: Staff Interviews
Department Leader Evaluate the qualifications of the leader Review appropriate documentation Evaluate how the inventory was created If an alternative maintenance program is in use, evaluate the inclusion process Evaluate the Monitoring processes Evaluate the effectiveness of the program What criteria is used to evaluate Evaluate the Completion rate of maintenance activities

69 Survey Process: Staff Interviews
Equipment Maintainers Evaluate their understanding of the maintenance process/strategies Evaluate staff knowledge related to the alternative maintenance program Evaluate assignment of maintenance activities Evaluate competencies based on repeat work orders Evaluate work scheduled against completed

70 Survey Process: Staff Interview
Users of the Equipment Evaluate equipment reliability Evaluate response time when equipment fails Evaluate emergency response process Evaluate “Culture of Safety” Appropriate training of staff related to equipment use Customer satisfaction with department Contract Services Evaluate the process used to ensure contractors use qualified personnel Evaluate reliability of equipment serviced Evaluate integration of the process

71 Evaluating Program Effectiveness
The equipment management programs must have written policies & procedures Evaluating the program: How is equipment evaluated to ensure no degradation of performance? Consider mis-calibration of equipment Consider test equipment calibration confirmation How are equipment-related incidents investigated? Could the malfunction have been avoided? Did the alternative maintenance strategy contribute to the malfunction? How to sequester equipment deemed unsafe?

72 Evaluating Program Effectiveness: Miscellaneous Topics
Survey should focus on High-risk equipment Are appropriate operation manuals and maintenance schedules available? Verify the inspection, testing & maintaining activities and frequencies are documented Evaluate the various maintenance strategies used Are they appropriate? Are they effective? Is the equipment reliable?

73 Standards Language Changes

74 Risk Icon Integrated into the Manuals, E-dition, AMP, & FSA Tool
Proximity to patient Probability of harm Severity of harm Number of patients at risk Risk Icon Integrated into the Manuals, E-dition, AMP, & FSA Tool All products will display a single icon at the EP level for three risk-focused categories: National Patient Safety Goals Accreditation program-specific risk area standards Selected direct/indirect impact standards In addition, the FSA Tool will use the R icon to identify the fourth risk category: RFI standards from current cycle survey events.

75 Time RE-Defined The Joint Commission EC chapter defines time as:
Daily, weekly, monthly are calendar references Quarterly is once every three months +/- 10 days January 1, 2014 Semi-annual is 6 months from the last scheduled event month +/- 20 days Annual is 12 months from the last scheduled event month +/- 30 days 3 years is 36 months from the last scheduled event month +/- 45 days NOTE 1: The above does not apply to required frequencies NOTE 2: An alternative of developing either a unique, written policy or adopting NFPA definitions when available is acceptable

76 Quarterly: +/- 10 days Semiannual: +/- 20 days Annual: +/- 30 days
Due Date + Due Date + 10 10 10 10 Scheduled Month Scheduled Month 20 20 20 20 30 30 30 30 Quarterly Jan February March Apr Semiannual June July Aug Sept Oct Nov Dec Annual Jan F M A M J J A S O N D Jan Frequencies required by Code may not be modified (e.g. EC EP 4 & 7)

77 Changes to Elements of Performance
EC , EP 3 When quarterly fire drills are required, at least 50% are unannounced. Fire drills are held at unexpected times and under varying conditions.

78 EC EP 4 Staff who work in buildings where patients are housed or treated participate in drills according to the hospital’s fire response plan. Note: When drills are conducted between 9:00 p.m. and 6:00 a.m., the hospital may use alternative methods to notify staff instead of activating audible alarms. Replaced “building’s fire alarm system.” See NFPA , “…a coded announcement shall be permitted to be used instead of audible alarms.”

79 Changes to Elements of Performance
Standard EC EP11:  For managing hazardous materials and waste, the hospital has the permits, licenses, manifests, and material safety data sheets required by law and regulation EC , EP 4 Twelve times a year, at intervals of not less than 20 days and not more than 40 days, At least monthly, the hospital tests each emergency generator under load for at least 30 continuous minutes. The completion dates of the tests are documented. EC , EP 6 Twelve times a year, at intervals of not less than 20 days and not more than 40 days, At least monthly, the hospital tests all automatic transfer switches. The completion date of the tests is documented.

80 Changes to Elements of Performance
EC , EP 5 The emergency generator monthly tests for diesel-powered emergency generators are conducted with a dynamic load that is at least 30% of the nameplate rating of the generator or meets the manufacturer’s recommended prime movers’ exhaust gas temperature. If the hospital does not meet either the 30% of nameplate rating or the recommended exhaust gas temperature during any test in EC , EP 4, then it must test each the emergency generator once every 12 months using supplemental (dynamic or static) loads of 25% of nameplate rating for 30 minutes, followed by 50% of nameplate rating for 30 minutes, followed by 75% of nameplate rating for 60 minutes, for a total of 2 continuous hours. Note: For non diesel-powered generators tests need only to be conducted with available load.

81 Changes to Elements of Performance
EC , EP 7 At least once every 36 months, hospitals with a diesel-powered generator providing emergency power for the services listed in EC , EPs 5 and 6, test each the emergency generator for a minimum of 4 continuous hours. The completion date of the tests is documented. Note: For additional guidance, see NFPA 110, 2005 edition, Standard for Emergency & Standby Power Systems. EC , EP 8 The 36-month diesel-powered emergency generator test uses a dynamic or static load that is at least 30% of the nameplate rating of the generator or meets the manufacturer’s recommended prime movers' exhaust gas temperature. Note: For non diesel-powered generators tests need only to be conducted with available load.

82 2012 Life Safety Code Update The following are available with certain provisions. These are based on CMS S&C LSC 82

83 Background The Joint Commission provided CMS with a list of items, based on later editions of the Life Safety Code, that would immediately have a positive impact on all healthcare CMS acted on the Joint Commission recommendation in the form of a State & Certification letter (S&C LSC) The action is a series of Categorical Waivers

84 Process If the organization decides to adopt these categorical waivers they must Ensure full compliance with the appropriate code reference Document the decision to adopt the categorical waiver For Life Safety Code items annotate the “Additional Comments” Section in the Statement of Conditions™ Basic Building Information (BBI) For Environment of Care items document by Minutes in discussion at the Environment of Care Committee (or equivalent) Declare the decision at the beginning of any survey

85 S&C 13-58-LSC Medical gas alarms Openings in exit enclosures
Emergency generators and standby power systems Doors, locking arrangements Suites Extinguishing requirements Clean waste and patient record recycling containers Plus four: see S&C LSC Wheeled equipment and fixed furniture in egress corridors One alternative kitchen cooking arrangement Direct vent gas fireplaces and solid fuel-burning fireplaces Combustible decorations on walls, doors, and ceilings

86 Relocatable Power Taps (RPTs)
Healthcare Interpretation Task Force (12/2007) stated NFPA 70, NFPA 99 and NFPA 101 all have regulations that control the electrical components and equipment in a patient room. It appears that it is the intent of these documents to restrict RPT use so that it is not used in conjunction with medical equipment CMS 3/2014: “RPT’s are not to be used with medical equipment in patient care areas. This includes critical areas such as operating rooms, recovery areas, intensive care areas, and non-critical patient care areas such as patient rooms, diagnostic areas, exam areas, etc.”

87 Relocatable Power Taps
RPTs may be used in anesthetizing locations if they are part of the equipment assembly. See NFPA (2) Ceiling drops are acceptable. See NFPA (3) RPTs may be used for non-patient care equipment such as computers/monitors/printers, and in areas such as waiting rooms, offices, nurse stations, support areas, corridors, etc. Precautions needed if RPT’s are used include: ensuring they are never “daisy-chained” preventing cords from becoming tripping hazards installing internal ground fault and over-current protection devices using power strips that are adequate for the number and types of devices used

88 S&C: LSC 9/26/2014 CMS is permitting a categorical waiver to allow for the use of power strips in existing and new health care facility patient care areas, if you are in compliance with all applicable 2012 LSC power strip requirements and with all other 2000 LSC electrical system and equipment provisions. The organization must follow all requirements of the categorical waiver process This includes identifying where they are located at the unit level

89 Categorical Waiver Process
If the organization decides to use this categorical waiver they must Ensure full compliance with the appropriate code reference Document the decision to adopt the categorical waiver The Relocatable Power Tap is not a LSC issue but an Environment of Care issue For Environment of Care items document by Minutes in discussion at the Environment of Care Committee (or equivalent) Declare the decision at the beginning of any survey See also November 2013 Perspectives

90 Definitions From NFPA 99-2012
Patient bed location is defined in section as the location of a patient sleeping bed, or the bed or procedure table of a critical care area. Patient-care-related electrical equipment is defined in section as electrical equipment that is intended to be used for diagnostic, therapeutic, or monitoring purposes in the patient care vicinity; Patient care room is defined in section as any room of a health care facility wherein patients are intended to be examined or treated. Note that this term replaces the term “patient care area” used in the 1999 NFPA 99, but the definition has not changed. Patient care vicinity is defined in section as a space, within a location intended for the examination and treatment of patients (i.e., patient care room) extending 6 ft. beyond the normal location of the bed, chair, table, treadmill, or other device that supports the patient during examination and treatment and extends vertically ft. 6 in. above the floor.

91 Requirements Power strips may be used in a patient care vicinity to power rack-, table-, pedestal-or cart-mounted patient care-related electrical equipment assemblies, provided all of the following conditions are met, as required by section : The receptacles are permanently attached to the equipment assembly. The sum of the ampacity of all appliances connected to the receptacles shall not exceed 75 percent of the ampacity of the flexible cord supplying the receptacles. The ampacity of the flexible cord is suitable in accordance with the current edition of NFPA 70, National Electric Code. The electrical and mechanical integrity of the assembly is regularly verified and documented through an ongoing maintenance program. Means are employed to ensure that additional devices or nonmedical equipment cannot be connected to the multiple outlet extension cord after leakage currents have been verified as safe.

92 Requirements Patient bed locations in new health care facilities, or in existing facilities that undergo renovation or a change in occupancy, shall be provided with the minimum number of receptacles as required by section Power strips providing power to rack-, table-, pedestal-, or cart-mounted patient care-related electrical equipment assemblies are not required to be an integral component of manufacturer tested equipment. Power strips may be permanently attached to mounted equipment assemblies by personnel who are qualified to ensure compliance with section

93 Requirements Power strips may not be used in a patient care vicinity to power non-patient care-related electrical equipment (e.g., personal electronics). Power strips may be used outside of the patient care vicinity for both patient care-related electrical equipment & non-patient-care-related electrical equipment. Power strips providing power to patient care-related electrical equipment must be Special-Purpose Relocatable Power Taps (SPRPT) listed as UL 1363A or UL Power strips providing power to non- patient-care-related electrical equipment must be Relocatable Power Taps (RPT) listed as UL 1363.

94 Medical Physicist, Dept. of Engineering
An Overview of The Joint Commission New and Revised Diagnostic Imaging Standards Slides Developed by: Andrea Browne, PhD, DABR Medical Physicist, Dept. of Engineering

95 Background Conducted research to identify risks related to diagnostic imaging Conducted a GAP analysis: Were risks areas sufficiently addressed in current standards or survey process Developed and posted new and revised imaging standards in Jan 2014 The standards focus on: Equipment that functions properly and a safe environment of care Qualified staff Processes to ensure safety and efficiency

96 The standards were pulled back and additional research was conducted…
What happened? Concerns were raised… …and we listened… What is expected in the role of the medical physicist Logistics and implications of documenting radiation dose Minimum qualifications for technologists performing CT exams The standards were pulled back and additional research was conducted…

97 Who was involved? Accredited customers and AAHP AAPM ABHP ABR ACR ARRT
ASRT HPS MITA NMTCB SNMMI PAYORS

98 What was the outcome? Based on feedback received, several standards were revised and two were deleted Entire set was re-posted in January 2015 See link to new standards: New and revised imaging requirements are effective July 1, 2015

99 What are the standards? They are accreditation requirements – applicable to accredited ambulatory care organizations, (including those that have achieved ADI certification) and hospitals providing diagnostic imaging services Heavy focus on MRI and CT modalities Research is underway to identify additional standards & survey process changes: cone beam CT fluoroscopy other risk areas

100 What is not included in these standards?
Requirements that address minimum qualifications for technologists performing diagnostic CT exams Requirements that address minimum qualifications for individuals interpreting diagnostic CT exams Work on these requirements will continue throughout 2015 What was deleted? Documentation of the radiation dose in interpretive report, and sent via PACS

101 Will the survey process change?
No changes to the on-site survey agenda Compliance will be assessed as part of the current survey activities (e.g. EC, Competence Assessment, Data Management, etc…) Will be incorporated into the current patient tracer processes

102 Diagnostic Imaging Standards
The Joint Commission New & Revised Diagnostic Imaging Standards 25 new/revised requirements 2 deletions

103 Notes: This element of performance does not apply to dental cone beam CT radiographic imaging studies performed for diagnosis of conditions affecting the maxillofacial region or to obtain guidance for the treatment of such conditions. This element of performance does not apply to CT systems used for therapeutic radiation treatment planning or delivery, or for calculating attenuation coefficients for nuclear medicine studies.

104 Notes (continued) This element of performance is only applicable for systems capable of calculating and displaying radiation dose indices. While the CTDIvol, DLP, and SSDE are useful indicators for monitoring radiation dose indices from the CT machine, they do not represent the patient’s radiation dose. Medical physicists are accountable for these activities. They may be assisted with the testing and evaluation of equipment performance by individuals who have the required training and skills, as determined by the physicist.

105 Requirements in the EC Chapter Address
Annual imaging equipment performance evaluations Imaging equipment quality control and maintenance activities MRI environmental risks – access control and patient screening Structural shielding design assessments Radiation protection surveys Staff dosimetry monitoring Testing of image acquisition monitors

106 EC.02.01.01: Manage MRI Safety Risks
EP 14: Patient safety Survey Process: Staff interview – Patient screening procedures Direct observation of patient screening and intake procedures. Review of screening forms Examples of Compliance: Patient history is obtained, available, reviewed Screening process addresses MRI safety risks Hearing protection is available and offered to patients Staff can describe emergency procedures

107 EC.02.01.01: Manage MRI Safety Risks
EP 16: Access restriction Survey Process: Staff interview – processes in place to restrict access? Responsibility for restricting access? Staff education on MRI Safety? Direct Interview – signage, other processes to restrict access , area under direct supervision? Examples of Compliance: Everyone screened or trained on MRI Safety Signage appropriately posted, conveys risks

108 EC.02.02.01: Hazardous Materials Risks
EP 17: Radiation exposure monitoring Survey process Staff interview-what processes are in place to monitor staff dosimetry badges, how often are they monitored? By whom? Direct observation – Are dosimetry badges being worn? Review dosimetry badge monitoring log(s) Examples of compliance Results of staff dosimetry monitoring are reviewed by the RSO, diagnostic medical physicist, or health physicist

109 EC. 02. 04. 01 EP 10: Medical Equipment Risks EC. 02. 04
EC EP 10: Medical Equipment Risks EC EP 15: Medical Equipment Activities EP 10: Identify activities EP 15: Maintain equipment Survey Process: Staff interview – What equipment testing / QC activities are needed? Frequency? By whom? Direct Observation – Review of QC and testing log(s) Examples of Compliance: Equipment testing and QC logs indicate being performed in accordance with manufacturer’s guidelines and organizational policy

110 EC.02.04.03: Maintain Medical Equipment
EP 17: Medical physicist activities Survey Process: Staff Interview – describe how/who/frequency measures & verifies CT radiation dose output Direct Observation – Review equipment testing reports, do they include dates & results? Examples of Compliance Annual testing documented as done by 7/1/16 Reports are dated; indicate being performed at least annually by a physicist for identified protocols

111 EC EP 19 – 23 EP 19: Annual CT Testing EP 20: Annual MRI Testing EP 21: Annual Nuclear Medicine Testing EP 22: Annual PET Testing EP 23: Annual acquisition monitor testing

112 Annual Equipment Performance Evaluations
Medical physicists are accountable, testing must be reviewed by the medical physicist They may be assisted with the testing and evaluation of equipment performance By individuals with the required training and skills, as determined by the physicist. Medical physicists are not required to be present during all data collection and testing Examples of those who may assist include: biomed staff, imaging technologists, and vendor/manufacturer service personnel

113 EC EP Survey Process: Staff interview – describe how/who/frequency CT, PET, NM and MRI performance evaluations Direct observation – Review performance evaluation reports. Tests performed? Recommendations? Resolution? Examples of Compliance: Reports indicate annual testing by appropriate medical physics personnel Specified tests conducted, results evaluated, recommendations and follow-up documented

114 EC EP 23 Survey Process: Staff interview – describe how/who/frequency testing acquisition monitors Direct observation – Review performance evaluation reports. Tests performed? Recommendations? Resolution? Examples of Compliance: Reports indicate annual testing by appropriate physics personnel Specified tests conducted, results evaluated, recommendations and follow-up documented

115 EC EP 4 & 6 EP 4: Structural shielding evaluation pre-construction EP 6: Survey to verify adequacy post-construction Survey Process: Staff interview –facility/engineering staff/physicist. New installs/replacements/modifications to CT, PET, NM areas? Shielding design assessment? When, by whom? Post-construction survey conducted? Direct observation – Review assessments as applicable Examples of Compliance: Evidence of appropriate assessment conducted by a physicist; survey perform upon project completion Not retroactive- applies as of 7/1/15

116 Resources: Shielding designs and radiation protection surveys - For additional guidance see National Council on Radiation Protection and Measurements Report No. 147 (NCRP-147). Image Gently and Image Wisely – for more information go to or MRI safety - Terminology for defining the safety of items in the magnetic resonance environment is provided in ASTM F2503 Standard Practice for Marking Medical Devices and Other Items for Safety in the Magnetic Resonance Environment ( CT protocols and Alert Level guidance - information on suggested scan protocol, alert levels, and dose check guidelines can be found at the American Association of Physicists in Medicine (AAPM) website

117 More Resources: Scan protocols, reference dose level and radiation dose log information and examples - found on the Conference of Radiation Control Program Directors (CRCPD) website at under Medical Radiation tab. American College of Radiology (ACR) Dose Index Registry - found at under the Quality & Safety tab. CT diagnostic reference levels - general information is available on the International Atomic Energy Agency (IAEA) website at . Verification of Medical Physicist qualifications – go to the Conference of Radiation Control Program Director (CRCPD) or American Board of Radiology (ABR) websites. The Joint Commission’s Standards Interpretation Group (630)

118 Department of Engineering 630 792 5900
George Mills, MBA, FASHE, CEM, CHFM, CHSP Director John Maurer, SASHE, CHFM, CHSP Engineer Andrea Browne, PhD, Medical Physicist Engineer Kathy Tolomeo, CHEP Engineer Anne Guglielmo, CFPS, LEED, A.P., CHSP Engineer James Woodson, P.E., CHFM Engineer 118

119 The Joint Commission Disclaimer
These slides are current as of 5/11/ The Joint Commission reserves the right to change the content of the information, as appropriate. These slides are only meant to be cue points, which were expounded upon verbally by the original presenter and are not meant to be comprehensive statements of standards interpretation or represent all the content of the presentation. Thus, care should be exercised in interpreting Joint Commission requirements based solely on the content of these slides. These slides are copyrighted and may not be further used, shared or distributed without permission of the original presenter or The Joint Commission. 119


Download ppt "2015 The Healthcare Environment"

Similar presentations


Ads by Google