1 New structure in Deregulated Environment
Gen Genco Genco Genco Open access in Transmission Transmission Traders Discom Discom Discom Traders Open access in Distribution Distribution Customer Customer Customer

2 These changes require the following:
1) Monitoring system wide information and commands via data communication system 2) To send selected local information to control center, customer, market participants. 3) Monitor critical real time information for taking security related operation . 4) To support Power Trading and spot market.

3 4) Reliable and fast communications among IED’s (
Intelligent Electronic Devices viz Relays, Meters, Fault recorders, RTU’s etc.) for exchanging information and change in settings as part of wide area protection system . 5) Dissemination of billing and other related calculations from Generation to Distribution for to various agencies including information for DMS & EMS. 7) To perform effective co-ordination through communications , Communication Protocols used are expected to be high speed ,reliable , fault tolerant and intelligent enabled.

4 8) The Protocols are to be accomplished for both local
( LAN) and wide area communications (WAN). 9) The protocols should be thin, flexible and have provisions for accommodating future requirements. 10) Safe , secured and reliable transmission of information. 11) Protecting information network from Hacking & misuse.

5 12. Information about the power system
gives the utility the strength to be more successful and competitive in a free market . 13.In this environment information becomes a strategic requirement when fast decisions are required.

6 Typical Substation Automation System Architecture
Remote Center HMI Event Printer Hard Copy Printer Ethernet LAN Engineering Tool ISAGRAPH Fault Analysis Reyevo / SEL5601 / IPSCOM ER1000 Station Controller Ohmega Argus Duobias-M SEL-311C M-3425 Multifunction Meter Delta Typical Substation Automation System Architecture

7 What is Protocol ? When Intelligent Devices communicate with each other, there needs to be a common set of rules and instructions that each device follows. A specific set of communication rules is called a protocol.

8 * The diversity of Equipments and Manufacturers lead to a increase of Proprietary Protocols

9 Computer to Computer data communication standards have been developed over past few decades.
Well known model for this purpose is the 7 Layer OSI ( Open System Interconnection) reference model.

10 This model provides encapsulation of the relevant data with in a packet.
This model provide isolation of application program from system and media. But adds significant overhead in processing power and bandwidth utilisation.

11 OSI 7 Layer Model Application 7 Presentation 6 Sessions 5 5 4
Transport Network 3 Data link 2 1 Physical

12 Functionality of different layers
Application Layer: This provides the interface and services that support user application. Ex. , WWW, SMTP. Presentation Layer: This layer responsible for data encryption, data compression .Ex JPG, MPEG etc Sessions Layer: Responsible for setting up the communication link and manages the sessions. It could provide connection oriented and connectionless services.

13 Functionality of different layers
Transportation Layer: Responsible for flow control, Packet size, error free delivery with proper sequence. Network layer: Route determination takes place in this layer. Translation of IP address to physical address ( NIC) also takes place here. Data link layer : Responsible for data movement across the actual physical link. Physical Layer: It defines the physical aspect of how the cabling is hooked.

14 ••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7
7 LAYER System X System Y Application 7 ••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 Presentation 6 ••••••••••••••••••••••••••••••••••••••••••••••••••••••• 6 Peer communication Protocols Session 5 ••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 ••••••••••••••••••••••••••••••••••••••••••••••••••••••• Transport 4 4 Intermediate System A Intermediate System B ••• 3 ••• 3 ••• Network 3 3 ••• 2 2 ••• 2 2 ••• Data Link 2 2 ••• 1 1 ••• 1 1 ••• Physical 1 1 Physical Media Physical Media Physical Media

15 Due to addition of many layer
overhead and bandwidth goes higher. It is not suitable for SCADA application. Most of the Protocols follows various flavours of this model.

16 Need For Standards * Protocol is a set of rules that governs how message containing data and control information are assembled at a source for their transmission across the network and then dissembled when they reach their destination. * The communication protocol allows two devices to communicate with each other. Each device involved in the communication must essentially support not only the same protocol but also the same version of the protocol. Any differences involved in the implementation of protocol at the either of ends will result in the communication errors.

17 Proprietary Vs Open Protocols
* Protocol, used by the vendor, the utility is restricted to one supplier for support and purchase of future devices. This presents a serious problem. Examples of Proprietary Protocols are SPA, K-Bus, VDEW etc. * With the arrival of open systems concept , it is desired that devices from one vendor be able to communicate with those of other vendors i.e. devices should inter-operate . To achieve interoperability one has to use industry standard open protocols. Ex: IEC ,101,104, IEC61850,DNP,Modbus etc

18 Advantages of Open Protocols
* Migration to standard communication protocol is a very important decision that leads to cost reduction and maximized flexibility within the utility sector. Broadly benefits for the utilities are: Availability of open system connectivity > Vendor independence > Reliable products at optimized costs > Easily available knowledge and specification Benefits drawn for vendors by standardization are: > Lower costs of installation and maintenance > A large market and thus opportunity to compete on price performance instead of technical details only. > Cost effective project implementation

19 Interoperability Vs Interchangeability
* Interoperability is the ability of two or more IEDs from same vendor or different vendors to exchange information and uses that information for correct co-operation. * Interchangeability is the ability to replace the device the supplied by one manufacturer with a device without making change to the other elements in the system.

20 PROTOCOL STRUCTURE EPA OSI 7-Layer 3-Layer Application Presentation
Session Transport Network Data Link Physical Application Data Link Physical OSI EPA

21 OSI Seven Layer architecture
Network Technology mainly based on OSI (Open System Interconnect) which is a 7 Layer model representing networking node by dividing tasks into layers that perform specific Functions. Logical Connection Application Presentation Session Transport Network Data Link Physical Application Application Presentation Presentation Session Session Transport Transport Network Network Data Link Data Link Physical Physical Physical Connection OSI Seven Layer architecture

22 } } PROTOCOL STRUCTURE for IP based Open Protocols TCP/IP Ethernet
IEC, DNP, UCA (and even MODBUS) standards are successfully able to adopt TCP/IP based Ethernet based technology for substation automation. IEC (UCA2) DNP3/TCP IEC 104 Application Presentation Session Transport Network Data Link Physical } TCP/UDP TCP/IP IP } IEEE 802.1 Ethernet IEEE 802.3

23 Link Layer Balanced Transmission
Request Message Slave Master (User Data, Confirm Expected) [P] (Acknowledgment) [S] Response Message (User Data, Confirm Expected) [P] DNP only uses balanced transmission IEC profiles permit either balanced or unbalanced transmission (Acknowledgment) [S] [P] = Primary Frame [S] = Secondary Frame 14

24 Link Layer Balanced Transmission
At the link layer, all devices are equal Collision avoidance by one of the following: Full duplex point to point connection (RS232 or four wire RS485) Designated master polls rest of slaves on network (two wire RS485 and disable data link confirms in slaves) Physical layer (CSMA/CD) 15

25 Link Layer Unbalanced Transmission
Request Message Slave Master (User Data, Confirm Expected) [P] (Acknowledgment) [S] Response Message Not supported in DNP (Request User Data) [P] (Respond User Data or NACK) [S] [P] = Primary Frame [S] = Secondary Frame 16

26 Link Layer Unbalanced Transmission
Only Master device can transmit primary frames Collision avoidance is not necessary since slave device cannot initiate exchange, or retry failed messages If the slave device responds with NACK: requested data not available the master will try again until it gets data, or a response time-out occurs 17

27 Protocols used in Electrical utilities are as follows:
Modbus / Profibus DNP ( Distributed Network Protocol ) IEC series UCA ( Utlity Communication Architecture ) – IEC series

28 - Application layer Protocol ( 7 th Layer of OSI )
MODBUS Developed in the process-control industries by MODICON , USA during 1976 - Application layer Protocol ( 7 th Layer of OSI ) Extensively used in industrial environment Used in process bus of substation bay ( Relays ) It operates on master slave type mode Slave node will not typically transmit data with out a request from the master.

29 It was originally designed as a simple way to transfer data between controls and sensors via RS-232 interfaces. Modbus now supports other communication media, including TCP/IP. Modbus is now an open standard, administered by the Modbus-IDA (

30 Modbus and DNP3 Communication Protocols
Modbus and DNP are both byte-oriented protocols. Modbus is an application layer protocol, while DNP contains Application and Data Link Layers, with a pseudo-transport layer. Both protocols are widely used over a variety of physical layers, including RS-232, RS-422, RS-485, and TCP/IP. Modbus has a separate specification for use over TCP/IP (Modbus-TCP). With DNP, the protocol is simply encapsulated within TCP/IP.

31 Distributed Network Protocol 3.0

32 Distributed Network Protocol ( DNP) was developed by Harris, USA.
The Distributed Networking Protocol (DNP) was originally developed by Westronic, Inc. (now GE Harris) in 1990. The “DNP 3.0 Basic 4” protocol specification document set was released into the public domain in 1993, and ownership of the protocol was given to the newly formed DNP Users Group in October 1993. DNP was specifically developed for use in Electrical Utility SCADA Applications. It is now the dominant protocol in electrical utility SCADA systems, and is gaining popularity in other industries, including Oil & Gas, Water, and Waste Water.

33 In 1993 the responsibility for defining further DNP specification was given to DNP user Group.
DNP is based on the earlier work of IEC TC 57 It is based on Enhanced Performance architecture ( EPA) model There are 4 core documents to define DNP 3

34 Emergence of Standard DNP 3.0 Based on earlier work of IEC TC57
Developed by GE Harris DNP 3.0 is an open protocol that was developed to establish interoperability between RTUs, IEDs (Intelligent Electronic Devices) and master stations. DNP was largely influenced by North and South America, together with the African and Asian regions as IEC 101 was from the European community.

35 DNP 3.0 Structure Three Layered Protocol (EPA) Application (Layer 7)
Data Link (Layer 2) Physical (Layer 1) This structure is similar to IEC. However, DNP3 enhances EPA by adding a fourth layer, a pseudo transport layer that allows for message segmentation.

36 Additional Pseudo Layer
In addition Pseudo Transport Layer (Layer 4) Support Advance RTU functions DNP introduces a pseudo-transport layer(OSI Layer 4) to build application data messages larger than a single data link frame. In case of IEC, each 101 message should be contained in a single data link frame.

37 DNP3 is an open, intelligent, robust, and efficient modern SCADA protocol.
It can request and respond with multiple data types in single messages, segment messages into multiple frames to ensure excellent error detection and recovery, include only changed data in response messages, assign priorities to data items and request data items periodically based on their priority, respond without request (unsolicited), support time synchronization and a standard time format, allow multiple masters and peer-to-peer operations, and allow user definable objects including file transfer. In 1994, the IEEE Power Engineering Society’s Data Acquisition, Monitoring and Control Subcommittee formed a Task Force to review the communication protocols being used between Intelligent Electronic Devices (IEDs) and Remote Terminal Units (RTUs) in substations.

38 The IEEE Task Force found a very confusing, constantly changing environment that was increasing the cost and time to completion of substation SCADA systems. The IEEE Task Force collected information on approximately 140 protocols and compared them to a list of communication protocol requirements. This comparison resulted in a short list of protocols that met most of the requirements. This short list was balloted and two serial SCADA protocols tied for being the most acceptable: IEC and DNP3.

39 Structure of IEC 60870-5 Three Layered Protocol(EPA)
Application (Layer 7) Data Link (Layer 2) Physical (Layer 1)

40 For Tele Control System that require particularly
Why 3-Layered Structure of EPA 1) Short Reaction Time 2) Reduced Transmission Bandwidth BW: Measure of capacity of a transmission system. Measured in Hertz. How fast data can flow on a given transmission path. In Digital data transmission, BW is expressed as data speed in bits per second. Thus, higher the BW, more data can be transmitted.

41 Purpose of 60870-5 Protocol High Integrity Efficient Data Transmission
Protection Against Undetected Transmission Errors Correct data should reach the destination Without Loss

42 DNP 3.0 and IEC 60870-5-101 Both DNP 3.0 and IEC 60870-5-101
Designed for Transmission of SCADA Data for Electric Power System Control Wide Market Acceptance Intended for Use in SCADA Systems Using directly Connected Serial Links

43 DNP 3.0 and IEC 60870-5-101 60870-5-101 and DNP Usage
Collection of Binary Data Collection of Analog Data Collection, freezing and Clearing of Counters

44 DNP 3.0 and IEC 60870-5-101 Time Synchronization Time-Stamping Events
File Transfer Unsolicited Events Reporting

45 IEC Series It is bit serial communication standards. The standard is optimised for efficient and reliable transfer of process data and commands to and from geographically widespread systems over low-speed (up to 64 kbps) fixed and dial-up connections.

46 IEC – It deals the functionality for the interoperability of telecontrol equipment of different manufactures for the communication between substations and between substation and control centres . IEC This standard deals with values of integrated totals which are transmitted at periodic intervals to update the energy interchanges between utilities or between heavy industry and utilities.

47 IEC 60870-5-103 - This deals with informative interface of protection equipment .
IEC This present a combination of the application layer of IEC and the transport functions provided by a TCP/IP.

48 IEC 61850 This standard unifies UCA with European standard. It aims to design a communication system that provides interoperability between the functions to be performed in a substation.

49 IEC : This specifies hardware and protocol specifications for local systems in which a hand held unit is connected to only one tariff device at a time. This specifies hardware and protocol specifications for local systems in which a hand held unit is connected to only one tariff device at a time.

50 to access (read and write) memory locations, without
·     1) IEC is essentially a protocol providing a means to access (read and write) memory locations, without telling anything about how those memory locations should be filled with information. ·    2) IEC does neither say anything about the format and the interpretation of the data.

51 3) IEC 61107, developed for the purposes of local data exchange, does not follow the OSI model of layered protocols and does not have the functions provided by these layers. Therefore, although it is widely used over telephone networks, it is only possible with some compromises. 4)      IEC lacks advanced security functions. 5) Consequently, for each new meter type, even from the same manufacturer, a new device driver is required. Such drivers carry information about where and how to find the information and how to interpret it. The development of device drivers has proven to be a lengthy and costly exercise.

52 Communication - Interfaces & Protocols in Substation
* Serial (RS232/RS485/RS422) * LAN (Ethernet) Serial Protocols * IEC (Protection) * IEC (Tele Control) * DNP 3.0 (Protection, Monitoring & Metering) * Modbus RTU (Metering) LAN Protocols * IEC * DNP 3.0 over TCP/IP * MODBUS over Ethernet ( For Industries) * IEC 61850

53 Communication Protocols from Station Level Equipment.
* Serial * Ethernet Station Level Protocol * IEC * IEC * DNP 3.0 over TCP/IP * Modbus over Ethernet / Serial

54 DNP 3.0 * Supports Balanced Transmission Services * Supports
- Time Synchronization - Time-stamped events - Freeze/Clear Counters - Select before operate - Unsolicited Responses

55 IEC 870-5-101: Basic Telecontrol Tasks
Protocol Standard for the telecontrol of Electrical Power Transmission Systems. Permanent Directly Connected (Serial) Link between Telecontrol stations. Supports both Balanced/Unbalanced Transmissions Frame Type FT1.2 (1 Byte Checksum error check)

56 IEC This protocol standard is developed to Provide Network access for IEC Application Layer remains same. Does not use the Link Layer functions of IEC Some APCI (Application Protocol Control Information) Added to 101 ASDU To suitable for network transportation

57 Modbus Over Ethernet / Serial
Modbus Over Ethernet protocol if useful in sending Modbus messages on LAN / WAN network. Additional of 6 Bytes as a MBAP Header to basic Modbus over serial frame. Slave Address byte of serial Modbus frame is replaced with Unit Identifier.

58 IEC Companion Standard for Interface of Protection Equipment's Unbalanced Master Slave Serial Protocol. Protective Relays Act as Slave Devices. Station Controller as a Master. Physical Interface may be RS232,RS485 (or) Fiber Optic. Status indications,Measurement values, time-tagged events, control commands and clock synchronization Can be transferred between Master & Slave Devices .

59 Future ( IEC / UCA ) Standard for communication network and systems in Substation. Intended to integrate * Protection System * Control System * Substation Field Devices * Interface to Supervisory Control and Data Acquisition(SCADA) of Control Center * One of the most important features of IEC is that it covers not only communication, but also qualitative properties of engineering tools, measures for quality management, and configuration management & Conformance testing.

60 Communication Standards Within the Substation
IEC / DNP 3.0 Modbus / IEC 61850

61 What to Expect from Vendor on Protocols in their Devices??
IEC protocol * Communication Settings supported (Baudrate, Parity, IED address range config.). *Function Types supported (both Standard, Private). *COT Supported. *ASDU Type supported for each type of Tag or Parameter or information. *Information number (Standard, Private) for each parameter or tag & description for the same. *Any private ASDU ( ASDU 254,255 )implementation? If so then details. * Interoperability Table if any

62 DNP3.0 Protocol * Details of Communication Interface supported. * DNP Levels Supported. * Data Scaling Range if any? *Data Retrieval Method supported (unsolicited/polled static/exception). *Object Type & variations supported. *Data Map (Index number ) of each parameter.

63 Modbus (RTU) Protocol *Details of Communication Interface supported. *Relay Address range supported. *Function Types supported. *Address range for each parameter. *Data Type(16 bit(integer),32 bitz(long int), etc) *Multiplication factors if any. *Parameters type (Read only/read/write).

64 Typical Architecture of ERSA System
HMI # 2 HMI # 1 Remote Control Center Ethernet LAN ER 1000 400 & 220 kV Bay Control Units Protective Relays Tariff Meter

65 MV Architecture Remote HMI Local HMI Station Controller Modbus
The above shows the most commonly followed system Archtecture around the globe. The archtecture is an open one pemits integration with devices of multiple vendors. The above architecture is a totally decentralised and distributed Archtecture.All the Application programmes , logics and interlocks etc are residin in the emebeded station controller not in the HMI PC. This increses the system reliability many folds. In this Architecture the master station HMI acts as Display and archiving device. The station controller also act as the communication gateway enable connectivity to devicces of multiple open /standard protocol. Hardwired I/O’s for protection and Equipment Status Multifunction Meters Bay Control & Protection Units

66 ER 1000 Station Controller/Communication Gateway
Remote Control Center Local HMI ER 1000 DNP 3.0 / IEC 101 / IEC 104 / Modbus serial or Ethernet [ Slave components] IEC 103 Master DNP 3.0 Master Modbus Master Hardwired Analog/Digital I/O’s for protection and Equipment Status IEC Slave Components DNP 3.0 Slave Components Modbus Slave Components

67 Functionality's & Requirement of station Controller
Communication Gateway Protocol Converter Virtual RTU Data Concentrator Automation Unit Wired I/O’s Open H/W architecture and OS IEC compliant PLC programming Highly modular and hence easily expandable Superior architecture compared to a PC based architecture Can work in any extreme environmental conditions

68 What is Simple Substation Control And Monitoring System????...
* Present the state and operational Details of the field equipment in a user friendly manner through a powerful GUI Control and monitor the field equipment, protection IED’s locally or remotely Inbuilt -Energy Management System with communicable Multifunction Meters. Report Generation (Hourly, Daily, monthly, yearly), Alarms IED Parameterization, Disturbance Analysis. Online Sequence of Time Tagged Events (Source / System Time Stamp) printing and Event File Storing.

69 Serial to Fibre Optic Converter
A simple relay based substation control Local Workstation Remote HMI Ethernet/Dialup IEC 103 SOE Printer IEC 103 Modbus ER 05 RS 485/422 to RS Converter Serial to Fibre Optic Converter ER 10 ER 10 Multifunction Meters RTU Modbus/RS485 ER Relays ER Relays

70 Typical structure of today’s automated substation

71 Typical structure of tomorrow’s automated substation

72 Data telemetry was introduced for monitoring , Control and Protection.
Electric utilities were among the first entities to embrace data telemetery. Data telemetry was introduced for monitoring , Control and Protection. Development in communication, Computer, introduction of Intelligent Electronic Devices (IED) made information collection easier.

73 Different manufacturers introduced different rules for communicating and exchanging information among their intelligent devices. This introduced barriers in communicating with other device manufactured by others.

74 IEC Series Data Exchange for Meter Reading- Tariff and Load control

75 on the liberalised market. The functions are
  1) covers all metering functions required on the liberalised market. The functions are modelled using metering domain specific interface objects. This allows developing meters meeting exactly customer needs, using standard building blocks. It also allows innovation and competition by enhancing functionality in a standard way as required while maintaining interoperability. 2) It ensures unique identification of all metering equipment world-wide and unambiguous identification of all data elements.

76 3) It ensures unambiguous interpretation of all
metering data. 4) It allows controlled and selective access by various parties to application relevant data. 5) It provides various levels of security mechanisms to control access to data depending on authentication and access rights.  6) opens the way for exchanging data over various communication media, as the meter data model is independent of the communication protocol stack.

77 7) It brings interoperability, and therefore lowers costs,
as it is based on a standard data model and internationally approved standard protocols. 8) It allows developing a genuine driver, as the meter describes the functions available and sends all information necessary to interpret data. This allows meter manufacturers and data collection system providers to concentrate on the applications relevant for their customers rather than on connectivity and interfaces;      9) It comes complete with a conformance testing scheme to guarantee interoperability.

78 IEC , TASE.2 This deals with mechanism for exchanging time-critical data between control centres. In addition, it provides support for device control, general messaging and control of programs at a remote control centre.

79 ELCOM90 : This originated from a Scandinavian initiative to standardise information exchange between control centres. ELCOM is an international accepted

80 IEC 61970 This deals with CIM facilities for the integration of EMS applications developed independently by different vendors, between entire EMS systems developed independently, or between an EMS system

81 IEC 62210 This deals with safety, security and reliability of systems in Electrical Utilities. The deregulated market has imposed new threats and safe operation is essential in a deregulated environment.

82 IEC This provides a standard for interconnection of monitoring and control systems for wind power plants

83 IEC TR This report deals with Electronic communication in deregulated markets and makes a clear distinction between communications for control of energy systems and communications for the market

84 Possible trend in the near future
Ref: CIGRE report on Substation Automation

85 Possible trend in the far future
Ref: CIGRE report on Substation Automation

86

87

88 IEC TC57 Reference Architecture
Control centre Control Centre S C A D Metering Protection Physical Device Remote Terminal Unit Substation -103 Substation Automation -101 EMS Application 61970 61850 61968 DMS Subsystem

89 Relevant IEC Standards
Technical Committee 57 Power system control and associated communications Published IEC Telecontrol equipment and systems IEC Distribution Automation using Power Line Carrier IEC TR Power system Control and associated Communications – Data and Communication security IEC Communication for monitoring and control of Wind Power plants. TR Deregulated energy market communications confirmed EDIFACT as a recommended standard for business transactions In progress IEC Communication networks and systems in substations IEC System Interfaces for Distribution Management IEC Energy Management Systems Application Program Interfaces IEC Communication systems for Distributed Energy Resources IEC Hydro Electric Power Plants – Communication for monitoring and control. .

90 Introduction UCA

91 Brief Description about UCA 2.0
Electric Power Research Institute (EPRI) launched a concept in 1990 known as the Utility Communication Architecture or UCA. The goal behind UCA was to identify a suite of existing communication protocols that could be easily mixed and matched, provide the foundation for the functionality required to solve the utility enterprise communication issues, and be extensible for the future. After some initial revisions, the results of the project have been known as UCA UCA 2.0 is described in a technical report TR 1550 of the IEEE [2]. UCA2- SUBSTATION COMMUNICATION MODEL

92 Concept of 61850

93 Brief description about IEC 61850
The basis and the way of standardizing communications in IEC are entirely new. IEC was developed from IEC x and UCA 2.0. Comprehensive EPRI project UCA 2.0 International Agreed Goals IEC , -103, -104 IEC 61850  The goal of this standard IEC “Communication networks and systems in substations” is to provide interoperability between the IED’s from different suppliers or, more precisely, between functions to be performed in a substation but residing in equipment (physical devices) from different suppliers. Interchangeability is outside the scope of this standard, but the objective of interchangeability will be supported following this standard.  Interoperability has the following levels for devices from different suppliers: (1) The devices shall be connectable to a common bus with a common protocol (syntax) (2) The devices shall understand the information provided by other devices (semantics) (3) The devices shall perform together a common or joint function if applicable (distributed functions) Since there are no constraints regarding system structure and data exchange, some static and dynamic requirements shall be fulfilled to provide interoperability.

94 IEC 61850 What does IEC 61850 achieve
Defines structure for protection and control System configuration Communication between bay devices Standardised language for describing substation Fault records in Comtrade format IEC 61850 Standard communication with TCP - IP Time synchronisation with SNTP Based on Ethernet standard

95 Advantages in IEC 61850? IEC 61850 is a global standard for
“Communication Networks and Systems in Substations” It specifies an expandable data model and services It does not block future development of functions It specifies no protection or control functions It supports free allocation of functions to devices It is open for different system philosophies It provides the Substation Configuration description Language (SCL) It supports comprehensive consistent system definition and engineering It uses Ethernet and TCP/IP for communication Provides the broad range of features of mainstream communication It is open for future new communication concepts

96 GOOSE ??

97 GOOSE Receiver Device Y GOOSE Receiver Device Z
IEC – GOOSE Principle A device sends information by Multicasting. Only devices which are subscribers receive this message. In the example, Receiver Z receives the message. Receiver Y is not a subscriber. GOOSE Receiver Device Y GOOSE Sender Device X Ethernet GOOSE message GOOSE Receiver Device Z

98 Difference of IEC 61850 and UCA 2.0 : fast messaging “GOOSE”
Overtaking path for IEC GOOSE Normal message Fast GOOSE Buffer for Normal Message Ethernet Switch

99 IEC Key benefits IEC is a definite step towards unified substation communication, compared to the former IEC , DNP3 and most proprietary protocols: speed of exchanges: 100 Mbps instead of few 10kbps, enabling more data to be exchanged or a better operation or maintenance of the system, peer-to-peer links, replacing conventional wires with no extra hardware but and also permitting the design of innovative automation schemes, client-server relations offering flexible solutions easy to upgrade compared to master slave communications, object oriented pre-defined names, creating a single vocabulary between users, suppliers and supplier’s devices therefore facilitating the system integration and commissioning, XML interfaces referencing the above objects for straightforward exchanges between engineering tools in order to optimise the data consistency and minimise project lead times. communication conformance tests that help reducing the variety of interpretation found in many legacy protocols and leading to long integration tests and tuning.

100 IEC 61850 Based SAS Projects PGCIL Maharanibagh GIS:
400 KV Switchyard with 5 bays (Two Main) 220 KV Switchyard with 7 bays (Two Main) Separate SA systems for 400 and 200 kV Levels. FAT completed in Dec. 2005 PGCIL Bhatapara: 400 KV Switchyard with 6 Diameters (1½ Breaker) 220 KV Switchyard with 12 bays (Two Main +Transfer) Common SA system for 400 and 220 kV Levels PGCIL Raigarh: 400 KV Switchyard with 8 Diameters (1½ Breaker) 220 KV Switchyard with 9 Bays (Two Main +Transfer) FAT completed in Jan. 2006

101 PGCIL Maharanibagh 400 kV S/S
REL 670 REC 670 REL 670 Main I 7SA522 Main II BBP Bay Units Main I, Main II RET 670 Main I RET 670 Main II REB 500 Main I REB 500 Main II Busbar Line x 2 Autotransformer x 2 Auxiliaries IEC Redundant Ring network IEC Gateway DR WS Redundant HMI GPS Receiver Ethernet Switch Laser Printer DMP Bus Coupl. x 1

102 PGCIL Maharanibagh 220 kV S/S
REC 670 REL 670 Main I 7SA522 Main II BBP Bay Unit REB 500 Busbar Line x 4 Autotransformer x 2 Bus Coupler x 1 IEC Redundant Ring network IEC Gateway DR WS Redundant HMI Ethernet Switch Laser Printer DMP