1 44 th Annual Conference & Technical Exhibition By Thomas Hartman, P.E. The Hartman Company Georgetown, Texas www.hartmanco.com Sustainable Chilled Water Systems

2 44 th Annual Conference & Technical Exhibition Session Outline Overview: New Directions Required for Sustainability Plant Issues: What Equipment, What Configurations Chilled Water Distribution: What Are the Objectives Summary – Conclusion – Questions - Discussion Sustainable Chilled Water Systems

3 44 th Annual Conference & Technical Exhibition Keys in Configuring a Sustainable Chiller Plant BEWARE! A Lot of Traps Explore new directions and technologies Incorporate Effective Performance Measurement Establish Accountability Sustainable Chilled Water Systems

4 44 th Annual Conference & Technical Exhibition Sustainable Chilled Water Systems

5 44 th Annual Conference & Technical Exhibition Managing Development of a Sustainable Chiller Plant LEADERSHIP! Be Directed and In Charge Set Aggressive Performance Goals Incorporate Effective Performance Measurement Establish Accountability Sustainable Chilled Water Systems

6 44 th Annual Conference & Technical Exhibition The Equal Marginal Performance Principle Sustainable Chilled Water Systems

7 44 th Annual Conference & Technical Exhibition Equal Marginal Performance Principle Based Control Sustainable Chilled Water Systems

8 44 th Annual Conference & Technical Exhibition Characteristics of Cooling Loads for Various Climates Sustainable Chilled Water Systems

9 44 th Annual Conference & Technical Exhibition 1While Constant Speed Chiller Efficiency is nearly constant between 60% & 100% loading, the Efficiency of Variable Speed Centrifugal Chillers increases dramatically as load falls in that range. 2The Efficiency of Variable Speed Centrifugal Chillers is more significantly improved by the reduction in Condensing Water Temperature. The Variable Speed Difference Variable vs. Constant Speed Chiller Performance Sustainable Chilled Water Systems

10 44 th Annual Conference & Technical Exhibition "Natural Curve" Of VS Centrifugal Chiller The "Natural Curve" of a variable speed centrifugal chiller is shown as the black line. The Natural Curve is the locus of load points at various condenser and evaporator conditions at which the highest operating efficiency is achieved. To achieve optimum performance, chillers should be sequenced such that the on-line chillers operate as close as possible to their Natural Curve. Sustainable Chilled Water Systems

11 44 th Annual Conference & Technical Exhibition Tower Approach Temperature For 3 Tower System At lower wet bulb temperatures, the approach of cooling towers rises due to reduced moisture capacity of cooler air. By keeping towers on line and slowing fans and pumps, greater air and water volumes pass over larger surface areas per unit energy expended to improve part load approach temperatures, as shown in this chart. The total power to fans and pumps is the same for the variable speed and constant speed systems at each condition. Note the improved approach by slowing, not shedding towers at low loads. Sustainable Chilled Water Systems

12 44 th Annual Conference & Technical Exhibition Chiller Plant with Conventional Controls Equipment is operated independently with local PID temperature and pressure loops. Chillers and towers are sequenced to keep on-line equipment as fully loaded as possible. Plant optimization, if it is applied at all, requires another level of control that continuously resets the various setpoints, which can reduce overall system stability. Sustainable Chilled Water Systems

13 44 th Annual Conference & Technical Exhibition All-Variable Speed Demand Based Control Equipment is connected via an integrated network and operation is coordinated to maintain lowest overall energy use at all load conditions using demand based control and natural curve sequencing of equipment. Unless incorporated as design criteria, temperature and pressure setpoints are not employed except as operating limits. Sustainable Chilled Water Systems

14 44 th Annual Conference & Technical Exhibition Network Enabled Demand Based Control Of All-Variable Speed Chiller Plants Control Features: Simple Direct Control Relationships between Chillers, Pumps and Tower Fans "Natural Curve" Sequencing of chillers Benefits: Ultra-Efficient Plant Operation Simpler and More Stable Plant Operation Longer Life for Equipment and Lower Maintenance Costs Sustainable Chilled Water Systems

15 44 th Annual Conference & Technical Exhibition Sustainable Chilled Water Plants Ultra Efficient All-Variable speed chiller plants are generally configured the same conventional plants, but must employ new operating strategies to achieve efficient operation. Network enabled Demand Based Control provides ultra- efficient, simple and stable control for all-variable speed chiller plants. Implementing all-variable speed plants successfully requires special emphasis on performance Sustainable Chilled Water Systems

16 44 th Annual Conference & Technical Exhibition All-Variable Speed/Flow Distribution Systems Background: Current distribution systems New Choices: Why all-variable flow distribution systems work well with variable speed chillers Application: Developing effective all-variable flow chilled water distribution systems. Scale: Large scale primary/ booster all-variable flow chilled water distribution systems Sustainable Chilled Water Systems

17 44 th Annual Conference & Technical Exhibition Primary/Secondary CHW Distribution System Sustainable Chilled Water Systems

18 44 th Annual Conference & Technical Exhibition Variable Primary Flow CHW Distribution System Sustainable Chilled Water Systems

19 44 th Annual Conference & Technical Exhibition Variable Speed Pump Operation Comparison Sustainable Chilled Water Systems

20 44 th Annual Conference & Technical Exhibition Sustainable Chilled Water Systems

21 44 th Annual Conference & Technical Exhibition Improving Efficiency of Variable Flow Distribution System for Demand Based Control Reduce the pressure drop through chilled water valves. Line size valves with zero pressure drop at full flow are effective if they are properly controlled. Operate chilled water pumps with network control that reacts to actual demand for flow by the valves served and sequence pumps to so that on-line pumps operate as close as possible to their natural curve. Sustainable Chilled Water Systems

22 44 th Annual Conference & Technical Exhibition Sustainable Chilled Water Systems

23 44 th Annual Conference & Technical Exhibition Demand Based Control Applied to Distribution System Elements Valve Control: Multivariable "Intelligent Iterative Control" is used whereby valve adjustment is based on setpoint error, pump speed, chilled water temperature, and current valve position. Pump Control: "Orifice area" pump speed control adjusts speed based on percent of total valve orifice area currently open and further adjusted by the number of valves nearly wide open. Pump Sequencing is based on "natural curve" principle. Sustainable Chilled Water Systems

24 44 th Annual Conference & Technical Exhibition Demand Based Control of Variable Flow Distribution System Sustainable Chilled Water Systems

25 44 th Annual Conference & Technical Exhibition Network Enabled Demand Based Control Of All-Variable Speed Distribution Systems Control Features: Line sized valves for near zero pressure drop. Simple and direct "Valve Orifice Area" control of chilled water pumps Distribution pumps sequence with chillers according to "Natural Curve" Benefits: Ultra-Efficient integrated system operation. Simpler and more stable plant operation Longer life for equipment and lower maintenance costs Sustainable Chilled Water Systems

26 44 th Annual Conference & Technical Exhibition Demand Based Control of All-Variable Flow Primary/Booster Distribution System Sustainable Chilled Water Systems

27 44 th Annual Conference & Technical Exhibition Sustainable Chilled Water Distribution Systems All-variable speed chilled water distribution systems are configured very similar to newer conventional systems, but employ new operating strategies. Network enabled iterative and demand based control provide ultra-efficient, simple and stable control for all-variable speed distribution systems. When properly configured and operated new technology all- variable speed chilled water distribution systems ensure every load served is satisfied while providing ultra-efficient operation. Sustainable Chilled Water Systems

28 44 th Annual Conference & Technical Exhibition Sustainable Chilled Water Systems

29 44 th Annual Conference & Technical Exhibition Implementing All-Variable Speed Chilled Water Systems WHY? Achieves approximately 0.5 kW/ton overall annual plant & distribution system performance – about half the energy use of most existing plants. Simple, stable, ultra-efficient control with reduced system maintenance. HOW? Network control coordinates all-variable speed equipment for optimum operation in response to actual demand on system. Plant is designed for direct control among components, and distribution system to minimize pressure drops and variations Sustainable Chilled Water Systems

30 44 th Annual Conference & Technical Exhibition Success With All-Variable Speed Chiller Plants New variable speed system technologies require special effort through design/construction/turnover Owner/Designer team must work together to ensure all problems will be solved Nearly every chiller plant is a good potential application for all- variable speed technologies Focus on Performance. Let overall plant performance drive the selection of configuration, equipment and controls Be certain the project incorporates measurement and verification and accountability for achieving projected performance Sustainable Chilled Water Systems

31 44 th Annual Conference & Technical Exhibition Next Steps Toward a Sustainable Chilled Water System 1.Instrument current facility or facilities to obtain actual energy used to generate and distribute chilled water. 2.Calculate the potential avoided costs by converting to an ultra-efficient all-variable speed chilled water system. 3.Develop cost-effective budgets, goals and target dates to implement a conversion to a more sustainable system. 4.Implement the project or projects required to achieve the targeted plant performance. 5.Incorporate performance verification and performance accountability to ensure the goals are achieved and maintained. Sustainable Chilled Water Systems

32 44 th Annual Conference & Technical Exhibition By Thomas Hartman, P.E. The Hartman Company Georgetown, Texas www.hartmanco.com Sustainable Chilled Water Systems Questions & Discussion