Presentation is loading. Please wait.

Presentation is loading. Please wait.

ECE 4411 Voltage Regulation. ECE 4412 Voltage Regulation (continued) E nl = no-load output voltage –Measure with a voltmeter when no load is connected.

Similar presentations


Presentation on theme: "ECE 4411 Voltage Regulation. ECE 4412 Voltage Regulation (continued) E nl = no-load output voltage –Measure with a voltmeter when no load is connected."— Presentation transcript:

1 ECE 4411 Voltage Regulation

2 ECE 4412 Voltage Regulation (continued) E nl = no-load output voltage –Measure with a voltmeter when no load is connected to the transformer V rated = voltmeter reading at the output terminals when the transformer is supplying the rated apparent power These voltages are all either High-side or Low-side voltages!

3 ECE 4413 Voltage Regulation (continued) Measurements are not always easy to make, so use the equivalent circuit.

4 ECE 4414 When the breaker is open, no current flows in R eq,LS, jX eq,LS, or Z LOAD,LS, therefore V out = V LS = E’ LS = E nl

5 ECE 4415 With rated load on the secondary, E’ LS = I LS Z eq,LS + V LS I LS = rated low-side current at a specified power factor V LS = rated low-side voltage Z eq,LS = equivalent impedance of the transformer referred to the low-side E’ LS = no-load low-side voltage

6 ECE 4416 Example 2.7 The equivalent low-side parameters of a 250kVA, 4160 – 480V, 60 Hz transformer areR eq,LS = 0.00920 Ω and X eq,LS = 0.0433 Ω. The transformer is operated in the step-down mode and is delivering rated current at rated voltage to a 0.840 power- factor lagging load. Determine

7 ECE 4417 –the no-load voltage –The actual input voltage on the high- side –The high-side current –The input impedance –The voltage regulation –The voltage regulation if the power factor of the load is 0.840 leading –Sketch the tip-to-tail phasor diagram of the secondary circuit for the 0.840 power factor lagging load. Show all voltage drops.

8 ECE 4418

9 9 Low-Side Output

10 ECE 44110

11 ECE 44111

12 ECE 44112 The high-side current The input impedance

13 ECE 44113 The voltage regulation

14 ECE 44114 Voltage Regulation if the power factor is 0.840 leading Regulation is negative because of a voltage rise in the transformer due to resonant effects.

15 ECE 44115 The “tip-to-tail” phasor diagram for the 0.840 power factor lagging load.

16 ECE 44116 Component Phasors

17 ECE 44117 Tip-to-Tail Addition


Download ppt "ECE 4411 Voltage Regulation. ECE 4412 Voltage Regulation (continued) E nl = no-load output voltage –Measure with a voltmeter when no load is connected."