Presentation is loading. Please wait.

Presentation is loading. Please wait.

“Importance of Reactive Power Management, Voltage Stability and FACTS Applications in today’s Operating Environment” Sharma Kolluri Manager of Transmission.

Similar presentations


Presentation on theme: "“Importance of Reactive Power Management, Voltage Stability and FACTS Applications in today’s Operating Environment” Sharma Kolluri Manager of Transmission."— Presentation transcript:

1 “Importance of Reactive Power Management, Voltage Stability and FACTS Applications in today’s Operating Environment” Sharma Kolluri Manager of Transmission Planning Entergy Services Inc Engineering Seminar Organized by IEEE Mississippi Section Jackson State University August 20, 2010

2 Outline Introduction VAR Basics Voltage Stability FACTS
Applications at Entergy Summary .

3 Voltage Profile during Aug 14th Blackout
Voltages decay to almost 60% of normal voltage. This is probably the point that load started dropping off. However, the recovery is too slow and generators are not able to maintain frequency during this condition. Many generators trip, load shedding goes into effect, and then things just shut down due to a lack of generation.

4 A “Near” Fast Voltage Collapse in Phoenix in 1995
North American Electric Reliability Council, System Disturbances, Review of Selected 1995 Electric System Disturbances in North America, March 1996.

5 Recommendation#23 Strengthen Reactive Power and Control Practices in all NERC Regions “Reactive power problem was a significant factor in the August 14 outage, and they were also important elements in the several of the earlier outages” -Quote form the outage report

6 Reactive Power

7 Laws of Reactive Physics
System load is comprised of resistive current (such as lights, space heaters) and reactive current (induction motor reactance, etc.). Total current IT has two components. IR resistive current IQ reactive current IT is the vector sum of IR & IQ IT = IR + jIQ IT IQ IR North American Electric Reliability Corporation

8 Laws of Reactive Physics
Complex Power called Volt Amperes (“VA”) is comprised of resistive current IR and reactive current IQ times the voltage. “VA” = VIT* = V (IR – jIQ) = P + jQ Power Factor (“PF”) = Cosine of angle between P and “VA” P = “VA” times “PF” System Losses Ploss = IT2 R (Watts) Qloss = IT2 X (VARs) VA Q P North American Electric Reliability Corporation

9 Reactive Physics – VAR loss
Every component with reactance, X: VAR loss = IT2 X Z is comprised of resistance R and reactance X On 138kV lines, X = 2 to 5 times larger than R. One 230kV lines, X = 5 to 10 times larger than R. On 500kV lines, X = 25 times larger than R. R decreases when conductor diameter increases. X increases as the required geometry of phase to phase spacing increases. VAR loss Increases in proportion to the square of the total current. Is approximately 2 to 25 times larger than Watt loss. North American Electric Reliability Corporation

10

11 Reactive Power for Voltage Support
Reactive Loads VARs flow from High voltage to Low voltage; import of VARs indicate reactive power deficit

12 Reactive Power Management/Compensation
What is Reactive Power Compensation? Effectively balancing of capacitive and inductive components of a power system to provide sufficient voltage support. Static and dynamic reactive power Essential for reliable operation of power system prevention of voltage collapse/blackout Benefits of Reactive Power Compensation: Improves efficiency of power delivery/reduction of losses. Improves utilization of transmission assets/transmission capacity. Reduces congestion and increases power transfer capability. Enhances grid reliability/security.

13 Transmission Line Real and Reactive Power Losses vs. Line Loading
Source: B. Kirby and E. Hirst 1997, Ancillary-Service Details: Voltage Control, ORNL/CON-453, Oak Ridge National Laboratory, Oak Ridge, Tenn., December 1997.

14 Static and Dynamic VAR Support
Static Reactive Power Devices Cannot quickly change the reactive power level as long as the voltage level remains constant. Reactive power production level drops when the voltage level drops. Examples include capacitors and inductors. Dynamic Reactive Power Devices Can quickly change the MVAR level independent of the voltage level. Reactive power production level increases when the voltage level drops. Examples include static VAR compensators (SVC), synchronous condensers, and generators.

15 Voltage Stability

16 Common Definitions Voltage stability - ability of a power system to maintain steady voltages at all the buses in the system after disturbance. Voltage collapse - A condition of a blackout or abnormally low voltages in significant part of the power system. Short term voltage stability - involves the dynamics of fast acting load components such as induction motors, electronically controlled loads, and HVDC converters. Long term voltage stability - involves slower acting equipments such as tap-changing transformer, thermostatically controlled loads, and generator limiters.

17 What is Voltage Instability/Collapse?
A power system undergoes voltage collapse if post-disturbance voltages are below “acceptable limits” voltage collapse may be due to voltage or angular instability Main factor causing voltage instability is the inability of the power systems to “maintain a proper balance of reactive power and voltage control”

18 Voltage Instability/Collapse
The driving force for voltage instability is usually the load The possible outcome of voltage instability: loss of loads loss of integrity of the power system Voltage stability timeframe: transient voltage instability: 0 to 10 secs long-term voltage stability: 1 – 10 mins Randy Graves of Distribution Asset Planning is compiling the list

19 Voltage stability causes and analysis
Causes of voltage instability Increase in loading Generators, synchronous condensers, or SVCs reaching reactive power limits Tap-changing transformer action Load recovery dynamics Tripping of heavily loaded lines, generators Methods of voltage stability analysis Static analysis methods Algebraic equations, bulk system studies, power flow or continuation power flow methods Dynamic analysis methods Differential as well as algebraic equations, dynamic modeling of power system components required

20 Generator Capability Curve
Over-excitation Limit Lagging (Over-excited) 0.8 pf line Stator Winding Heating Limit - Per unit MVAR (Q) + Normal Excitation (Q = 0, pF = 1) MW Turbine Limit Leading (Under-excited) Under-excitation Limit Stability Limit

21 P-V Curve

22 Q-V Curve 200 Q-V Curve with Detailed Load Model -80 -60 -40 -20 20 40
Peak Load with Fixed Taps -80 -60 -40 -20 20 40 60 80 100 120 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 Voltage (p.u.) Mvars Base Case Contingency

23 Key Concerns Limit UVLS activation Minimize motor tripping
Voltage (pu)

24 Possible Solutions for Voltage Instability
Install/Operate Shunt Capacitor Banks Add dynamic Shunt Compensation in the form of SVC/STATCOM to mitigate transient voltage dips Add Series Compensation on transmission lines in the problem area Implement UVLS Scheme Construct transmission facilities

25 Voltage Collapse

26 Fault Induced Delayed Voltage Recovery (FIDVR)
FIDVR Definition Load Models

27 Fault Induced Delayed Voltage Recovery (FIDVR)
What is it? After a fault has cleared, the voltage stays at low levels (below 80%) for several seconds Results in dropping load / generation or fast voltage collapse 4 key factors drive FIDVR: Fault Duration Fault Location High load level with high Induction motor load penetration Unfavorable Generation Pattern

28 Southern Company was really unaware that the system was evolving to the point where concern about exposure to FIDVR was warranted. However, as a result of the Union City event in 1999, we became acutely aware that FIDVR exposure existed. The Union City event was actually a multiple contingency event – an event well beyond even NERC Category D, and thus you would never plan and build for such an event. This is a DFR voltage versus time recording at a plant about 50 miles NW of the fault location. Note that the voltage did not fully recover for about 15 seconds. The depth of the voltage depression was more severe at load serving substations more removed from generation (source of dynamic Mvars)

29

30 Load characteristics The accuracy of analytical results depends on modeling of power system components, devices, and controls. Power system components - Generators, excitation systems, over/under excitation limiters, static VAr systems, mechanically switched capacitors, under load tap changing transformers, and loads among others. Loads are most difficult to model. Complex in behavior varying with time and location Consist of a large number of continuous and discrete controls and protection systems Dynamics of loads, especially, induction motors at low voltage levels should be properly modeled.

31 Induction motor characteristics
Impact of fault on transmission grid Depressed voltages at distribution feeders and motor terminals Reduction of electrical torque by the square of the voltage resulting in slow down of motors The slow down depends on the mechanical torque characteristics and motor inertias With fault clearing Speed – per unit Torque -per unit Electric torque 1.0 Constant load torque Square-law load torque Fig. 1 Induction motor characteristics Partial voltage recovery Slowed motors draw high reactive currents, depressing voltage magnitudes Motor will reaccelerate to normal speed if, electrical torque>mechanical torque else, the motors will rundown, stall, and trip The problem is severe in the summer time with large proportion of air conditioner motors

32 Air conditioner motor characteristics
Main portion (80-87%) consumed by compressor motor Electromagnetic contactor drop out between (43-56%) of the nominal voltage and reclose above drop out voltage Stalling at (50-73%) of the nominal voltage Thermal overload protection act if motors stall for 5-20 seconds The operation time of thermal over load (TOL) protection relay is inversely proportional to the applied voltage at the terminal Air conditioner should be modeled to analyze the short term voltage stability problem Quite important for utilities in the Western interconnection

33 Fig. 2 Traditional load model
Load modeling Old models – Loads are represented as lumped load at distribution feeder Does not consider the electrical distance between the transmission bus and the end load components The diversity in composition and dynamic behavior of various electrical loads is not modeled Modeling WECC interim model 20% of the load as generic induction motor load 80% constant current P and constant impedance Q Distribution Capacitor Distribution Bus OLTC Transmission Bus Lumped Load (ZIP load) Fig. 2 Traditional load model 33

34 Composite load modeling
Representation of distribution equivalent Feeder reactance Substation transformer reactance Parameters of various load components Discharge lighting Electronic Loads Constant Impedance loads Motor loads Distribution Capacitor Bus 3 Distribution Capacitor Transmission Bus Bus 1 Bus 2 Distribution Bus Substation Capacitor OLTC Distribution Feeder Feeder Equivalent Static Loads (Constant impedance, constant current, constant impedance loads) Dynamic Loads (Small motor, Large motor, trip motor loads) Fig. 3 Composite load model structure

35 FACTS

36 What is FACTS? Alternating Current Transmission Systems Incorporating Power Electronic Based and Other Static Controllers to Enhance Controllability and Increase Power Transfer Capability. power semi-conductor based inverters information and control technologies

37 Major FACTS Controllers
Static VAR Compensator (SVC) Static Reactive Compensator (STATCOM) Static Series Synchr. Compensator (SSSC) Unified Power Flow Controller (UPFC) Back-To-Back DC Link (BTB)

38 FACTS Applications UPFC STATCOM BTB SSSC Voltage Control
Power System Stability SSSC S/S UPFC Power Generation Load Increased Transmission Capacity Inter-area Control Inter-tie Reliability Power Flow Control System Reliability Improved Power Quality Enhanced Import Capability Inter-connected RTO System Power System BTB STATCOM

39 Static VAr compensator (SVC)
Variable reactive power source Can generate as well as absorb reactive power Maximum and minimum limits on reactive power output depends on limiting values of capacitive and inductive susceptances. Droop characteristic XC TCR XL I V Firing angle control Fig. 4 Schematic diagram of an SVC

40 Static compensator (STATCOM)
Voltage source converter device Alternating voltage source behind a coupling reactance Can be operated at its full output current even at very low voltages Depending upon manufacturer's design, STATCOMs may have increased transient rating both in inductive as well as capacitive mode of operation Transformer DC-AC switching converter I X System bus Cs Vdc V E Fig. 5 Schematic diagram of STATCOM

41 Technology Applications at Entergy

42 Technology Applications at Entergy to Address Reactive Power Issues
Large Shunt Capacitor Banks UVLS Series Compensation SVC Coordinated Capacitor Bank Control DVAR AVR

43 2006 Power Systems Conference and Exposition
Determining Reactive Power Requirements in the Southern Part of the Entergy System for Improving Voltage Security – A Case Study Sharma Kolluri Sujit Mandal Entergy Services Inc New Orleans, LA Panel on Optimal Allocation of Static and Dynamic VARS for Secure Voltage Control 2006 Power Systems Conference and Exposition Atlanta, Georgia October 31, 2006

44 Areas of Voltage Stability Concern
North Arkansas Mississippi West of the Atchafalaya Basin (WOTAB) Southeast Louisiana Western Region Amite South/DSG

45 Study Objective Identify Voltage Stability Problems in the DSG area
Determine the proper mix of reactive power support to address voltage stability problem Determine size and location of static and dynamic devices.

46 Downstream of Gypsy Area - Critical Facilities
Ninemile Units MW MW MW MW MW 115 kV 230 kV Michoud Units MW MW MW 115 kV kV Little Gypsy-South Norco 230kV line Waterford-Ninemile 230kV line

47 DSG Issues Area load growth 1.6% projected for 2003 - 2013
Weather normalized to 100º F Projected peak load – 3800 MW Area power factor - Low 94% at peak load Worst double contingency Loss of the Waterford to Ninemile 230 kV transmission line and one of the 230 kV generating units at Ninemile or Michoud Michoud Ninemile New Orleans area voltage profile on June 2, 2003 (with 2 major generators offline) Area Problems Thermal overloads of underlying 115 kV and 230 kV transmission system Depressed voltages throughout New Orleans metro area potentially leading to voltage collapse and load shedding

48 Various Steps Used for Determining Reactive Power Requirements
Step 1 – Problem identification Step 2 – Determining total reactive power requirements Step 3 – Sizing and locating dynamic devices Step 4 – Sizing and locating static shunt devices Step 5 – Verification of reactive power requirements

49 Tools & Techniques Used
Various tools and techniques used for analysis purposes PV analysis using PowerWorld Transient stability using PSS/E Dynamics Mid-term stability using PSS/E Dynamics PSS/E Optimal Power Flow Detailed Models used Motor models and appropriate ZIP model for dynamic analysis Tap-changing distribution transformers, overexcitation limiters, self-restoring loads modeled in mid-term stability study

50 Criteria/Requirements
Minimize motor tripping Improve post-fault voltage Voltage (pu)

51 Steady State Analysis Results

52 PV Curve Ninemile Unit 4 out-of-service Trip Ninemile Unit 5 and Waterford – Ninemile 230 kV line
cc

53 Dynamic Analysis

54 Stability Simulation Ninemile Unit 4 out-of-service Trip Ninemile Unit 5 and Waterford – Ninemile 230 kV line

55 Process for Determining Reactive Power Requirements
Approx 700 MVAr of reactive power shortage identified in the DSG How much static and how much dynamic? Criteria for determining static and dynamic requirements Voltage at critical buses should recover to 1 pu in several seconds Voltage at critical buses should recover to 0.9 pu within seconds Voltage should not dip below 0.7 pu for more than 20 cycles Generator reactive power output should be below Qmax Factors considered in sizing static/dynamic devices Short circuit levels, size & location of the stations, number and existing size of cap banks, back-to-back switching, etc

56 SVC Size and Location Sites considered Size Ninemile 230 kV
Gretna 115 kV Paterson 115 kV Size 300 MVAR 500 MVAR Optimal size and location

57 Steps to locate Static Shunt Devices
Static shunt requirements – 400 MVAR approximately Options available to locate the static shunt devices on the transmission or distribution systems OPF Program used to come up with size and location of shunt devices

58 OPF Application PSS/E OPF Program used
Objective Function – Minimize adjustable shunts OPF simulated for critical contingencies

59 List of Shunt Capacitor Banks Banks Recommended

60 Simulation Results with the Capacitors and SVC Ninemile Unit 4 out-of-service Trip Ninemile Unit 5 and Waterford – Ninemile 230 kV line

61 SVC Performance Ninemile Unit 4 out-of-service Trip Ninemile Unit 5 and Waterford – Ninemile 230 kV line

62 Summary Process for determining static and dynamic reactive power requirements discussed OPF program utilized for sizing/locating static shunt capacitor banks Results verified using mid-term stability simulations Study recommendation – 400 MVAR of static shunt devices and 300 MVAR of dynamic shunt compensation

63 Ninemile SVC Configuration
= 75 MVAr = 150 MVAr

64 External Device Control Single line diagram of SVC and MSC

65 SVC Ninemile

66 SVC Ninemile

67 SVC Topology: 2 x 75MVAr TSC & 1 x 150MVAr TSC
Porter 0/+300Mvar SVC SVC Topology: 2 x 75MVAr TSC & 1 x 150MVAr TSC

68 Porter Static Var Compensator (SVC)
Maintains system voltage by continuously varying VAR output to meet system demands Controls capacitor banks on the transmission system to match reactive output to the load requirements.

69 Porter SVC

70 Series Capacitor – Dayton Bulk 230kV Station
The Capacitor offsets reactance in the line, making it appear to the system to be half of its actual length. Power flows are redirected over this larger line, unloading parallel lines and increasing transfer capability.

71 DSMES Unit Stores Energy in a superconducting coil
Automatically releases energy to the system when needed to ride through voltage dips caused by faults. This unit improves power quality and reduces customer loss of production.

72 Industry Issues Coordination of reactive power between regions
No clearly defined requirements for reactive power reserves Proper tools for optimizing reactive power requirements Incentive to reduce losses

73 Summary The increasing need to operate the transmission system at its maximum safe transfer limit has become a primary concern at most utilities Reactive power supply or VAR management is an important ingredient in maintaining healthy power system voltages and facilitating power transfers Inadequate reactive power supply was a major factor in most of the recent blackouts

74 Questions?

75 Under Voltage Load Shed Logic - Western Region
T&D Planning April 2010

76 Western Region – Overview
≤ 230 kV Tie Lines Generation Load Center

77 Load Projection 2010 peak: 1770 MW 2012 peak: 1852 MW

78 Sample PV Curve Result Lewis Creek Unit 1 & China-Porter 230kV Out - 2010

79 2010 Summer PV Curve Analysis
Scenarios P Limit (MW) With 3% Margin (MW) Voltage (4/8 Buses) (pu) Lewis Creek U1 out 2385 2313 0.84 – 0.89 Lewis Creek U1 + China-Jacinto out 2260 2192 0.83 – 0.89 Lewis Creek U1 + Grimes-Crockett out 2230 2163 0.86 – 0.91 Lewis Creek U1 + China-Porter out 2065 2003 0.85 – 0.93 Approved Construction Plan Projects included: *Relocate Caney Creek 138kV

80 Dynamic Analysis Results

81 Results: 2010 case without load shed
Case 3 Voltages (pu): Goslin: 0.810; Conroe: 0.855; Cleveland: 0.909; Jacinto: 0.924; Dayton: 0.944; Huntsville: 0.944 Case 4 Voltages (pu): Goslin: 0.757; Conroe: 0.800; Dayton: 0.913; Huntsville: 0.928; Cleveland: 0.928; Rivtrin: 0.941

82 2010 Summer Conditions - Dynamics Analysis
Lewis Creek Unit 1 outaged in the base case 50% induction motor load is modeled Result: Shed Load Block 1 (183 MW)

83 Observations for 2010 Summer Peak Conditions
Existing load shed logic in Western Region OK for 2010 Summer conditions Voltage at some critical buses drop below 0.7 pu for more than 20 cycles – Potential of motor load tripping Conclusions for 2010 Summer Reducing load shed blocks to MW in Western Region has no negative impact

84 Results: 2010 case with load shed (Block 1)
Case 3 Voltages (pu): Goslin: 0.872; Conroe: 0.902; Cleveland: 0.934; Jacinto: 0.948; Dayton: 0.966; Huntsville: 0.968 Case 4 Voltages (pu): Goslin: 0.827; Conroe: 0.855; Dayton: 0.939; Cleveland: 0.951; Huntsville: 0.954; Jacinto: 0.964

85 Conclusions and Recommendations
Retain the exiting UVLS logic Change the load blocks Block one: 180 MW Block two: 70 MW (existing size 111 MW)

86 Proposed Load Shed Logic
4/8 buses <0.90 pu Armed all time Drop load One or more Lewis Creek units in-service? OEL at Lewis Creek units 4/8 buses < 0.92 pu Time Delay 3 seconds Load Blocks: Block 1: 175 MW Alden: 50 MW Metro: 35 MW Oakridge:30 MW Goslin: 60 MW Block 2: 75 MW In the vicinity of Block 1 Monitored Buses: Metro 138kV Goslin 138kV Alden 138kV Oakridge 138kV Huntsville 138kV Rivtrin 138 kV Poco 138 kV Conroe 138 kV Reset the Process for next LVSH block Load Blocks: Block 1: 175 MW Block 2: 75 MW The above conditions need to be met for 3 scans to trigger load shedding


Download ppt "“Importance of Reactive Power Management, Voltage Stability and FACTS Applications in today’s Operating Environment” Sharma Kolluri Manager of Transmission."

Similar presentations


Ads by Google