1 “Energy Efficiency Guide for Industry in Asia”
Refrigeration & Air Conditioning Presentation from the “Energy Efficiency Guide for Industry in Asia” Electrical Equipment/ Refrigeration & AC TO THE TRAINER This PowerPoint presentation can be used to train people about the basics of refrigeration and air condonditioning. The information on the slides is the minimum information that should be explained. The trainer notes for each slide provide more detailed information, but it is up to the trainer to decide if and how much of this information is presented also. Additional materials that can be used for the training session are available on under “Energy Equipment” and include: Textbook chapter on this energy equipment that forms the basis of this PowerPoint presentation but has more detailed information Quiz – ten multiple choice questions that trainees can answer after the training session Option checklist – a list of the most important options to improve energy efficiency of this equipment

2 Electrical Equipment/
Introduction Type of refrigeration Assessment of refrigeration and AC Energy efficiency opportunities Electrical Equipment/ Refrigeration & AC

3 High Temperature Reservoir Low Temperature Reservoir
Introduction High Temperature Reservoir Low Temperature Reservoir R Work Input Heat Absorbed Heat Rejected How does it work? Electrical Equipment/ Refrigeration & AC Refrigeration and air conditioning is used to cool products or a building environment. The refrigeration or air conditioning system (R) transfers heat from a cooler low-energy reservoir to a warmer high-energy reservoir

4 Electrical Equipment/
Introduction How does it work? Thermal energy moves from left to right through five loops of heat transfer: 1) Indoor air loop 2) Chilled water loop 3) Refrigerant loop 4) Condenser water loop 5) Cooling water loop Electrical Equipment/ Refrigeration & AC There are several heat transfer loops in a refrigeration system as shown in Figure 2. Thermal energy moves from left to right as it is extracted from the space and expelled into the outdoors through five loops of heat transfer: Indoor air loop. In the left loop, indoor air is driven by the supply air fan through a cooling coil, where it transfers its heat to chilled water. The cool air then cools the building space. Chilled water loop. Driven by the chilled water pump, water returns from the cooling coil to the chiller’s evaporator to be re-cooled. Refrigerant loop. Using a phase-change refrigerant, the chiller’s compressor pumps heat from the chilled water to the condenser water. Condenser water loop. Water absorbs heat from the chiller’s condenser, and the condenser water pump sends it to the cooling tower. Cooling tower loop. The cooling tower’s fan drives air across an open flow of the hot condenser water, transferring the heat to the outdoors. (Bureau of Energy Efficiency, 2004)

5 Electrical Equipment/
Introduction AC Systems AC options / combinations: Electrical Equipment/ Refrigeration & AC Air Conditioning (for comfort / machine) Split air conditioners Fan coil units in a larger system Air handling units in a larger system Depending on applications, there are several options / combinations of air conditioning, which are available for use: Air conditioning (for space or machines) Split air conditioners Fan coil units in a larger system Air handling units in a larger system

6 Electrical Equipment/
Introduction Refrigeration systems for industrial processes Small capacity modular units of direct expansion type (50 Tons of Refrigeration) Centralized chilled water plants with chilled water as a secondary coolant (50 – 250 TR) Brine plants with brines as lower temperature, secondary coolant (>250 TR) Electrical Equipment/ Refrigeration & AC The following refrigeration systems exist for industrial processes (e.g. chilling plants) and domestic purposes (modular units, i.e. refrigerators): Small capacity modular units of the direct expansion type similar to domestic refrigerators. Centralized chilled water plants with chilled water as a secondary coolant for a temperature range over typically 5 oC. They can also be used for ice bank formation. Brine plants, which use brines as a lower temperature, secondary coolant for typically sub-zero temperature applications, which come as modular unit capacities as well as large centralized plant capacities. The plant capacities up to 50 TR (tons of refrigeration) are usually considered as small capacity, 50 – 250 TR as medium capacity and over 250 TR as large capacity units.

7 Electrical Equipment/
Introduction Refrigeration at large companies Bank of units off-site with common Chilled water pumps Condenser water pumps Cooling towers More levels of refrigeration/AC, e.g. Comfort air conditioning (20-25 oC) Chilled water system (8 – 10 oC) Brine system (< 0 oC) Electrical Equipment/ Refrigeration & AC A large company may have a bank of units, often with common chilled water pumps, condenser water pumps, cooling towers, as an off site utility. The same company may also have two or three levels of refrigeration and air conditioning such as a combination of: Comfort air conditioning (20 – 25 oC) Chilled water system (8 – 10 oC) Brine system (sub-zero applications)

8 Electrical Equipment/
Introduction Type of refrigeration Assessment of refrigeration and AC Energy efficiency opportunities Electrical Equipment/ Refrigeration & AC This section include various types of refrigeration such as Vapour Compression Refrigeration and Vapour Absorption Refrigeration system

9 Electrical Equipment/
Types of Refrigeration Refrigeration systems Vapour Compression Refrigeration (VCR): uses mechanical energy Vapour Absorption Refrigeration (VAR): uses thermal energy Electrical Equipment/ Refrigeration & AC The two principle types of refrigeration plants found in industrial use are: Vapour compression refrigeration (VCR) and vapour absorption refrigeration (VAR). VCR uses mechanical energy as the driving force for refrigeration, while VAR uses thermal energy as the driving force for refrigeration.

10 Electrical Equipment/
Type of Refrigeration Vapour Compression Refrigeration Highly compressed fluids tend to get colder when allowed to expand If pressure high enough Compressed air hotter than source of cooling Expanded gas cooler than desired cold temperature Electrical Equipment/ Refrigeration & AC Compression refrigeration cycles take advantage of the fact that highly compressed fluids at a certain temperature tend to get colder when they are allowed to expand. If the pressure change is high enough, then the compressed gas will be hotter than our source of cooling (outside air, for instance) and the expanded gas will be cooler than our desired cold temperature. In this case, fluid is used to cool a low temperature environment and reject the heat to a high temperature environment.

11 Electrical Equipment/
Type of Refrigeration Vapour Compression Refrigeration Two advantages Lot of heat can be removed (lot of thermal energy to change liquid to vapour) Heat transfer rate remains high (temperature of working fluid much lower than what is being cooled) Electrical Equipment/ Refrigeration & AC Vapour compression refrigeration cycles have two advantages. First, a large amount of thermal energy is required to change a liquid to a vapor, and therefore a lot of heat can be removed from the air-conditioned space. Second, the isothermal nature of the vaporization allows extraction of heat without raising the temperature of the working fluid to the temperature of whatever is being cooled. This means that the heat transfer rate remains high, because the closer the working fluid temperature approaches that of the surroundings, the lower the rate of heat transfer.

12 Electrical Equipment/
Type of Refrigeration Vapour Compression Refrigeration Refrigeration cycle Condenser Evaporator High Pressure Side Low Pressure Side Compressor Expansion Device 1 2 3 4 Electrical Equipment/ Refrigeration & AC The refrigeration cycle is shown in the Figure and can be broken down into the following stages (note to the trainer: the next slides will explain what is happening between 1 to 4)

13 Electrical Equipment/
Type of Refrigeration Low pressure liquid refrigerant in evaporator absorbs heat and changes to a gas Vapour Compression Refrigeration Refrigeration cycle Condenser Evaporator High Pressure Side Low Pressure Side Compressor Expansion Device 1 2 3 4 Electrical Equipment/ Refrigeration & AC The refrigeration cycle is shown in the Figure and can be broken down into the following stages (note to the trainer: the numbers 1-4 are shown in the figure): 1 – 2. Low-pressure liquid refrigerant in the evaporator absorbs heat from its surroundings, usually air, water or some other process liquid. During this process it changes its state from a liquid to a gas, and at the evaporator exit is slightly superheated.

14 Electrical Equipment/
Type of Refrigeration The superheated vapour enters the compressor where its pressure is raised Vapour Compression Refrigeration Refrigeration cycle Condenser Evaporator High Pressure Side Low Pressure Side Compressor Expansion Device 1 2 3 4 Electrical Equipment/ Refrigeration & AC The refrigeration cycle is shown in the Figure and can be broken down into the following stages (note to the trainer: the numbers 1-4 are shown in the figure): 2 – 3. The superheated vapour enters the compressor where its pressure is raised. The temperature will also increase, because a proportion of the energy put into the compression process is transferred to the refrigerant.

15 Electrical Equipment/
Type of Refrigeration The high pressure superheated gas is cooled in several stages in the condenser Vapour Compression Refrigeration Refrigeration cycle Condenser Evaporator High Pressure Side Low Pressure Side Compressor Expansion Device 1 2 3 4 Electrical Equipment/ Refrigeration & AC The refrigeration cycle is shown in the Figure and can be broken down into the following stages (note to the trainer: the numbers 1-4 are shown in the figure): 3 – 4. The high pressure superheated gas passes from the compressor into the condenser. The initial part of the cooling process (3-3a) de-superheats the gas before it is then turned back into liquid (3a-3b). The cooling for this process is usually achieved by using air or water. A further reduction in temperature happens in the pipe work and liquid receiver (3b - 4), so that the refrigerant liquid is sub-cooled as it enters the expansion device

16 Electrical Equipment/
Type of Refrigeration Liquid passes through expansion device, which reduces its pressure and controls the flow into the evaporator Vapour Compression Refrigeration Refrigeration cycle Condenser Evaporator High Pressure Side Low Pressure Side Compressor Expansion Device 1 2 3 4 Electrical Equipment/ Refrigeration & AC The refrigeration cycle is shown in the Figure and can be broken down into the following stages (note to the trainer: the numbers 1-4 are shown in the figure): 1 – 2. Low-pressure liquid refrigerant in the evaporator absorbs heat from its surroundings, usually air, water or some other process liquid. During this process it changes its state from a liquid to a gas, and at the evaporator exit is slightly superheated. 2 – 3. The superheated vapour enters the compressor where its pressure is raised. The temperature will also increase, because a proportion of the energy put into the compression process is transferred to the refrigerant. 3 – 4. The high pressure superheated gas passes from the compressor into the condenser. The initial part of the cooling process (3-3a) de-superheats the gas before it is then turned back into liquid (3a-3b). The cooling for this process is usually achieved by using air or water. A further reduction in temperature happens in the pipe work and liquid receiver (3b - 4), so that the refrigerant liquid is sub-cooled as it enters the expansion device.CondenserEvaporatorHigh Pressure SideLow Pressure SideCompressorExpansion Device1234 4 - 1 The high-pressure sub-cooled liquid passes through the expansion device, which both reduces its pressure and controls the flow into the evaporator

17 Electrical Equipment/
Type of Refrigeration Vapour Compression Refrigeration Type of refrigerant Refrigerant determined by the required cooling temperature Chlorinated fluorocarbons (CFCs) or freons: R-11, R-12, R-21, R-22 and R-502 Electrical Equipment/ Refrigeration & AC A variety of refrigerants are used in vapor compression systems. The choice of fluid is determined largely by the cooling temperature required. Commonly used refrigerants are in the family of chlorinated fluorocarbons, CFCs, also known as freons: R-11, R-12, R-21, R-22 and R-502.

18 Electrical Equipment/
Type of Refrigeration Vapour Compression Refrigeration Choice of compressor, design of condenser, evaporator determined by Refrigerant Required cooling Load Ease of maintenance Physical space requirements Availability of utilities (water, power) Electrical Equipment/ Refrigeration & AC The choice of refrigerant and the required cooling temperature and load determine the choice of compressor, as well as the design of the condenser, evaporator, and other auxiliaries. Additional factors such as ease of maintenance, physical space requirements and availability of utilities for auxiliaries (water, power, etc.) also influence component selection.

19 Electrical Equipment/
Type of Refrigeration Vapour Absorption Refrigeration Condenser Generator Evaporator Absorber Cold Side Hot Side Electrical Equipment/ Refrigeration & AC The vapour absorption refrigeration system consists of: Evaporator Absorber High pressure generator Condenser The next slides discuss each of these in more detail.

20 Electrical Equipment/
Type of Refrigeration Vapour Absorption Refrigeration Evaporator Electrical Equipment/ Refrigeration & AC Evaporator The refrigerant (water) evaporates at around 4oC under a high vacuum condition of 754 mm Hg in the evaporator. Chilled water goes through heat exchanger tubes in the evaporator and transfers heat to the evaporated refrigerant. The evaporated refrigerant (vapor) turns into liquid again, while the latent heat from this vaporization process cools the chilled water (in the diagram from 12 oC to 7 oC). The chilled water is then used for cooling purposes.

21 Electrical Equipment/
Type of Refrigeration Vapour Absorption Refrigeration Absorber Electrical Equipment/ Refrigeration & AC Absorber In order to keep evaporating, the refrigerant vapor must be discharged from the evaporator and refrigerant (water) must be supplied. The refrigerant vapor is absorbed into lithium bromide solution, which is convenient to absorb the refrigerant vapor in the absorber. The heat generated in the absorption process is continuously removed from the system by cooling water. The absorption also maintains the vacuum inside the evaporator. © UNEP 2006

22 Electrical Equipment/
Type of Refrigeration Vapour Absorption Refrigeration High pressure generator Electrical Equipment/ Refrigeration & AC High Pressure Generator As lithium bromide solution is diluted, the ability to absorb the refrigerant vapor reduces. In order to keep the absorption process going, the diluted lithium bromide solution must be concentrated again. An absorption chiller is provided with a solution concentrating system, called a generator. Heating media such as steam, hot water, gas or oil perform the function of concentrating solutions.The concentrated solution is returned to the absorber to absorb refrigerant vapor again.

23 Electrical Equipment/
Type of Refrigeration Vapour Absorption Refrigeration Condenser Electrical Equipment/ Refrigeration & AC Condenser To complete the refrigeration cycle, and thereby ensuring the refrigeration takes place continuously, the following two functions are required To concentrate and liquefy the evaporated refrigerant vapor, which is generated in the high-pressure generator. To supply the condensed water to the evaporator as refrigerant (water) For these two functions a condenser is installed.

24 Electrical Equipment/
Type of Refrigeration Evaporative Cooling Air in contact with water to cool it close to ‘wet bulb temperature’ Advantage: efficient cooling at low cost Disadvantage: air is rich in moisture Electrical Equipment/ Refrigeration & AC Cold Air Hot Air Sprinkling Water There are occasions where air conditioning, which stipulates control of humidity up to 50 % for human comfort or for process, can be replaced by a much cheaper and less energy intensive evaporative cooling. Evaporative cooling is an extremely efficient means of cooling at very low cost. The concept is very simple and is the same as that used in a cooling tower. Air is brought in close contact with water to cool it to a temperature close to the wet bulb temperature. The cool air can be used for comfort or process cooling. The disadvantage is that the air is rich in moisture. The possibility of evaporative cooling is especially attractive for comfort cooling in dry regions. This principle is practiced in textile industries for certain processes. (Adapted from Munters, 2001)

25 Electrical Equipment/
Introduction Type of refrigeration Assessment of refrigeration and AC Energy efficiency opportunities Electrical Equipment/ Refrigeration & AC This section include performance evaluation of refrigeration plant and examples for the assessment of refrigeration plant.

26 Electrical Equipment/
Assessment of Refrigeration and AC Assessment of Refrigeration Cooling effect: Tons of Refrigeration TR is assessed as: 1 TR = 3024 kCal/hr heat rejected Electrical Equipment/ Refrigeration & AC The cooling effect produced is quantified as to ns of refrigeration, or shortly TR. 1 TR of refrigeration = 3024 kCal/hr heat rejected. The refrigeration TR is assessed as TR = Q xCp x (Ti – To) / 3024, where Q is mass flow rate of coolant; Cp is coolant specific heat in; Ti is inlet, temperature of coolant to evaporator; and To is outlet temperature of coolant from evaporator. The above TR is also called as chiller tonnage. TR = Q xCp x (Ti – To) / 3024 Q = mass flow rate of coolant in kg/hr Cp = is coolant specific heat in kCal /kg deg C Ti = inlet, temperature of coolant to evaporator (chiller) in 0C To = outlet temperature of coolant from evaporator (chiller) in 0C

27 Electrical Equipment/
Assessment of Refrigeration and AC Assessment of Refrigeration Electrical Equipment/ Refrigeration & AC The specific power consumption kW/TR is a useful indicator of the performance of a refrigeration system. By measuring the refrigeration duty performed in TR and the kW inputs, kW/TR is used as an energy performance indicator. In a centralized chilled water system, apart from the compressor unit, power is also consumed by the chilled water (secondary) coolant pump, the condenser water pump (for heat rejection to cooling tower) and the fan in the cooling tower. Effectively, the specific power consumption for a certain TR output is the sum of: Compressor kW/TR Chilled water pump kW/TR Condenser water pump kW/TR Cooling tower fan kW/TR © UNEP 2006

28 Electrical Equipment/
Assessment of Refrigeration and AC Assessment of Refrigeration Coefficient of Performance (COPCarnot) Standard measure of refrigeration efficiency Depends on evaporator temperature Te and condensing temperature Tc: COP in industry calculated for type of compressor: Electrical Equipment/ Refrigeration & AC COPCarnot = Te / (Tc - Te) The theoretical Coefficient of Performance (Carnot), (COPCarnot, a standard measure of refrigeration efficiency of an ideal refrigeration system) depends on two key system temperatures: evaporator temperature Te and condenser temperature Tc. COP is given as: COPCarnot = Te / (Tc - Te) (Click once) But COPCarnot is only a ratio of temperatures, and does not take into account the type of compressor. Hence the COP normally used in industry is calculated using the equation on the slide

29 Assessment of Refrigeration and AC
Electrical Equipment/ Refrigeration & AC COPCarnot = Te / (Tc - Te) This expression also indicates that higher COPCarnot is achieved with higher evaporator temperatures and lower condenser temperatures. COP increases with rising evaporator temperature (Te) COP increases with decreasing condensing temperature (Tc)

30 Electrical Equipment/
Assessment of Refrigeration and AC Assessment of Air Conditioning Measure Airflow Q (m3/s) at Fan Coil Units (FCU) or Air Handling Units (AHU): anemometer Air density  (kg/m3) Dry bulb and wet bulb temperature: psychrometer Enthalpy (kCal/kg) of inlet air (hin) and outlet air (Hout): psychrometric charts Calculate TR Electrical Equipment/ Refrigeration & AC In case of air conditioning units, the airflow at the fan coil units or the air handling units can be measured with an anemometer. Dry bulb and wet bulb temperatures are measured at the inlet and outlet of AHU or the FCU. The refrigeration load in TR is assessed as: TR = Q x  x (hin - hout) / Where Q is the air flow;  is density of air; h in is enthalpy of inlet air; and h out is enthalpy of outlet air. Use of psychometric charts can help to calculate hin and hout from dry bulb and wet bulb temperature values which are measured during trials by a whirling psychrometer. Power measurements at compressor, pumps, AHU fans, cooling tower fans can be taken with a portable load analyzer. The specific power consumption can then be calculated.

31 Electrical Equipment/
Assessment of Refrigeration and AC Assessment of Air Conditioning Indicative TR load profile Small office cabins : 0.1 TR/m2 Medium size office (10 – 30 people occupancy) with central A/C: 0.06 TR/m2 Large multistoried office complexes with central A/C: 0.04 TR/m2 Electrical Equipment/ Refrigeration & AC An indicative TR load profile for air conditioning is presented as follows: Small office cabins = 0.1 TR/m2 Medium size office i.e., = 0.06 TR/m2 10 – 30 people occupancy with central A/C Large multistoried office = 0.04 TR/m2 complexes with central A/C

32 Electrical Equipment/
Assessment of Refrigeration and AC Considerations for Assessment Accuracy of measurements Inlet/outlet temp of chilled and condenser water Flow of chilled and condenser water Integrated Part Load Value (IPLV) kW/TR for 100% load but most equipment operate between 50-75% of full load IPLV calculates kW/TR with partial loads Four points in cycle: 100%, 75%, 50%, 25% Electrical Equipment/ Refrigeration & AC Accuracy of flow and temperature measurements In a field performance assessment, accurate instruments are required to measure the Inlet and outlet temperatures of chilled water and condenser water, preferably with a count of at least 0.1 oC. Flow measurements of chilled water can be made with an ultrasonic flow meter directly or can be determined based on pump duty parameters. Condenser water flow can also be measured with a non-contact flow meter directly or determined by using pump duty parameters. Integrated Part Load Value (IPLV) Although the kW/ TR can serve as an initial reference, it should not be taken as an absolute since this value is based on a 100% equipment capacity level. But most equipment operate between 50% and 75% of their capacity. To overcome this, an average kW/TR with partial loads has to be determined, which is called the Integrated Part Load Value (IPLV). The IPLV is the most appropriate reference, although not considered the best, because it only captures four points within the operational cycle: 100%, 75%, 50% and 25%. Furthermore, it assigns the same weight to each value, and most equipment operate between 50% and 75% of their capacity.

33 Electrical Equipment/
Introduction Type of refrigeration Assessment of refrigeration and AC Energy efficiency opportunities Electrical Equipment/ Refrigeration & AC Energy efficiency opportunities.

34 Electrical Equipment/
Energy Efficiency Opportunities Optimize process heat exchange Maintain heat exchanger surfaces Multi-staging systems Matching capacity to system load Capacity control of compressors Multi-level refrigeration for plant needs Chilled water storage System design features Electrical Equipment/ Refrigeration & AC We will go through the following eight areas for energy efficiency improvements.

35 Electrical Equipment/
Energy Efficiency Opportunities 1. Optimize Process Heat Exchange High compressor safety margins: energy loss Proper sizing heat transfer areas of heat exchangers and evaporators Heat transfer coefficient on refrigerant side: 1400 – 2800 Watt/m2K Heat transfer area refrigerant side: >0.5 m2/TR Optimum driving force (difference Te and Tc): 1oC raise in Te = 3% power savings Electrical Equipment/ Refrigeration & AC There is a tendency to apply high safety margins to operations, which influence the compressor suction pressure / evaporator set point. For instance, a process-cooling requirement of 15 oC would need chilled water at a lower temperature, but the range can vary from 6 oC to about 10 oC. At chilled water of 10 oC, the refrigerant side temperature has to be lower (about –5oC to +5oC). The refrigerant temperature determines the corresponding suction pressure of the refrigerant, which in turn determines the inlet duty conditions for the refrigerant compressor. Minimizing energy consumption can be achieved in the following ways: Proper sizing of heat transfer areas of process heat exchangers and evaporators the heat transfer coefficient on the refrigerant side can range from 1400 – 2800 watts /m2K. The refrigerant side heat transfer areas are of the order of 0.5 m2/TR and above in evaporators 2. Optimizing the driving force, i.e. the difference between evaporator temp Te and condensing temp Tc. A 1oC raise in evaporator temperature can save almost 3 % of the power consumed. The next slide shows the effect of Te and Tc on the cooling effect TR and the power consumption

36 Energy Efficiency Opportunities
1. Optimize Process Heat Exchange Evaporator Temperature (0C) Refrigeration Capacity*(tons) Specific Power Consumption (kW/TR) Increase kW/TR (%) 5.0 67.58 0.81 - 0.0 56.07 0.94 16.0 -5.0 45.98 1.08 33.0 -10.0 37.20 1.25 54.0 -20.0 23.12 1.67 106.0 Electrical Equipment/ Refrigeration & AC This table shows the effect of evaporation temperature on the compressor power consumption. At a constant condenser temperature Tc of 40oC, lower evaporator temperatures reduce the refrigeration capacity TR and increase the power consumption The second table shows the effect of condensing temperature on the compressor power consumption. At a constant evaporator temperature Te of 10oC, increasing the condensing temperature leads to a reduction in refrigeration capacity and an increase in power consumption. The conclusion is therefore that you try to keep the difference between Te and Tc at an optimum level to ensure the best TR at the lowest power consumption. Condenser temperature 40◦C (National Productivity Council) Condensing Temperature (0C) Refrigeration Capacity (tons) Specific Power Consumption (kW /TR) Increase kW/TR (%) 26.7 31.5 1.17 - 35.0 21.4 1.27 8.5 40.0 20.0 1.41 20.5 *Reciprocating compressor using R-22 refrigerant. Evaporator temperature.-10◦ C

37 Electrical Equipment/
Energy Efficiency Opportunities 1. Optimize Process Heat Exchange 3. Selection of condensers Options: Air cooled condensers Air-cooled with water spray condensers Shell & tube condensers with water-cooling Water-cooled shell & tube condenser Lower discharge pressure Higher TR Lower power consumption Electrical Equipment/ Refrigeration & AC 3. Selection of condensers The choice of condensers in practice is between air-cooled, air-cooled with water spray, and shell and tube condensers with water-cooling. Larger shell and tube heat exchangers (0.65 m2/TR and above) that are used as condensers and that are equipped with good cooling tower operations allow operation at low discharge pressure values and improve the TR capacity of the refrigeration plant and thus reduce the power consumption. For example (optional) If the refrigerant R22 is used in a water-cooled shell and tube condenser then the discharge pressure is 15 kg/cm2. If the same refrigerant is used in an air-cooled condenser then the discharge pressure is 20 kg/cm2. This shows how much additional compression duty is required, which results in almost 30 % additional energy consumption by the plant.

38 Electrical Equipment/
Energy Efficiency Opportunities 2. Maintain Heat Exchanger Surfaces Poor maintenance = increased power consumption Maintain condensers and evaporators Separation of lubricating oil and refrigerant Timely defrosting of coils Increased velocity of secondary coolant Maintain cooling towers 0.55◦C reduction in returning water from cooling tower = 3.0 % reduced power Electrical Equipment/ Refrigeration & AC Once compressors have been purchased, effective maintenance is the key to optimizing power consumption. Poor maintenance forces a compressor to work harder, which results in increased power consumption A maintenance checklist for the condenser and evaporator Ensuring proper separation of the lubricating oil and the refrigerant Timely defrosting of coils Increasing the velocity of the secondary coolant (air, water, etc.). Equally important is proper selection, sizing, and maintenance of cooling towers. A reduction of 0.55oC in temperature of the water returning from the cooling tower reduces compressor power consumption by 3%.

39 Refrigeration Capacity* (TR) Specific Power Consumption (kW/TR)
Energy Efficiency Opportunities 2. Maintain Heat Exchanger Surfaces Effect of poor maintenance on compressor power consumption Electrical Equipment/ Refrigeration & AC Condition Te (0C) Tc (0C) Refrigeration Capacity* (TR) Specific Power Consumption (kW/TR) Increase kW/TR (%) Normal 7.2 40.5 17.0 0.69 - Dirty condenser 46.1 15.6 0.84 20.4 Dirty evaporator 1.7 13.8 0.82 18.3 Dirty condenser and evaporator 12.7 0.96 38.7 This table shows the effect of poor maintenance of compressor power consumption. For example, a dirty condenser and evaporator can increase the power consumption per ton of refrigeration (TR) by 38%! (National Productivity Council)

40 Electrical Equipment/
Energy Efficiency Opportunities 3. Multi-Staging Systems Suited for Low temp applications with high compression Wide temperature range Two types for all compressor types Compound Cascade Electrical Equipment/ Refrigeration & AC Efficient compressor operation requires that the compression ratio be kept low, to reduce discharge pressure and temperature. For low temperature applications involving high compression ratios, and for wide temperature range requirements, it is preferable (due to equipment design limitations) and often economical to employ multi-stage reciprocating machines or centrifugal / screw compressors. There are two types of multi-staging systems, which are applicable to all types of compressors: compound and cascade.

41 Electrical Equipment/
Energy Efficiency Opportunities 3. Multi-Stage Systems a. Compound Two low compression ratios = 1 high First stage compressor meets cooling load Second stage compressor meets load evaporator and flash gas Single refrigerant b. Cascade Preferred for -46 oC to -101oC Two systems with different refrigerants Electrical Equipment/ Refrigeration & AC Efficient compressor operation requires that the compression ratio be kept low, to reduce discharge pressure and temperature. For low temperature applications involving high compression ratios, and for wide temperature range requirements, it is preferable (due to equipment design limitations) and often economical to employ multi-stage reciprocating machines or centrifugal / screw compressors. There are two types of multi-staging systems, which are applicable to all types of compressors: compound and cascade. Compound a combination of two compressors with low compression ratios can provide a high compression ratio A single refrigerant is used in the system, and the two compressors share the compression task equally. a first-stage compressor that sized to meet the cooling load, feeds into the suction of a second-stage compressor after inter-cooling of the gas. A part of the high-pressure liquid from the condenser is flashed and used for liquid sub-cooling. The second compressor, therefore, has to meet the load of the evaporator and the flash gas. Cascade For temperatures in the range of –46oC to –101oC, cascaded systems are preferable. In this system, two separate systems using different refrigerants are connected so that one rejects heat to the other. The main advantage of this system is that a low temperature refrigerant, which has a high suction temperature and low specific volume, can be selected for the low-stage to meet very low temperature requirements.

42 Electrical Equipment/
Energy Efficiency Opportunities 4. Matching Capacity to Load System Most applications have varying loads Consequence of part-load operation COP increases but lower efficiency Match refrigeration capacity to load requires knowledge of Compressor performance Variations in ambient conditions Cooling load Electrical Equipment/ Refrigeration & AC Consideration of part-load operation is important, because most refrigeration applications have varying loads. The load may vary due to variations in temperature and process cooling needs. During part-load operation, the evaporator temperature rises and the condenser temperature falls, effectively increasing the COP. But at the same time, deviation from the design operation point and the fact that mechanical losses form a greater proportion of the total power negate the effect of improved COP, resulting in lower part-load efficiency. Matching refrigeration capacity to the load is a difficult exercise, requiring knowledge of compressor performance, and variations in ambient conditions, and detailed knowledge of the cooling load.

43 Electrical Equipment/
Energy Efficiency Opportunities 5. Capacity Control of Compressors Cylinder unloading, vanes, valves Reciprocating compressors: step-by-step through cylinder unloading: Centrifugal compressors: continuous modulation through vane control Screw compressors: sliding valves Speed control Reciprocating compressors: ensure lubrication system is not affected Centrifugal compressors: >50% of capacity Electrical Equipment/ Refrigeration & AC The capacity of compressors is controlled in a number of ways. We will discuss four of these Capacity control through cylinder unloading, vanes and valves Capacity control of reciprocating compressors through cylinder unloading results in incremental (step-by-step) modulation. In contrast, continuous modulation occurs in centrifugal compressors through vane control and in screw compressors through sliding valves. Capacity regulation through speed control is the most efficient option. Reciprocating compressors: it should be ensured that the lubrication system is not affected. Centrifugal compressors: restrict speed control to about 50 % of the capacity to prevent surging. Below 50%, vane control or hot gas bypass can be used for capacity modulation.

44 Electrical Equipment/
Energy Efficiency Opportunities 5. Capacity Control of Compressors Temperature monitoring Reciprocating compressors: return water (if varying loads), water leaving chiller (constant loads) Centrifugal compressors: outgoing water temperature Screw compressors: outgoing water temperature Part load applications: screw compressors more efficient Electrical Equipment/ Refrigeration & AC Temperature control requires careful system design. Reciprocating compressors: for widely varying loads control the compressor by monitoring the return water (or other secondary coolant) temperature. If load fluctuations are not high: the temperature of the water leaving the chiller should be monitored. The outgoing water temperature should be monitored for centrifugal and screw chillers. Capacity regulation through speed control is the most efficient option. The efficiency of screw compressors operating at part load is generally higher than either centrifugal compressors or reciprocating compressors, which may make them attractive in situations where part-load operation is common.

45 Electrical Equipment/
Energy Efficiency Opportunities 6. Multi-Level Refrigeration Bank of compressors at central plant Monitor cooling and chiller load: 1 chiller full load more efficient than 2 chillers at part-load Distribution system: individual chillers feed all branch lines; Isolation valves; Valves to isolate sections Load individual compressors to full capacity before operating second compressor Provide smaller capacity chiller to meet peak demands Electrical Equipment/ Refrigeration & AC Managing part-load at bank of compressors at central plant Many industries use a bank of compressors at a central location to meet the load. Usually the chillers feed into a common header from which branch lines are taken to different locations in the plant. In such situations, operation at part-load requires extreme care. For efficient operation, the cooling load, and the load on each chiller must be monitored closely. It is more efficient to operate a single chiller at full load than to operate two chillers at part-load. The distribution system should be designed such that individual chillers can feed all branch lines. Isolation valves must be provided to ensure that chilled water (or other coolant) does not flow through chillers not in operation. Valves should also be provided on branch lines to isolate sections where cooling is not required. This reduces pressure drops in the system and reduces power consumption in the pumping system. Individual compressors should be loaded to their full capacity before operating the second compressor. In some cases it is economical to provide a separate smaller capacity chiller, which can be operated on an on-off control to meet peak demands, with larger chillers meeting the base load.

46 Electrical Equipment/
Energy Efficiency Opportunities 6. Multi-Level Refrigeration Packaged units (instead of central plant) Diverse applications with wide temp range and long distance Benefits: economical, flexible and reliable Disadvantage: central plants use less power Flow control Reduced flow Operation at normal flow with shut-off periods Electrical Equipment/ Refrigeration & AC Packaged units Packaged units can be used For diverse applications requiring a wide range of temperatures depending on the distance at which cooling loads need to be met. Packaged units at load centers reduce distribution losses in the system. Advantages: Economical, flexibility and reliability. Despite the advantages of packaged units, central plants generally have lower power consumption since at reduced loads power consumption can reduce significantly due to the large condenser and evaporator surfaces. Flow control Flow control is also commonly used to meet varying demands. Reduced flow. In such cases the savings in pumping at reduced flow should be weighed against the reduced heat transfer in coils due to reduced velocity. In some cases, operation at normal flow rates, with subsequent longer periods of no-load (or shut-off) operation of the compressor, may result in larger savings.

47 Electrical Equipment/
Energy Efficiency Opportunities 7. Chilled Water Storage Chilled water storage facility with insulation Suited only if temp variations are acceptable Economical because Chillers operate during low peak demand hours: reduced peak demand charges Chillers operate at nighttime: reduced tariffs and improved COP Electrical Equipment/ Refrigeration & AC Depending on the nature of the load, it is economical to provide a chilled water storage facility with very good cold insulation. Also, the storage facility can be fully filled to meet the process requirements so that chillers need not be operated continuously. This system is usually economical if small variations in temperature are acceptable. This system has the added advantage of allowing the chillers to be operated at periods of low electricity demand to reduce peak demand charges. Low tariffs offered by some electric utilities for operation at nighttime can also be taken advantage of by using a storage facility. An added benefit is that lower ambient temperature at night lowers condenser temperature and thereby increases the COP. If temperature variations cannot be tolerated, it may not be economical to provide a storage facility since the secondary coolant would have to be stored at a temperature much lower than required to provide for heat gain. The additional cost of cooling to a lower temperature may offset the benefits. The solutions are case specific. For example, in some cases it may be possible to employ large heat exchangers, at a lower cost burden than low temperature chiller operation, to take advantage of the storage facility even when temperature variations are not acceptable. Ice bank systems, which store ice rather than water, are often economical.

48 Electrical Equipment/
Energy Efficiency Opportunities 8. System Design Features FRP impellers, film fills, PVC drift eliminators Softened water for condensers Economic insulation thickness Roof coatings and false ceilings Energy efficient heat recovery devices Variable air volume systems Sun film application for heat reflection Optimizing lighting loads Electrical Equipment/ Refrigeration & AC In overall plant design, adoption of good practices improves the energy efficiency significantly. Some areas for consideration are: Design of cooling towers with FRP impellers and film fills, PVC drift eliminators, etc. Use of softened water for condensers in place of raw water. Use of economic insulation thickness on cold lines, heat exchangers, considering cost of heat gains and adopting practices like infrared thermography for monitoring - applicable especially in large chemical / fertilizer / process industry. Adoption of roof coatings / cooling systems, false ceilings / as applicable, to minimize refrigeration load. Adoption of energy efficient heat recovery devices like air to air heat exchangers to pre-cool the fresh air by indirect heat exchange; control of relative humidity through indirect heat exchange rather than use of duct heaters after chilling. Adopting of variable air volume systems Adopting of sun film application for heat reflection Optimizing lighting loads in the air conditioned areas Optimizing number of air changes in the air conditioned areas are few other examples.

49 Electrical Equipment/
Refrigerant: HFC’s HFC refers to the chemical composition of the refrigerant. HydroFluoroCarbon indicates that the refrigerant is comprised of Hydrogen, Fluorine, and Carbon. A blend that contains different HFCs is considered an HFC refrigerant. Electrical Equipment/ Refrigeration & AC In overall plant design, adoption of good practices improves the energy efficiency significantly. Some areas for consideration are: Design of cooling towers with FRP impellers and film fills, PVC drift eliminators, etc. Use of softened water for condensers in place of raw water. Use of economic insulation thickness on cold lines, heat exchangers, considering cost of heat gains and adopting practices like infrared thermography for monitoring - applicable especially in large chemical / fertilizer / process industry. Adoption of roof coatings / cooling systems, false ceilings / as applicable, to minimize refrigeration load. Adoption of energy efficient heat recovery devices like air to air heat exchangers to pre-cool the fresh air by indirect heat exchange; control of relative humidity through indirect heat exchange rather than use of duct heaters after chilling. Adopting of variable air volume systems Adopting of sun film application for heat reflection Optimizing lighting loads in the air conditioned areas Optimizing number of air changes in the air conditioned areas are few other examples.

50 Electrical Equipment/
Refrigerant : HCFC’s HCFC refers to the chemical composition of the refrigerant. HydroChloroFluoroCarbon indicates that the refrigerant is comprised of Hydrogen, Chlorine, Fluorine, and Carbon. A blend that contains both an HCFC and HFC is considered an HCFC refrigerant. Electrical Equipment/ Refrigeration & AC In overall plant design, adoption of good practices improves the energy efficiency significantly. Some areas for consideration are: Design of cooling towers with FRP impellers and film fills, PVC drift eliminators, etc. Use of softened water for condensers in place of raw water. Use of economic insulation thickness on cold lines, heat exchangers, considering cost of heat gains and adopting practices like infrared thermography for monitoring - applicable especially in large chemical / fertilizer / process industry. Adoption of roof coatings / cooling systems, false ceilings / as applicable, to minimize refrigeration load. Adoption of energy efficient heat recovery devices like air to air heat exchangers to pre-cool the fresh air by indirect heat exchange; control of relative humidity through indirect heat exchange rather than use of duct heaters after chilling. Adopting of variable air volume systems Adopting of sun film application for heat reflection Optimizing lighting loads in the air conditioned areas Optimizing number of air changes in the air conditioned areas are few other examples.

51 Electrical Equipment/
Refrigerant: CFC’s CFC refers to the chemical composition of the refrigerant. ChloroFluoroCarbon indicates that the refrigerant is comprised of Chlorine, Fluorine, and Carbon. A blend that contains a CFC and any other product is still considered a CFC refrigerant. Electrical Equipment/ Refrigeration & AC In overall plant design, adoption of good practices improves the energy efficiency significantly. Some areas for consideration are: Design of cooling towers with FRP impellers and film fills, PVC drift eliminators, etc. Use of softened water for condensers in place of raw water. Use of economic insulation thickness on cold lines, heat exchangers, considering cost of heat gains and adopting practices like infrared thermography for monitoring - applicable especially in large chemical / fertilizer / process industry. Adoption of roof coatings / cooling systems, false ceilings / as applicable, to minimize refrigeration load. Adoption of energy efficient heat recovery devices like air to air heat exchangers to pre-cool the fresh air by indirect heat exchange; control of relative humidity through indirect heat exchange rather than use of duct heaters after chilling. Adopting of variable air volume systems Adopting of sun film application for heat reflection Optimizing lighting loads in the air conditioned areas Optimizing number of air changes in the air conditioned areas are few other examples.

52 Electrical Equipment/
Refrigerant: Selection Criteria Selection of refrigerant for a particular application is based on the following requirements: Thermodynamic and thermo-physical properties: suction pressure, discharge pressure, pressure ratio, latent heat of vaporization, Isentropic index of compression, Liquid specific heat, Vapor specific heat, Thermal conductivity, Viscosity Environmental and safety properties, and ODP, GWP, TEWI, Toxicity, Flammability, Chemical stability, Compatibility, Miscibility with L-Oil, Dielectric strength, Ease of Leak detection 3. Economics Cheap and Easily available Electrical Equipment/ Refrigeration & AC In overall plant design, adoption of good practices improves the energy efficiency significantly. Some areas for consideration are: Design of cooling towers with FRP impellers and film fills, PVC drift eliminators, etc. Use of softened water for condensers in place of raw water. Use of economic insulation thickness on cold lines, heat exchangers, considering cost of heat gains and adopting practices like infrared thermography for monitoring - applicable especially in large chemical / fertilizer / process industry. Adoption of roof coatings / cooling systems, false ceilings / as applicable, to minimize refrigeration load. Adoption of energy efficient heat recovery devices like air to air heat exchangers to pre-cool the fresh air by indirect heat exchange; control of relative humidity through indirect heat exchange rather than use of duct heaters after chilling. Adopting of variable air volume systems Adopting of sun film application for heat reflection Optimizing lighting loads in the air conditioned areas Optimizing number of air changes in the air conditioned areas are few other examples.

53 Refrigeration & Air Conditioning Systems
THANK YOU FOR YOUR ATTENTION Electrical Equipment/ Refrigeration & AC Thank you for your attention!