Presentation is loading. Please wait.

Presentation is loading. Please wait.

Metering In Today’s World

Similar presentations


Presentation on theme: "Metering In Today’s World"— Presentation transcript:

1 Metering In Today’s World
KEEP IT SIMPLE By Larry Chapman

2

3

4 Blondel’s Theorem Blondel’s Theorem—In a system of N conductors, N-l meter elements, properly connected, will measure the power or energy taken. The connection must be such that all voltage coils have a common tie to the conductor in which there is no current coil.

5 Blondel is right, Everybody Else is WRONG!
When metering applications agree with this simple guideline there will never be an error or compromise in metering accuracy and we would be living with 6 meter form numbers and 6 basic wiring schemes. Metering, in general would be understandable, straight forward and easily mastered. We can thank our lucky stars for the nature of engineers in general, because without them trying to prove ways to get the job done without following Blondel’s plan this course would be very short. So, lets get down to learning how to play the hand we have been dealt.

6 Definitions of Abbreviations Common to Metering
Kh: Watthour constant of the meter. Equal to watts per single disc revolution. Solid state meters will have an indicator of some fashion for this value. Rr: Register Ratio, normally indicated on the face plate or stamped in the body of the register. Rs: Ratio of the first driven gear on the register to the meter disc shaft. Not indicated on the meter in any way. Value must be determined. CTr: Current transformer ratio. Never accept nameplate information. ALWAYS verify. Always depicted as some value to 5 for the maximum secondary current. VTr.Voltage, or Potential transformer ratio. Never accept nameplate information. ALWAYS verify. Usually depicted as some value to 120 for the maximum secondary voltage. TF: Transformer Factor. (CTr/Turns)XVTr=TF. Turns equals the number of times the primary current is presented to the current transformer. NEVER assume this value to be the billing multiplier! PKh: Watts per single disc revolution with the transformer factor applied to the meter Kh. Kr: Register constant, better known as the billing multiplier. ALWAYS run the billing multiplier formula to verify this value.

7 Common Metering Formulas
R.G.: Register Gear Ratio. Derived by / Kh = R.G. IE: / 7.2 = /9 Rr: Register Ratio. Derived by R.G. / Rs = Rr IE: /9 / 100 = 13 8/9 TF: Transformer Factor. (CTr / Turns) X Vtr =TF Consider a service with a single 400/5 current transformer and two primary turns at the CT and a 480/120 VT. IE: (80 / 2)X4 = 160 PKh: Primary Kh. Meter Kh X TF. A value utilized to calculate load or register ratios to compensate for the transformer factor. IE: (0.6 X 160) = 96

8 The Two Most Important Formulas Ever
Kr: Billing Multiplier (Rr X Rs X TF X Kh) / 10000 This is absolutely the most important formula you will ever learn for dealing with electromechanical meters! When solid state meters become involved the recommended procedure is to apply the transformer factor as the billing multiplier and program the meter with a Kh equal to that indicated on the nameplate. NEVER use primary rated register programming, it only sets you up for disaster. KW: Determined by a timed disc revolution at the meter. (3.6 X Kh. X TF) / Time in Seconds for 1 Disc Rev.= KW IE: 3.6 X .3 X 160) / 28 Seconds = KW NOTE *** 3.6 = the number of seconds in one hour / 1000

9 Other Formulas of Interest
VA: Volt-Amperes. Volt X Amps = VA IE: 120 X 10 = 1200 VA Watts: Volts X Amps X Cosine of the Phase Angle = Watts IE: 120 X 10 X Cos 30 = 1039 Watts Since our product is sold in units of 1000 and billed to our customers as Kilowatts or, in some instances, Kilovolt Amperes we simply convert VA and Watts as follows. KVA: VA / IE: / 1000 = 1.2 KVA KW: Watts / IE: 1039 / 1000 = KW KW must be viewed as demand and not confused with KWH. KWH is simply the sum of the KW consumed over the period of 1 hour. This is the value displayed on the meter register. The demand is determined in intervals of time and calculated to indicate what that consumption would be if the load remained constant for a full 60 minutes.

10 Other Formulas (Cont’d)
As meter people we are not at all interested in having to deal with gathering the information required to prove the accuracy of the metering package from any place other than the meter socket. For that reason, the rest of these formulas are based on that assumption. There are as many formulas to calculate these values as there are engineers to dream them up, and you may be more accustomed to using others to get the same answers. Calculating KVA Single Phase 2-Wire Circuit: (Line to Line Volts X Total Amps X TF) / 1000 = KVA IE: (120 X 5 X 160) / 1000 = 96 KVA Single Phase 3-Wire Circuit: (Line to Line Volts X Total Amps X TF) /2000 = KVA IE: (240 X 10 X 160) / 2000 = 192

11 Other Formulas (Cont’d)
Polyphase Circuit: (Average Line to Line Volts X Total Amps X TF) / = KVA IE: (208 X 15 X 160) / = **** NOTE **** is derived from the Square Root of 3 X 1000 In the event readings are taken at a 3-Phase, 3-Wire socket and the current for the 3rd phase is not available, simply add a value equal to the average of the other two to the total current. If a form 5S or 45S meter is being used with a 3-Phase, 4-Wire Delta circuit with two current transformers, enter the reading of the single phase current transformer twice to the formula to compensate for the double primary adjustment in the transformer factor.

12 Other Formulas (Cont’d)
Polyphase 3-Phase, 4-Wire WYE Circuit with 5S or 45S Meter Scheme: ((Average Line to Line Volts X Total Amps X TF) / )*Cos30 = KVA IE: ((208 X 17.3 X 160) / )*.866 = **** NOTE **** is derived from the 3 X 1000 In this instance the center phase current is presented to the CT on the left meter element backwards and again to the CT on the right meter element backwards. The Cos30 value of .866 compensates the formula to allow for this discrepancy. Next we look to calculating power factor using two electromechanical meters to collect KWH and KVARH information, or reactive load, information. There are two accepted methods of determining KVAR.

13 KVAR, KQ, KVA, Who Cares? The formula for using meter revolutions disc is the same for KW, KVAR, and KQ meters. (3.6 X Kh. X TF) / Time = KW, KVAR, or KQ IE: (3.6 X 1.8 X 160)/ = 100 KW. If the Watt and Var meters are running the same speed KVA is derived from the formula: KVA = (KW₂ + KVAR₂ ) IE: (100₂ + 100₂) = KVA Power Factor = (KW / KVA) IE: (100 / ) = or 70.21% As long as the two meters involved are simply a KW meter and a KVAR meter the above holds true and all is well. Once we take on the “KQ” meter everything changes.

14 The “Q” Meter With a “Q” Meter in the equation we first have to determine the value of KVAR using: (3.6 X Kh. X TF) / Time = KW, KVAR, or KQ IE: (3.6 X 1.8 X 160)/ = 100 KW. If the Watt and Q meters are running the same speed KVAR is derived from the formula: KVAR = ((2 X KQ)-KW) / or the 3 IE: ((2 X 100)-100) / = KVAR KVA = (KW₂ + KVAR₂ ) IE: (100₂ ₂) = KVA Power Factor = (KW / KVA) IE: (100 / ) = .866 or 86.60% If your customer is trying to correct his power factor though addition of capacitance it is clear that using the wrong formula for your calculations would certainly create confusion.

15 Metering Formula’s Simplified
Transformer Factor: (CTr X VTr) / Turns Primary at CT = TF IE: (40 X 2.5) / 1 = 100 Multiplier: (Rr X Rs X Kh X TF) / 10,000 = Kr or Billing Multiplier IE: ( X 50 X1.8 X 100) / 10,000 = 100 Primary Kh: TF X Kh = Primary Kh IE: 100 X 1.8 = 180 KW by Timed Disc 3.6 X Kh X TF Time, 1-Rev in Seconds Meter Socket KVA Formula’s 1-Phase 2-Wire Svc: (Amps X Volts X TF) / 1000 = KVA 1-Phase 3-Wire Svc: ((Amps “A” + Amps “B”) X (Line to Line Volts) X TF) / 2000 = KVA 3-Phase 3-Wire Svc: ((Sum Amps “A”,”B” and “C”) X (Line to Line Volts) X TF) / = KVA **** Amps “B” is the average value of “A” and “C” **** 3-Phase 4-Wire Svc: Note: With 4-Wire Wye and 2 CT’s use the above and multiply the outcome by to prove for KVA

16 The Deep Dark Secrets of CT’s and VT’s
Presented By Larry Chapman

17 Current Transformers When and why do we use them?
What are their dangers and weaknesses? What are shunts all about and who needs them?   What information on the nameplate is pertinent? What about CT Ratios, Turns Ratios and Effective Ratios? What does a Burden Rating and/or a Burden Test have to do with anything? What is Rating Factor all about and who really gives a Rip?

18 Voltage or Potential Transformers
Last, but definitely not least, what happens to billing information from the meter and is the billing multiplier effected? Should meters still be protected from surges if VT’s are in use? Once we know and understand the answers to these questions CT’s and VT’s are a piece of cake. When and why do we use them? What are their dangers and weaknesses? What about Accuracy Class? What about Burden Ratings? How should they be protected and how can we be protected from them?

19 Current Transformer Discussion
Current Transformers are used to bring large loads down to a current that is save for us, as meter people, to deal with. Remember, A Meter is NOT a switch. Another fact to consider is the ability to handle loads above 200 amps in a meter socket. In today’s world we do have available Class 320 and Class 400 meters that can, when properly installed, handle their respective rated loads. Inadvertently install a Class 320 meter in a Class 200 meter socket and a potential fire hazard is created. Install a Class 200 meter in Class 320 meter socket and an overload on the meter can occur leading to not only inaccurate billing but also, eventually, another fire hazard.

20 More CT Discussion The class 400 meter is actually bolted in place and, if proper torque is applied when connected, is quite safe. How many service vehicles are carrying a torque wrench. If a fire is proven to start at the meter socket you can rest assured every lawyer in the country is coming after the deepest pockets involved. Other problems include special adapters for testing as well as the sometimes risky means of removing these meters for test. When a load exceeds the limits of a class 200-meter socket my recommendation will always be to use Current Transformers!

21 CT Discussions Continue
Keep in mind, meter people never deal with loads in excess of 10 amps and 120 volts to neutral anyway, the wires just bend easier. Current Transformers can hurt you. There is an extremely high voltage present when load is applied with the secondary circuit open. This voltage dissipates rapidly and would generally result in a burn or simply a shock not unlike an electric fence contact. In the event the CT is a bar type winding, used in all Primary Metering applications and some earlier secondary units, an open secondary can result in the destruction of the CT in a very noticeable manner.

22 Most CT’s in use today are “Window” or “Doughnut” type CT’s
 Most CT’s in use today are “Window” or “Doughnut” type CT’s. These devices will not fail with an open secondary. Actually CT’s removed after extended periods of open conditions have tested as accurately as they did when built.  The metering accuracy at the sights was terrible however due to the loss of indication on the respective phases involved.  For personnel safety a shunt across the secondary winding is provided with all CT’s when shipped. The shunt is in the closed position at the time of shipment to allow protection should the CT be installed and load applied prior to the installation of the meter socket and meter. This shunt MUST be opened after meter installation or loss of revenue occurs. The meter will NOT stop, as many believe. In a perfect world the best the meter could do is register 50% but it will register something and sometimes lull the unsuspecting in to going home “Fat, Dumb & Happy”, only to find later they have been giving Kilowatts away for years.  The shunt should, however, not be discarded. You may need it again someday.

23 Current Transformer Nameplates
The nameplate informs us of the CT’s Ratio, Burden Class, Thermal Rating, Accuracy Class and design of the secondary windings. Something to bear in mind is that attaching this nameplate is the last thing done before it goes out the door. There is no guarantee the correct nameplate was installed at the factory and all CT’s should have a recorded acceptance test run prior to installation. The ratio of a current transformer is simply a mathematical comparison of the current applied to the primary core of the CT and the output current of the secondary windings of the device. All CT Ratios are presented as ###/5. A 200/5 CT will deliver 5 Amperes of secondary current to a meter coil when the consumer’s total load through the CT is 200 Amperes.

24 CT Turns Ratios This brings us to Turns Ratio’s. By presenting the same load to a CT multiple times we “Effectively” divide that CT’s ratio by the number of times we presented the load. IE: If we pass 200 amperes through a CT once the ratio of the 200/5 CT remains 40/1. If we pass the same 200 amperes through the same CT it will be seen again and will present a second 5 amperes of secondary current to the meter coil. The meter does not know this is the same service load originally presented and simply adds another 5 amperes to its original 5 for a total of 10 amperes at the meter. The fact that we have lied to the meter will not effect the actual CT Ratio as it now sees amperes for a total of The meter now sees 5+5 amperes for a total of 10. A CT Ratio of 400/10 remains 40/1.

25 Effective CT Ratio Our problem is that we have tricked the CT into presenting the same load to the meter twice, and unless we really have a problem with this consumer, we do not want to bill him double. This is where the term “Effective Ratio” comes into the picture. A simple formula to determine this value is: CT Ratio Turns Primary  IE: As depicted above, a 200/5 CT with Double Primary equals: 200/5 or 40/1 This will yield an “Effective Ratio” of 20/1 and is the value required in any billing multiplier calculation.

26 Burden Class, Thermal Rating Factor and Burden Testing
The Burden Class and Thermal Rating are both required to be displayed by ANSI standards. All we really need to understand is if a CT is ANSI rated it will carry the burden of 50 feet of #12 wire and up to 4 electric meter current coils without a significant drop in accuracy. It will also carry (Rated Current X its Rating Factor) in a free air environment of around 86 Degrees forever, and do so, accurately. A Burden Test is something that should be conducted at any time you are at the metering sight. This test can help you find problems with a CT, or the wiring to it, before you actually start loosing revenue. Nothing on the nameplate or the test report sent with a CT indicates the accuracy at less than 10% of rated current. This is why we really do need to be concerned with the Rating Factor

27 Current Transformer Rating Factors
ALWAYS load a CT as far into the envelope of the high end as you possibly can. If you make a habit of buying class 20 transformer rated meters and push the CT up into the upper regions of its rating factor you can rest assured the meter is getting the best chance it can to see all the load. The only time this practice can cause any trouble is when using a mass memory device for load profile information. It is possible to saturate the recorder with more pulses than it can record in a given time period. This problem is addressable in the software of all the equipment. Just keep it in mind when setting things up. Recently some of the low end CT’s have been failing the burden test at “.1 Ohms”. The thing is, when you read the name plate, that’s all they are rated for. DON’T Buy cheap Stuff! You get what you pay for.

28 Voltage Transformers Voltage Transformers! Old guys call these things Potential Transformers and some people, in the business of selling metering equipment, call them obsolete for voltages below 600 Volts. If the customer requires any voltage in excess of 240 Volts, Phase to Phase, ABSOLUTELY ALWAYS use voltage transformers Volts exceeds the level required to induce the ionization of air and is an absolute bomb waiting to explode in a meter socket. All that is required is enough impurities in the air around a source of ignition and a voltage potential above 360 volts. At this voltage amplitude, given a source of ignition, breathable air will BURN!!

29 Voltage Transformers (Cont’d)
The arc generated by removing potential voltage from a meter can be that source. A 480-Volt arc will not stop burning until the wire is gone or the voltage potential is removed. #12 wire will not trip the breaker, or blow the fuse in a 500 KVA transformer but it sure will make a big, bright, blue ball of fire! Use of these things does require some extra effort and consideration. H1 and H2 are the designation symbols for the high voltage, or primary side, of a VT. X1 and X2 are the designation symbols for the low voltage, or secondary side, of a VT. Don’t make the mistake of connecting this guy backwards. There will be a VERY LOUD noise, a black cloud around the area it was mounted in. Stains in your shorts are also common if you are very close!

30 Loading & Protecting Voltage Transformers
A Voltage Transformer cannot carry significant load; it is designed to carry potential voltages only and is usually rated from 25 to 300 Watts. Fusing the primary side is common in Substations and recommended. Fusing the secondary side at 1 amp and providing voltage conditioning, in the form of some type of surge suppression, is also recommended on the secondary side. This can provide extra protection for the metering package and may help the new multi-function solid state equipment installed actually live for 10 years or so.

31 Accuracy of Voltage Transformers
The accuracy of voltage transformers as well as the burden rating is on the nameplate. The accuracy must be ANSI rated to use any voltage transformer for potential to a billing meter. The burden capability must provide for enough wattage to run any equipment intended at the metering sight. This includes recorders, remote telephone modems, meter shack lighting etc. Keep all these things in mind when determining the correct VT’s for a sight. All VT’s must carry the same accuracy class and burden rating. Don’t go out there and hang a 3 KVA house service transformer to make a metering VT. It’s not accurate enough, and besides it’s not legal!

32 VT Ratio’s & Multipliers
VT Ratio’s are usually marked as 7200/120 or 480/240 or 300/120 etc. This depicts the high or input voltage to the low or output voltage. Multipliers are either involved in the actual billing or in determining what register will be used on the meter to eliminate the need for a multiplier. In the case of Solid State metering they can be used to force the meter to use primary readings. With Mechanical meters always use the multiplier formula: Kr = Kh X Rs X Rr X TF Where TF = CTr X VTr Turns Primary at the CT With Solid State meters it is always best to leave the meter programmed at nameplate Meter Kh and apply transformer factor as the billing multiplier.

33 What do they mean? By Larry Chapman
Meter Form Numbers What do they mean? By Larry Chapman

34 Single Phase Single Phase 120 Volt, 2-Wire Service. Signs,
Lighting, phone booth Etc. Single Phase 240 Volt, 3-Wire Service. Probably 90% of the electric services in operation today.

35 The 1S Meter The 1S meter can only be used in a Single Phase, 2-Wire application. In today's world the only place these are practical is on a telephone booth or possibly sign lighting. Caution must be taken not to place a Form 2S meter in this service or to place this meter in a service requiring the Form 2S meter. The resultant errors are many and will be discussed during the course of this seminar. Suffice it to say both under billing and over billing can occur in either case. 

36 The 2S Meter The 2S meter can only be used in a Single Phase, 3-Wire application. This meter makes a compromise on voltage balance to allow metering a 3-Wire load with single element meter. Caution must be taken not to place a Form 2S meter in a 2-wire, 120-volt service or in a network metering application. This meter, in a network service, will return 86% on the delivered kilowatts if the load is perfectly balanced and power factor is unity.

37 Multipliers Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically.  Caution must be taken involving the use of register ratio's to adjust the billing multiplier. Work the appropriate multiplier formula for any installation this meter is involved with. Kh. X Rs X Rr X TF = BILLING MULTIPLIER. 10,000 The recommended Billing Multiplier with Solid State Meters is theTransformer Factor. CTr X Vtr = TF Turns Primary at the CT

38 The 3S Meter The 3S meter is the most versatile of all single-phase meters. Once the need for transformer rated metering is established this meter can be used on any 2 or 3-Wire single-phase load. Remember that a network service is not a single-phase load. At least one current transformer will always be involved with the use of this meter. Any time this meter is removed from a service the related Current and Voltage transformers should be tested as well as properly shunted or protected during the time the meter is removed. Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically.

39 3S Meter Continued Caution must be taken involving the use of register ratio's to adjust the billing multiplier. Work the appropriate multiplier formula for any installation this meter is involved with. Kh. X Rs X Rr X TF = BILLING MULTIPLIER. 10,000 The recommended Billing Multiplier with Solid State Meters is theTransformer Factor. CTr X Vtr = TF Turns Primary at the CT

40 4S Meters The 4S meter is the "Transformer Rated" version of the form 2S meter and makes all the same compromises. This meter is not one bit more accurate in service than a Form 3S meter. The only time it is needed is, in the event load wires are too large to pass through the Current Transformer more than once. As with any "Transformer Rated” installation, all Current and Voltage transformers should be tested as well as properly shunted or protected during the time the meter is removed.

41 4S Meters Continued Kh. X Rs X Rr X TF = BILLING MULTIPLIER. 10,000
Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically.  Caution must be taken involving the use of register ratio's to adjust the billing multiplier. Work the appropriate multiplier formula for any installation this meter is involved with. Kh. X Rs X Rr X TF = BILLING MULTIPLIER. 10,000 The recommended Billing Multiplier with Solid State Meters is theTransformer Factor. CTr X Vtr = TF Turns Primary at the CT

42 1-Phase, 3-Wire Network This application being described as a single phase service Is misleading, to say the least. It is not possible to build a network voltage without using a 3-Phase, 4-Wire, Wye transformer bank. Typically this service is used to provide a single phase solution for apartments, to better balance the loads on the service transformer, or a nearby home when a large “Wye” bank is already set to serve a school or business adjacent to the location.

43 12S Network Service The 12S is also common for use on a “Network Service”. Network metering is applied when only 2 phases of a 3-Phase 4-Wire WYE transformer are being used to provide service voltage to a consumer. IE: Apartment buildings, shops in a mall ETC. This commonly will provide only 208 Volts to the consumer and motorized equipment must be set up to run properly on this voltage. Never install a Form 2S meter in a service requiring a 12S meter. In any case the meter accuracy will be less than 75% registration.

44 5S Network Service The 5S meter is a "Transformer Rated" meter capable of metering Any and All loads. The absolute most versatile meter made. Make sure you follow an accepted wiring scheme. Use extreme caution when you get "Creative" with this meter.

45 Multipliers Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically.  Caution must be taken involving the use of register ratio's to adjust the billing multiplier. Work the appropriate multiplier formula for any installation this meter is involved with. Kh. X Rs X Rr X TF = BILLING MULTIPLIER. 10,000 The recommended Billing Multiplier with Solid State Meters is theTransformer Factor. CTr X Vtr = TF Turns Primary at the CT

46 3-Phase, 3-Wire Delta Not the most popular configuration today, but it still exists and must be metered Properly. There can never be a ground connection made on the “X0” bushing or any of the center tap “X2” bushings. Grounding the phase that is presented to the meter as the “Common” voltage is highly recommended and actually required in many states.

47 12S 3-Phase, 3-Wire Delta The 12S meter is used in 3-Phase 3-Wire services of all voltage ranges. Remember this is a 2-element meter and cannot be used on any 4-Wire application. On a 3-phase, 3-wire service it is common but not always required to ground the phase presented to the meter as the “Common” voltage phase. If this metering package is implemented on a 4-wire transformer connection the voltage phase not connected to the meter socket lugs remains hot, regardless if the meter is removed, and the resultant danger to personnel is very real. 

48 5S 3-Phase, 3-Wire Delta The 5S meter is a "Transformer Rated" meter capable of metering Any and All loads. The absolute most versatile meter made. Make sure you follow an accepted wiring scheme. Use extreme caution when you get "Creative" with this meter. 480 Volt 3-Wire Delta

49 3-Phase, 4-Wire Delta The popularity of this configuration is primarily thanks to “Rural Electrification”. The need for 3-Phase power at services that were largely single phase loads came when farming began to see a need for large motors in drying and moving grain, while the remaining 9 months of the year lighting and other household uses were dominant. This is also the only 3-Phase configuration that can be properly built using only 2 primary line phases and 2 single phase 3-Wire transformers. When these banks are built the transformer intended to carry the single phase portion of the load is larger in KVA rating. Proper sizing would depend on the total KVA of 3-Phase load as well as the total KVA of the single phase load. IE: An expected 15 KVA 3-Phase load and 10 KVA single phase load would require a 25 KVA transformer plus a 15 KVA transformer.

50 15S Meter The 15S meter is the self-contained version of the 8S "Transformer Rated" meter. This meter actually meters the single phase portion of a 3-Phase, 4-Wire, DELTA service exactly the same as a Form 2S meter does a normal Single Phase 3-Wire service with the left element. The "Wild Leg" is then metered by the right element of the meter. The most common mistake on the 4-Wire DELTA service is connecting the "Wild Phase" to the wrong coil of the meter. This voltage and current absolutely MUST be presented to the right element of the meter. The resultant loss of revenue is approximately 18% when this error is left uncorrected. 15S

51 15S Discussion A 14S mechanical meter installed in the 15S service can register anywhere from 40% to 140%, depending on the location of the “Wild Phase” and the consumers load balance. This problem has been known to cause severe discontent among the natives. A 16S mechanical meter installed in the 15S service will actually run correctly as long as the right voltage coil stands up to the high "Wild Phase" voltage. With mechanical meters the voltage coil failure is imminent, and once the failure occurs a loss of 1/3 of all consumption created by 3-Phase equipment will take place. Today's Solid State, "Multi-Form", meter is actually nothing more than a 16S meter. The fact that its voltage coils are wide range coils capable of being very accurate at all voltage ranges make it compatible with this application.

52 Multipliers Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically.  Caution must be taken involving the use of register ratio's to adjust the billing multiplier. Work the appropriate multiplier formula for any installation this meter is involved with. Kh. X Rs X Rr X TF = BILLING MULTIPLIER. 10,000 The recommended Billing Multiplier with Solid State Meters is the Transformer Factor. CTr X Vtr = TF Turns Primary at the CT

53 8S - 4,Wire Delta The 8S meter is a "Transformer Rated" meter that actually meters the single phase portion of a 3-Phase, 4-Wire, DELTA service exactly the same as a Form 2S meter does a normal Single Phase 3-Wire service with the left element. The "Wild Leg" is then metered by the right element of the meter. The most common mistake on the 4-Wire DELTA service is connecting the "Wild Phase" to the wrong coil of the meter. This voltage and current absolutely MUST be presented to the right element of the meter. The resultant loss of revenue is approximately 18% when this error is left uncorrected.

54 8S Meter Mix Ups A 6S meter installed in the 8S service will run forward at approximately 33%. This is due to the cross phasing on the B Phase coil and the loss of voltage on the C Phase coil. A 9S meter installed in the 8S service will actually run correctly as long as the right voltage coil stands up to the high "Wild Phase" voltage. With mechanical meters the voltage coil failure is imminent, and once the failure occurs a loss of 1/3 of all consumption created by 3-Phase equipment will take place. Today's Solid State, "Multi-Form", meter is actually nothing more than a 9S meter. The fact that its voltage coils are wide range coils capable of being very accurate at all voltage ranges make it compatible with this application. One thing the Solid State meter has brought us is the misconception of no longer needing to include step down voltage transformers in the wiring scheme. This is an extremely unintelligent thought process. Any voltage in excess of 240 Volts, Phase to Phase, should be reduced with Voltage Transformers. If management has no concern for the safety of the metering personnel it may help to stress the increased life span of the $ meter you just installed.

55 8S 480 Volt This is not very common, but it does exist. Please use VT’s when you get stuck with this service. When Mechanical meters were used in this application only two VT’s were required, however, the solid state meter will require the third VT to afford a voltage reference to neutral.

56 5S 4-Wire, Delta 5S meters are commonly used with 3-Phase, 3-Wire Delta configurations. Some of the early Solid State versions of this meter were not compatible for use in 4-Wire Delta applications. SEE Form 45S for info on these. As with any "Transformer Rated” installation, all Current and Voltage transformers should be tested as well as properly shunted or protected during the time the meter is removed. Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically.

57 45S Vs 5S, 4-Wire Delta The 45S meter is a Solid State "Transformer Rated" meter capable of metering Any and All loads. The absolute most versatile meter made. Note the difference in the voltage coil configuration between the 45S and 5S The 45S actually has 3 voltage coils instead of 2 like the 5S it replaces. This solved the early problems with 4-Wire DELTA wiring schemes.

58 More 45S When using VT’s with this meter it is still necessary to use the proper number. IE: 3-Phase, 3-Wire use 2 VT’s, 3-Phase, 4-Wire use 3 VT’s with the exception of a configuration that mimics the 6S meter.

59 The 24S Heaven Forbid! The 24S meter is the other "Transformer Rated" meter that should have never been made. It is the same engineering nightmare as the 7S with some major problems added in. These meters should be retired and replaced by an 8S wiring scheme whenever the chance presents itself. The 24S meter has 7 terminals. They are exactly the same bayonet configuration as the self-contained CLASS 200 Form 14S, 15S and 16S meters. This meter, plugged in to any one of those sockets will EXPLODE!

60 24S Headaches Keep in mind that if you inadvertently install a 14S, 15S, or 16S in this meter's wiring scheme it will also attempt to explode. The only difference is the wire to the meter socket in a transformer rated application is usually small enough that the meter wins. This will still cause a very bright blue flash and the potential for some serious burns to hands and faces. The 7S will run forward if inadvertently installed in this 3-Phase, 4-Wire, DELTA, 24S wiring scheme. Registration can vary from 40% to 140% if this occurs and the consumer will never believe you if you let him in on this little secret and then try to tell him his service was at the 40% level. Another thing to remember, the voltage coils of the 7S meter are commonly 120 Volts and will not live long under these conditions.

61 3-Phase, 4-Wire Wye This is the most versatile and practical transformer configuration in use today. Load balance, voltage requirements and safety are all much easier goals to meet with this configuration than any of the rest. It requires 3 primary phases to produce it and it provides 3 secondary phases of equal voltage to ground for consumer applications.

62 14S Meter The 14S meter is a “self-contained Class 200 meter that, like the "Transformer Rated" 6S, meter blows all engineering theory out the window. It is less accurate than the 16S in applications where voltage may vary but not enough to justify its replacement. This meter is not manufactured as a solid state meter. Its solid state replacement is called the Form (14S, 15S, 16S). As long as you remember the 14S, mechanical meter cannot live with a 4-Wire, DELTA service and a 15S, mechanical meter cannot live with a 4-Wire WYE service you should be OK. Wiring

63 14S (Continued) The most common error involving this meter is replacing it with a Form 15S meter. The 15S meter is for 3-Phase, 4-Wire, DELTA service. This error will result in a 15% Loss of Revenue with a balanced load. Always take voltage readings at the points in the socket where the meter makes contact. This will help you prevent a mistake of this nature. The 16S mechanical meter in this service is OK. NEVER install a Form 7S or 24S meter in this socket! It makes very loud noises!

64 16S Meter The 16S meter is the self-contained version of the 9S "Transformer Rated" meter. This meter, in Solid State form, is the only 7 terminal meter you need. If you study the self-contained 4-Wire meter socket diagrams you will see they are all identical. Remember the limiting factor of the 16S mechanical meter is the inability of the voltage coil to withstand the “Wild Phase” voltage. It cannot be installed in the 3-Phase, 4-Wire, DELTA service for this reason.

65 More 16S Notes A 14S meter installed in the 16S service is not a problem as they are both designed to do the same job. The configuration of the 15S mechanical meter will cause a loss of revenue equal to approximately 18%in the 4-Wire, WYE application.

66 You will Get Tired of This Slide
Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically.  Caution must be taken involving the use of register ratio's to adjust the billing multiplier. Work the appropriate multiplier formula for any installation this meter is involved with. Kh. X Rs X Rr X TF = BILLING MULTIPLIER. 10,000 The recommended Billing Multiplier with Solid State Meters is theTransformer Factor. CTr X Vtr = TF Turns Primary at the CT

67 5S With Wye Services 5S or 45S meters used with Wye services can use several combinations. Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically. One More

68 6S Meters The 6S meter is a "Transformer Rated" meter that blows all engineering theory out the window. It is less accurate than the 9S in applications where voltage may vary and the billing multiplier is large. Contrary to some "Prune Peddlers" statements, replacement of this meter with the 9S is not necessary unless it is on a primary metering sight or the multiplier exceeds Once these criteria are met the change may well pay for itself. 277/480 Wye

69 6S (Continued) The most common error with a 6S is forgetting the jumper from neutral to the #17 position, the second connection down on the right side of the socket, when wiring the socket at the job sight. The second most common error is installing one of the other 13 terminal meters in its place. A 36S meter installed in the 6S service will run correctly and the only danger is damage to the "KYZ" output if it is used.

70 More 6S Concerns An 8S meter installed in the 6S service will meter approximately 86% of the consumption on phases A & B and have no potential at phase C causing the loss of all revenue created by C phase. A 9S meter installed in the 6S service has a loss of potential at C phase plus the fact that B phase current is presented to C phase voltage on the center element. The end result of this problem is accurate registration for A phase, 50% negative registration for B phase, and no registration for C phase. The most disturbing fact of any of these conditions is that in all cases, with a balanced load, the meter will run forward.

71 Still the 6S The onset of today's Solid State, "Multi-Form", meter has also caused some confusion. The 6S meter wiring scheme must have a 6S or 36S meter installed. The only exceptions to this is are meters from General Electric and Itron that are actually 9S meters with the programming capability of being told it is living under 6S conditions. ANSII dubs this wiring scheme a 46S but the meter manufacturers have chosen to ignore that little technicality. The socket MUST be re-wired in accordance with the manufacturers respective wiring diagrams. The only time this trick is recommended is when you are dealing with a primary metering application and do not have the option of adding a Voltage Transformer to allow use of the proper 9S wiring scheme. In reality this was a very dumb idea !!!

72 36S Meter The 36S meter is actually a 6S "Transformer Rated" meter with all voltage returns connected to 1 common return. It is less accurate than the 9S in applications where voltage may vary and the billing multiplier is large.   The most common error with a 36S is replacing it with a form 6S and forgetting the jumper from neutral to the 6th position 7 center terminals, when wiring the socket at the job sight.

73 More 36S The second most common error is installing one of the other 13 terminal meters in its place. An 8S meter installed in the 36S service will meter approximately 86% of the consumption on phases A & B and have no potential at phase C causing the loss of all revenue created by C phase. A 9S meter installed in the 36S service has a loss of potential at C phase plus the fact that B phase current is presented to C phase voltage on the center element. The end result of this problem is accurate registration for A phase, 50% negative registration for B phase, and no registration for C phase. Just remember that in any combination, with a balanced load, the meter will run forward and lose money.

74 Even More 36S The onset of today's Solid State, "Multi-Form", meter has caused some confusion. The 36S meter wiring scheme must have a 36S meter installed. Adding a ground wire to the 6th position will allow replacement with a 6S As with any "Transformer Rated” installation, all Current and Voltage transformers should be tested as well as properly shunted or protected during the time the meter is removed. Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically.

75 The 7S Disaster The 7S meter is a "Transformer Rated" meter that should have never been made. It is the same engineering nightmare as the 6S with some major problems added in. These meters should be retired and replaced by a 9S wiring scheme whenever the chance presents itself. The 7S meter has 7 terminals. They are exactly the same bayonet configuration as the self-contained CLASS 200 Form 14S, 15S and 16S meters. This meter, plugged in to any one of those sockets will EXPLODE!  

76 More 7S Another interesting concern is that if you inadvertently install a 14S, 15S, or 16S in this meter's wiring scheme it will also attempt to explode. The only difference is the wire to the meter socket in a transformer rated application is usually small enough that the meter wins. This will still cause a very bright blue flash and the potential for some serious burns to hands and faces, not to mention the possible need for an underwear change. Installing a 24S in this socket will cause the meter to register approximately 86% of the consumption on phases A & B and have no potential at phase C, causing the loss of all revenue created by C phase. Actually the same problem as installing the 8S in the 6S application.

77 Multipliers Make sure any automatic shunting devices in the meter socket are working properly. A closed shunt after the meter is set in place does not stop the meter. It only slows it down drastically.  Caution must be taken involving the use of register ratio's to adjust the billing multiplier. Work the appropriate multiplier formula for any installation this meter is involved with. Kh. X Rs X Rr X TF = BILLING MULTIPLIER. 10,000 The recommended Billing Multiplier with Solid State Meters is theTransformer Factor. CTr X Vtr = TF Turns Primary at the CT

78 The 9S Meter The 9S meter is a "Transformer Rated" meter that can actually meter any service known when wired properly. The only limiting factor of the 9S meter is the voltage coil's ability to exist with whatever voltage is applied. The Solid State version of this meter, with wide range voltage transformers, has revolutionized the metering industry. Called the "Multi-Form 8S-9S" meter, many “Prune Peddlers” have misrepresented it as the replacement meter for all 13 terminal metering applications. This is not the case.

79 9S - 277/480 Wye The 4-Wire Wye 277/480 Volt installations should all use VT’s to allow maximum protection at the meter socket. Just keep in mind that the possibility of miswiring the installation increases dramatically when we add 12 more connection points to the combination. The “Two Sockets-Two Meters” VT Pack works very well in this application. Keep in mind these VT’s are only rated at 90VA, so do not utilize them to energize additional equipment. IE: Recorders, external AMR devices or load control equipment.

80 9S Discussion General Electric has the new KV Meter that does have the capability of replacing any 13 terminal meter, however you must adhere to the wiring schemes and programming requirements set forth in their "Fitzall Applications Manual". A 6S meter installed in the 9S service will run forward at approximately 33%. This is due to the cross phasing on the B Phase coil and the loss of voltage on the C Phase coil. An 8S meter installed in the 9S service will create a loss of about 18% due to the single phase element of the meter not having a neutral reference. 9S meters should not be confused with 10S meter. The difference is the 9S has a single voltage common at the right most position of the 7 center terminals. The 10S meter has the voltage common of each coil separated and connected to the 5th, 6th, and 7th terminals respectively.

81 It’s all about YOUR personal Safety !!!!!!!!
9S / 10S Discussion    FORM 10S The 10S meter was designed for use as a reactive meter, either a KVAR meter or a KQ meter and is not used in the solid state world since reactive data is something the solid state meter easily provides. Those of you involved in substation or power plant metering may still run across this meter but I suspect it is gradually being replaced and phased out. The 9S meter will probably become the standard meter base for Polyphase applications in the future. There is already a class 200 form 9S meter available for use with the "Two Sockets Two Meters" companies’ self-contained metering application. As these things develop I am certain new form numbers will be assigned to help prevent confusion, but for now just watch for them. Again, do not accept the misconception that we no longer need to include step down voltage transformers in the wiring scheme. Any voltage in excess of 240 Volts, Phase to Phase, should be reduced with Voltage Transformers. It’s all about YOUR personal Safety !!!!!!!!


Download ppt "Metering In Today’s World"

Similar presentations


Ads by Google