Tutorial: Mechanic - electrician Topic: Basics of electrical engineering the 2nd. year Protection in electric networks Prepared by: Škarka Miloš Projekt.

Similar presentations


Presentation on theme: "Tutorial: Mechanic - electrician Topic: Basics of electrical engineering the 2nd. year Protection in electric networks Prepared by: Škarka Miloš Projekt."— Presentation transcript:

1

2 Tutorial: Mechanic - electrician Topic: Basics of electrical engineering the 2nd. year Protection in electric networks Prepared by: Škarka Miloš Projekt Anglicky v odborných předmětech, CZ.1.07/1.3.09/04.0002 je spolufinancován Evropským sociálním fondem a státním rozpočtem České republiky.

3  Injury by electric current – physiological effect of electric current coming through a body of a person or an animal  Basic protection – protection against an injury by electric current in a failure-free state  Protection in the case of a malfunction – protection against an injury by electric current during one malfunction  Dangerous animate part – an animate part, which could cause an injury by electric current in certain conditions  Basic insulation – insulation of dangerous animate parts providing basic protection  Additional insulation – separate insulation used for basic insulation, to provide protection in case of a malfunction  Double insulation – insulation containing basic and additional insulation  Links – electric connections between conductive parts for potential balancing

4  Animate part – conductor of conductive parts designed for voltage in normal operation including the central conductor  Inanimate part is conductive part of an electric device, which can be touched and where there is usually no voltage, but where can a dangerous contact voltage occur because of a malfunction (for example metal casing of a distributor).

5  Dangerous contact voltage is voltage (or a variance of potentials), which can cause an injury by electric current to a person or an animal contacting an inanimate part during a malfunction. Its size depends on the type of environment, in which this contact occurs (ČSN 33 2000-4-41).

6 Allowed contact voltage is a part of grounding system voltage opposite to the ground, which can be crossed over by a human in distance from hands to feet (horizontally 1m).

7 Amount of the allowed contact voltage depends not only on a purpose of its use and on an environment, but even on a duration of a malfunction. The shorter the duration of the contact voltage is, the higher the contact voltage can be. Allowable values of the permanently allowed contact voltage at the device up to 1000V are mentioned in the following chart. Environmentcontact with parts (in operation) Safe low voltage of animate parts [V] AlternatingDirect NormalAnimate50100 Inanimate50120 Dangerous *)Animate2560 Inanimate50120 Extremely Dangerous Animate1225 Inanimate2560 *) It can be also specified differently in the regulation, if the sum of conditions (determining or influencing danger of an injury caused by an electric current) demands it

8  Normal – ordinary; cold; dusty (if dust is not conductive and not flammable). Its character prevents an injury by electric current.  Dangerous – hot, wet (even temporarily), dusty (if dust is conductive and not flammable with increased corrosive aggression), with shocks, outdoor places with mechanical damage and conductive environment. These are those places, where there is a temporary or permanent danger of an injury caused by electric current because of external effects.  Extremely dangerous – wet, with extreme corrosive aggression, places, where there is danger of an injury greatly increased by adverse conditions (water, kettles and metal tanks, narrow spaces with metal materials, healthcare facilities or special regulations for specific protection). The danger of an injury is even more increased because of special conditions and outer effects

9  Protection against a dangerous contact with animate parts Prevents passing of electric current through a body of a person or an animal, or the current is reduced to the safe amount  Protection against a dangerous contact with inanimate parts Prevents passing of electric current through a body of a person or an animal, or the current is reduced to the safe amount or the device in case of a malfunction automatically disconnects from the source.  Protection against a dangerous contact with animate and inanimate parts Voltage in animate parts can never exceed the safe amount  -

10  Inanimate part  Dangerous contact voltage  Allowed contact voltage of inanimate parts

11  types of environment  Give examples

12  www.wikipedia.cz www.wikipedia.cz  www.vosaspsekrizik.cz/cs/download/padesat ka/ochrana-dotyk.pdf www.vosaspsekrizik.cz/cs/download/padesat ka/ochrana-dotyk.pdf  Elektro v praxi, 1 část, Solid Team